MEG 407 · Principles of Air-conditioning and Refrigerating Engineering

The actual cycle and operating conditions

Subcooling, superheating, pressure drops and non-isentropic compression, compressor isentropic efficiency, the standard rating cycle, and how evaporator and condenser temperatures change capacity and COP.

Our notes

3 min read

How the real cycle differs

  1. Superheating at the evaporator exit: the vapour is a few kelvin above saturation (usually set to about 5 K by the expansion valve) so no liquid enters the compressor. Useful superheat inside the space adds a little refrigeration effect; superheat picked up in the suction line outside the space is wasted.
  2. Subcooling of the liquid below its saturation temperature in the condenser or a subcooler: lowers h₃ = h₄, increases the refrigeration effect and reduces flash gas: good.
  3. Pressure drops in the evaporator, condenser and pipes: the compressor must work across a larger pressure ratio.
  4. Non-isentropic compression: friction and heat transfer make the real exit enthalpy higher than h₂s.
  5. Heat gains in the suction line, heat losses from the compressor.

Compressor isentropic efficiency

η_s = (h₂s − h₁) ÷ (h₂ − h₁), so the actual exit enthalpy is h₂ = h₁ + (h₂s − h₁) ÷ η_s.
Worked example. Using the cycle of the previous topic with η_s = 0.80:

  • Actual work = 36.2 ÷ 0.80 = 45.25 kJ/kg; h₂ = 239.2 + 45.25 = 284.45 kJ/kg.
  • COP = 143.7 ÷ 45.25 = 3.18 (compared with 3.97 ideal).
  • Heat rejected = 284.45 − 95.5 = 188.95 kJ/kg. Check: 143.7 + 45.25 = 188.95. ✓

Worked example: effect of subcooling

If the liquid is subcooled so h₃ = 87.0 kJ/kg (instead of 95.5), the refrigeration effect becomes 239.2 − 87.0 = 152.2 kJ/kg (5.9% more) for the same compressor work (36.2), so COP = 152.2 ÷ 36.2 = 4.20. (The liquid enthalpy is taken as that of saturated liquid at the subcooled temperature, a standard approximation.)

The standard rating cycle

To compare compressors and refrigerants fairly, manufacturers quote capacity and COP at fixed standard rating conditions. A traditional one is an evaporator at −15°C and a condenser at 30°C, with stated subcooling and superheat. Modern standards (ASHRAE, ISO, AHRI) set conditions for each type of equipment (for example air-conditioners are rated at specified indoor and outdoor dry-bulb and wet-bulb temperatures). A machine's actual capacity differs when it runs at other conditions.

Effect of operating conditions

ChangeRefrigeration effect per kgMass flow (fixed compressor)CapacityCOP
Lower evaporator temperatureFalls slightlyFalls (the suction vapour is less dense)Falls sharplyFalls
Higher condenser temperatureFalls (more flash gas)Falls a little (higher pressure ratio cuts volumetric efficiency)FallsFalls
More subcoolingRisesSameRisesRises

Why capacity falls so much at low evaporator temperature: the suction vapour has a larger specific volume (less dense), so a fixed-displacement compressor pumps less mass per second.
Worked example (volumetric effect). If suction specific volume rises from 0.14 to 0.20 m³/kg when the evaporator temperature is lowered, the mass flow of a compressor handling 7.0 L/s falls from 0.050 to 0.035 kg/s, a 30% loss of mass flow before counting the smaller refrigeration effect.

Practical lessons (relevant to Nigeria)

  • Install outdoor units in shade with free air flow; clean condenser coils (dust and harmattan haze clog them).
  • Do not set the thermostat lower than needed.
  • Low voltage and voltage swings overheat compressors: use stabilisers or inverter units designed for wide voltage ranges.

Exams usually ask: sketch the actual cycle on a p-h diagram; explain the effects of superheating, subcooling and pressure drops; compute COP with a given isentropic efficiency; explain the effect of evaporator and condenser temperatures.

Common mistake: assuming superheat always improves performance. Superheat gained inside the cooled space adds useful effect, but superheat from the surroundings in the suction line only raises compressor work and discharge temperature.