Requirements of a good refrigerant

Thermodynamic: suitable saturation pressures (evaporator pressure above atmospheric so air does not leak in; condenser pressure not too high), high latent heat, low specific volume of vapour (smaller compressor), high critical temperature, low freezing point.
Chemical and safety: non-toxic, non-flammable, stable, non-corrosive, compatible with oil and materials, easy leak detection.
Environmental: zero ozone depletion potential (ODP), low global warming potential (GWP).
Economic: cheap and available.
No refrigerant meets all of these; selection is a compromise.

Designation (ASHRAE Standard 34)

For halocarbons derived from methane or ethane, R-xyz with:

  • x = number of carbon atoms − 1 (omitted when zero),
  • y = number of hydrogen atoms + 1,
  • z = number of fluorine atoms; the rest of the bonds are chlorine.

Worked examples.

  • CCl₂F₂: C 1 → 0, H 0 → 1, F 2 → R-12.
  • CHClF₂: C 1 → 0, H 1 → 2, F 2 → R-22.
  • C₂H₂F₄: C 2 → 1, H 2 → 3, F 4 → R-134 (the "a" marks the isomer used: R-134a).
  • CH₂F₂: 0, 3, 2 → R-32.
  • Propane C₃H₈: 2, 9, 0 → R-290.

Other series: R-4xx zeotropic blends (R-404A, R-407C, R-410A), R-5xx azeotropic blends (R-502), R-6xx miscellaneous organics (R-600a isobutane), R-7xx inorganics: 700 + molar mass (R-717 ammonia, NH₃ = 17; R-718 water; R-744 carbon dioxide, CO₂ = 44).

Families

FamilyExamplesStatus
CFCsR-11, R-12Banned: high ODP
HCFCsR-22Being phased out (developing countries: 97.5% cut by 2030, complete by 2040)
HFCsR-134a, R-410A, R-404A, R-32No ODP but high GWP (R-410A about 2,090, R-134a about 1,430; R-32 about 675): being phased down
HFOsR-1234yf, R-1234zeVery low GWP, mildly flammable
NaturalR-717 ammonia, R-744 CO₂, R-290 propane, R-600a isobutane, R-718 waterODP 0; GWP 0 to 3 (ammonia toxic; hydrocarbons flammable; CO₂ very high pressure)

Safety classes (ASHRAE 34)

A letter for toxicity (A lower, B higher) and a number for flammability (1 none, 2L mildly, 2, 3 highly). R-134a and R-410A are A1; R-32 and R-1234yf A2L; R-290 and R-600a A3; ammonia B2L. Many new split ACs sold in Nigeria use R-32, and most new household fridges use R-600a: technicians must be trained for flammable refrigerants (no open flames, ventilation, correct charge sizes).

International rules (dated)

  • Montreal Protocol (1987): phases out ozone-depleting substances (CFCs, then HCFCs). Nigeria is a party and runs phase-out plans through its National Ozone Office (Federal Ministry of Environment).
  • Kigali Amendment (2016): phases down HFCs because of their GWP; developing countries such as Nigeria follow a later schedule (freeze in the mid-2020s, cuts after).
  • Venting refrigerant is bad practice: recover and recycle.

Secondary refrigerants

Fluids that carry cold from the primary refrigerant's evaporator to the load without changing phase: chilled water (above 0°C), brines (calcium chloride or sodium chloride solutions) and glycols (ethylene or propylene glycol) for below 0°C. They keep the main refrigerant charge small and confined (good for toxic ammonia plants and large buildings).

Binary mixtures (blends)

  • Azeotropic: boil at one temperature at a given pressure, like a pure substance (R-502).
  • Zeotropic: the composition of liquid and vapour differ, so the temperature changes during evaporation at constant pressure: the temperature glide (R-407C has about 5 to 7 K). Leaks change the composition, so zeotropes must be charged as liquid.
  • Near-azeotropic blends such as R-410A have a tiny glide.

Exams usually ask: list the requirements of a refrigerant; designate refrigerants from formulas; compare CFCs, HCFCs, HFCs and natural refrigerants; explain ODP, GWP and the Montreal and Kigali agreements; explain secondary refrigerants and temperature glide.

Common mistake: counting chlorine atoms in the R-number. Only C, H and F are counted; chlorine fills the remaining bonds.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.