MEG 407 · Principles of Air-conditioning and Refrigerating Engineering
Our notes
2 min readThe problem
An ideal vapour compression refrigerator uses R-134a between an evaporator pressure of 0.14 MPa and a condenser pressure of 0.8 MPa. The mass flow rate is 0.05 kg/s. Find the refrigeration capacity, compressor power, heat rejected, COP and the quality after throttling.
Step 1: states from R-134a tables (rounded)
| State | Condition | Values |
|---|---|---|
| 1 | Saturated vapour at 0.14 MPa (about −18.8°C) | h₁ = 239.2 kJ/kg, s₁ = 0.9446 kJ/kg K, v₁ = 0.1400 m³/kg |
| 2 | Superheated at 0.8 MPa with s₂ = s₁ | h₂ = 275.4 kJ/kg (by interpolation; about 39°C) |
| 3 | Saturated liquid at 0.8 MPa (about 31.3°C) | h₃ = 95.5 kJ/kg |
| 4 | Throttled to 0.14 MPa | h₄ = h₃ = 95.5 kJ/kg |
At 0.14 MPa the tables also give h_f = 27.1 kJ/kg and h_fg = 212.1 kJ/kg.
Step 2: per kg
- q_L = h₁ − h₄ = 239.2 − 95.5 = 143.7 kJ/kg
- w = h₂ − h₁ = 275.4 − 239.2 = 36.2 kJ/kg
- q_H = h₂ − h₃ = 275.4 − 95.5 = 179.9 kJ/kg
Check: q_L + w = 143.7 + 36.2 = 179.9. ✓
Step 3: rates
- Refrigeration capacity Q_L = 0.05 × 143.7 = 7.19 kW = 7.19 ÷ 3.517 = 2.04 TR.
- Compressor power W = 0.05 × 36.2 = 1.81 kW.
- Heat rejected Q_H = 0.05 × 179.9 = 9.00 kW.
- COP = 143.7 ÷ 36.2 = 3.97.
Step 4: quality after throttling
x₄ = (h₄ − h_f) ÷ h_fg = (95.5 − 27.1) ÷ 212.1 = 68.4 ÷ 212.1 = 0.32. About a third of the refrigerant is already vapour when it enters the evaporator.
Step 5: compare with Carnot
Carnot COP between the saturation temperatures: T_L = 273.15 − 18.8 = 254.35 K; T_H = 273.15 + 31.3 = 304.45 K.
COP_Carnot = 254.35 ÷ (304.45 − 254.35) = 254.35 ÷ 50.10 = 5.08.
The ideal vapour compression cycle reaches 3.97 ÷ 5.08 = 78% of Carnot. The shortfall comes from the throttling loss and from the superheat after compression (heat rejected above T_H).
Step 6: compressor suction volume
Volume flow = m × v₁ = 0.05 × 0.1400 = 0.0070 m³/s = 7.0 L/s = 25.2 m³/h. For a reciprocating compressor with a volumetric efficiency of 80%, the swept volume rate must be 7.0 ÷ 0.8 = 8.75 L/s.
Turning it round: sizing for a load
A cold room needs 10 kW with the same cycle. m = 10 ÷ 143.7 = 0.0696 kg/s; compressor power = 0.0696 × 36.2 = 2.52 kW. Check: 10 ÷ 3.97 = 2.52 kW. ✓
Exam technique
- Draw the p-h sketch and number the states.
- Write the known property at each state (pressure or temperature plus one more).
- Use s₂ = s₁ and h₄ = h₃.
- Interpolate carefully in the superheat table (show the working).
- Check with q_H = q_L + w.
Exams usually ask: complete analyses like this one for R-134a, R-22, R-717 (ammonia) or R-12 with property tables or a p-h chart; find capacity in kW and tons, power, COP and swept volume.
Common mistake: using h_g at the condenser pressure for h₂. State 2 is superheated: find it in the superheat table at the condenser pressure with s₂ = s₁.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
University Physics Volume 2, 4.3 Refrigerators and Heat Pumps
(opens openstax.org in a new tab)
OpenStax, University Physics Volume 2, 4.3 Refrigerators and Heat Pumps, CC BY-NC-SA 4.0 · licence
Watch
-
Best pick Refrigeration Cycle Example
6 min · ≈ 27 MB · about ₦15
(opens youtube.com in a new tab)
-
Calc Vapor Compression Refrigeration Cycle R134a
7 min · ≈ 32 MB · about ₦18
(opens youtube.com in a new tab)
-
Refrigeration - Schematic and a Pressure Enthalpy Chart
9 min · ≈ 41 MB · about ₦23
(opens youtube.com in a new tab)
-
Lecture -18 Worked Out Examples 1
1 h · ≈ 270 MB · about ₦152
(opens youtube.com in a new tab)
We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.