The ideal vapour compression cycle

Components (compressor, condenser, expansion device, evaporator), the four processes, the pressure-enthalpy (p-h) diagram, and the equations for refrigeration effect, work, heat rejected and COP.

Our notes

2 min read

Components

  1. Compressor: raises the refrigerant vapour from evaporator pressure to condenser pressure (reciprocating, rotary, scroll, screw or centrifugal).
  2. Condenser: the hot vapour gives heat to the surroundings (air or water) and condenses to liquid.
  3. Expansion device: a throttling valve or capillary tube drops the pressure; some liquid flashes to vapour and the temperature falls.
  4. Evaporator: the cold, low-pressure refrigerant absorbs heat from the space or product and evaporates.

The four processes (ideal cycle)

State changeProcessNotes
1 to 2Isentropic compressionSaturated vapour at evaporator pressure → superheated vapour at condenser pressure (s₂ = s₁)
2 to 3Constant-pressure heat rejectionDesuperheating, then condensing to saturated liquid
3 to 4ThrottlingConstant enthalpy (h₄ = h₃); irreversible; pressure and temperature fall; a liquid-vapour mixture leaves
4 to 1Constant-pressure heat absorptionEvaporation to saturated vapour

The p-h diagram

Refrigeration engineers use the pressure-enthalpy diagram (pressure on a log scale against enthalpy):

  • The saturation dome: saturated liquid line on the left, saturated vapour line on the right, critical point at the top.
  • Left of the dome: subcooled liquid; inside: wet mixture; right: superheated vapour.
  • The ideal cycle is a simple shape: a horizontal line at low pressure (evaporation, 4 to 1), a curve up along a constant-entropy line (compression, 1 to 2), a horizontal line at high pressure (condensation, 2 to 3) and a vertical line down (throttling, 3 to 4, constant h).

The horizontal distances give the energies directly, which is why the p-h diagram is preferred.

Steady-flow equations (per kg of refrigerant)

Using the steady-flow energy equation with negligible kinetic and potential energy changes:

  • Refrigeration effect: q_L = h₁ − h₄
  • Compressor work: w = h₂ − h₁
  • Heat rejected: q_H = h₂ − h₃
  • COP = (h₁ − h₄) ÷ (h₂ − h₁)
  • Energy check: q_H = q_L + w.

For a mass flow rate m (kg/s): Q_L = m q_L (kW), W = m w, Q_H = m q_H.

  • Mass flow for a given load: m = Q_L ÷ (h₁ − h₄).
  • Volume flow at compressor inlet = m × v₁ (v₁ = specific volume of suction vapour); this sets the compressor size.

Why throttling

Throttling is cheap, simple and controllable. The cost is lost refrigeration effect (h₄ is higher than it would be with isentropic expansion) and a little more work per unit cooling. The loss is called the throttling loss.

Quality after throttling

The fraction of vapour leaving the valve: x₄ = (h₄ − h_f) ÷ h_fg at evaporator pressure. Flash vapour does no useful cooling, so a low x₄ is better (subcooling the liquid reduces it).

Exams usually ask: sketch the vapour compression cycle on p-h and T-s diagrams; name the components and processes; write the equations for refrigeration effect, work, heat rejected and COP.

Common mistake: treating throttling as isentropic. Throttling keeps enthalpy constant (h₄ = h₃) and increases entropy.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.