Worked analysis of a vapour compression cycle

A complete R-134a cycle: reading states from tables, refrigeration capacity, compressor power, heat rejected, COP, quality, tonnage, comparison with Carnot and volumetric flow.

Our notes

2 min read

The problem

An ideal vapour compression refrigerator uses R-134a between an evaporator pressure of 0.14 MPa and a condenser pressure of 0.8 MPa. The mass flow rate is 0.05 kg/s. Find the refrigeration capacity, compressor power, heat rejected, COP and the quality after throttling.

Step 1: states from R-134a tables (rounded)

StateConditionValues
1Saturated vapour at 0.14 MPa (about −18.8°C)h₁ = 239.2 kJ/kg, s₁ = 0.9446 kJ/kg K, v₁ = 0.1400 m³/kg
2Superheated at 0.8 MPa with s₂ = s₁h₂ = 275.4 kJ/kg (by interpolation; about 39°C)
3Saturated liquid at 0.8 MPa (about 31.3°C)h₃ = 95.5 kJ/kg
4Throttled to 0.14 MPah₄ = h₃ = 95.5 kJ/kg

At 0.14 MPa the tables also give h_f = 27.1 kJ/kg and h_fg = 212.1 kJ/kg.

Step 2: per kg

  • q_L = h₁ − h₄ = 239.2 − 95.5 = 143.7 kJ/kg
  • w = h₂ − h₁ = 275.4 − 239.2 = 36.2 kJ/kg
  • q_H = h₂ − h₃ = 275.4 − 95.5 = 179.9 kJ/kg

Check: q_L + w = 143.7 + 36.2 = 179.9. ✓

Step 3: rates

  • Refrigeration capacity Q_L = 0.05 × 143.7 = 7.19 kW = 7.19 ÷ 3.517 = 2.04 TR.
  • Compressor power W = 0.05 × 36.2 = 1.81 kW.
  • Heat rejected Q_H = 0.05 × 179.9 = 9.00 kW.
  • COP = 143.7 ÷ 36.2 = 3.97.

Step 4: quality after throttling

x₄ = (h₄ − h_f) ÷ h_fg = (95.5 − 27.1) ÷ 212.1 = 68.4 ÷ 212.1 = 0.32. About a third of the refrigerant is already vapour when it enters the evaporator.

Step 5: compare with Carnot

Carnot COP between the saturation temperatures: T_L = 273.15 − 18.8 = 254.35 K; T_H = 273.15 + 31.3 = 304.45 K.
COP_Carnot = 254.35 ÷ (304.45 − 254.35) = 254.35 ÷ 50.10 = 5.08.
The ideal vapour compression cycle reaches 3.97 ÷ 5.08 = 78% of Carnot. The shortfall comes from the throttling loss and from the superheat after compression (heat rejected above T_H).

Step 6: compressor suction volume

Volume flow = m × v₁ = 0.05 × 0.1400 = 0.0070 m³/s = 7.0 L/s = 25.2 m³/h. For a reciprocating compressor with a volumetric efficiency of 80%, the swept volume rate must be 7.0 ÷ 0.8 = 8.75 L/s.

Turning it round: sizing for a load

A cold room needs 10 kW with the same cycle. m = 10 ÷ 143.7 = 0.0696 kg/s; compressor power = 0.0696 × 36.2 = 2.52 kW. Check: 10 ÷ 3.97 = 2.52 kW. ✓

Exam technique

  1. Draw the p-h sketch and number the states.
  2. Write the known property at each state (pressure or temperature plus one more).
  3. Use s₂ = s₁ and h₄ = h₃.
  4. Interpolate carefully in the superheat table (show the working).
  5. Check with q_H = q_L + w.

Exams usually ask: complete analyses like this one for R-134a, R-22, R-717 (ammonia) or R-12 with property tables or a p-h chart; find capacity in kW and tons, power, COP and swept volume.

Common mistake: using h_g at the condenser pressure for h₂. State 2 is superheated: find it in the superheat table at the condenser pressure with s₂ = s₁.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.