MEG 407 · Principles of Air-conditioning and Refrigerating Engineering
Our notes
3 min readRequirements of a good refrigerant
Thermodynamic: suitable saturation pressures (evaporator pressure above atmospheric so air does not leak in; condenser pressure not too high), high latent heat, low specific volume of vapour (smaller compressor), high critical temperature, low freezing point.
Chemical and safety: non-toxic, non-flammable, stable, non-corrosive, compatible with oil and materials, easy leak detection.
Environmental: zero ozone depletion potential (ODP), low global warming potential (GWP).
Economic: cheap and available.
No refrigerant meets all of these; selection is a compromise.
Designation (ASHRAE Standard 34)
For halocarbons derived from methane or ethane, R-xyz with:
- x = number of carbon atoms − 1 (omitted when zero),
- y = number of hydrogen atoms + 1,
- z = number of fluorine atoms; the rest of the bonds are chlorine.
Worked examples.
- CCl₂F₂: C 1 → 0, H 0 → 1, F 2 → R-12.
- CHClF₂: C 1 → 0, H 1 → 2, F 2 → R-22.
- C₂H₂F₄: C 2 → 1, H 2 → 3, F 4 → R-134 (the "a" marks the isomer used: R-134a).
- CH₂F₂: 0, 3, 2 → R-32.
- Propane C₃H₈: 2, 9, 0 → R-290.
Other series: R-4xx zeotropic blends (R-404A, R-407C, R-410A), R-5xx azeotropic blends (R-502), R-6xx miscellaneous organics (R-600a isobutane), R-7xx inorganics: 700 + molar mass (R-717 ammonia, NH₃ = 17; R-718 water; R-744 carbon dioxide, CO₂ = 44).
Families
| Family | Examples | Status |
|---|---|---|
| CFCs | R-11, R-12 | Banned: high ODP |
| HCFCs | R-22 | Being phased out (developing countries: 97.5% cut by 2030, complete by 2040) |
| HFCs | R-134a, R-410A, R-404A, R-32 | No ODP but high GWP (R-410A about 2,090, R-134a about 1,430; R-32 about 675): being phased down |
| HFOs | R-1234yf, R-1234ze | Very low GWP, mildly flammable |
| Natural | R-717 ammonia, R-744 CO₂, R-290 propane, R-600a isobutane, R-718 water | ODP 0; GWP 0 to 3 (ammonia toxic; hydrocarbons flammable; CO₂ very high pressure) |
Safety classes (ASHRAE 34)
A letter for toxicity (A lower, B higher) and a number for flammability (1 none, 2L mildly, 2, 3 highly). R-134a and R-410A are A1; R-32 and R-1234yf A2L; R-290 and R-600a A3; ammonia B2L. Many new split ACs sold in Nigeria use R-32, and most new household fridges use R-600a: technicians must be trained for flammable refrigerants (no open flames, ventilation, correct charge sizes).
International rules (dated)
- Montreal Protocol (1987): phases out ozone-depleting substances (CFCs, then HCFCs). Nigeria is a party and runs phase-out plans through its National Ozone Office (Federal Ministry of Environment).
- Kigali Amendment (2016): phases down HFCs because of their GWP; developing countries such as Nigeria follow a later schedule (freeze in the mid-2020s, cuts after).
- Venting refrigerant is bad practice: recover and recycle.
Secondary refrigerants
Fluids that carry cold from the primary refrigerant's evaporator to the load without changing phase: chilled water (above 0°C), brines (calcium chloride or sodium chloride solutions) and glycols (ethylene or propylene glycol) for below 0°C. They keep the main refrigerant charge small and confined (good for toxic ammonia plants and large buildings).
Binary mixtures (blends)
- Azeotropic: boil at one temperature at a given pressure, like a pure substance (R-502).
- Zeotropic: the composition of liquid and vapour differ, so the temperature changes during evaporation at constant pressure: the temperature glide (R-407C has about 5 to 7 K). Leaks change the composition, so zeotropes must be charged as liquid.
- Near-azeotropic blends such as R-410A have a tiny glide.
Exams usually ask: list the requirements of a refrigerant; designate refrigerants from formulas; compare CFCs, HCFCs, HFCs and natural refrigerants; explain ODP, GWP and the Montreal and Kigali agreements; explain secondary refrigerants and temperature glide.
Common mistake: counting chlorine atoms in the R-number. Only C, H and F are counted; chlorine fills the remaining bonds.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Refrigerant
(opens en.wikipedia.org in a new tab)
Wikipedia, Refrigerant, CC BY-SA 4.0 · licence
-
Montreal Protocol
(opens en.wikipedia.org in a new tab)
Wikipedia, Montreal Protocol, CC BY-SA 4.0 · licence
-
Kigali Amendment
(opens en.wikipedia.org in a new tab)
Wikipedia, Kigali Amendment, CC BY-SA 4.0 · licence
-
Global warming potential
(opens en.wikipedia.org in a new tab)
Wikipedia, Global warming potential, CC BY-SA 4.0 · licence
-
UNEP Ozone Secretariat: the Montreal Protocol and Kigali Amendment
The treaty secretariat's own site: phase-out schedules for CFCs, HCFCs and HFCs, and each country's data (Nigeria included).
(opens ozone.unep.org in a new tab)
-
NPTEL: Refrigeration and Air Conditioning (IIT Kharagpur, whole course)
Forty lessons as free PDFs: refrigerants, vapour compression and multistage systems, absorption, air cycle, psychrometry, cooling loads and air-conditioning systems.
(opens nptel.ac.in in a new tab)
NPTEL, NPTEL: Refrigeration and Air Conditioning (IIT Kharagpur, whole course), CC BY-NC-SA 4.0 · licence
Watch
-
Best pick Refrigerant Types, Issues and Future
13 min · ≈ 59 MB · about ₦33
(opens youtube.com in a new tab)
-
The Hole - A film on the Montreal Protocol, narrated by Sir David Attenborough
5 min · ≈ 23 MB · about ₦13
(opens youtube.com in a new tab)
-
Climate 101: Ozone Depletion | National Geographic
3 min · ≈ 14 MB · about ₦8
(opens youtube.com in a new tab)
We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.