MEG 407 · Principles of Air-conditioning and Refrigerating Engineering
Our notes
3 min readWhy more than one pressure
When the evaporator is very cold and the condenser hot (freezers at −30°C or lower, blast freezing of fish), a single stage gives:
- a very high pressure ratio, so poor volumetric efficiency and capacity,
- very high discharge temperatures that break down oil,
- a large flash gas fraction after throttling, and so a low COP.
Splitting the lift into stages fixes these.
Flash gas removal
Throttle the condenser liquid in two steps. At the intermediate pressure, a flash chamber separates the vapour formed (the flash gas) and sends it straight to the high-stage compressor, so the low-stage compressor and evaporator do not handle it. Only liquid goes on to the second expansion valve and the evaporator.
Intercooling
The superheated vapour leaving the low-stage compressor is cooled before the high stage, either in a water intercooler or by mixing with saturated vapour in the flash chamber. Compression near the saturated vapour line needs less work (isentropic lines spread out as superheat increases).
Two-stage compression with a flash chamber
States (R-134a, 0.14 MPa evaporator, 0.32 MPa flash chamber, 0.8 MPa condenser):
- Liquid from the condenser at 0.8 MPa: h = 95.5 kJ/kg.
- Throttled to 0.32 MPa (constant h): enters the flash chamber with h = 95.5.
- At 0.32 MPa: saturated liquid h_f = 55.2 kJ/kg, saturated vapour h_g = 251.9 kJ/kg.
Worked example: flash chamber balance
Fraction of vapour formed in the flash chamber:
x = (95.5 − 55.2) ÷ (251.9 − 55.2) = 40.3 ÷ 196.7 = 0.205.
So for each 1 kg circulated through the high-stage compressor, 0.205 kg is flash vapour that bypasses the low stage, and 0.795 kg of saturated liquid (h = 55.2) goes on to the evaporator.
Evaporator effect per kg of low-stage flow = h₁ − 55.2 = 239.2 − 55.2 = 184.0 kJ/kg, compared with 143.7 kJ/kg in the single-stage cycle: a 28% increase in cooling per kg reaching the evaporator.
Check by an energy balance on the chamber (mixing the low-stage compressor's flow is ignored here, as in a chamber that only separates): energy in = 1 × 95.5 = 95.5; energy out = 0.205 × 251.9 + 0.795 × 55.2 = 51.6 + 43.9 = 95.5 kJ. ✓
For a 20 kW evaporator load, the low-stage flow = 20 ÷ 184.0 = 0.1087 kg/s, and the high-stage flow = 0.1087 ÷ 0.795 = 0.1367 kg/s.
Choosing the intermediate pressure
A common first estimate for minimum total work is the geometric mean: p_i = √(p_evap × p_cond). Worked example. √(0.14 × 0.8) = √0.112 = 0.335 MPa, close to the 0.32 MPa used above. Each stage then has a pressure ratio of about 0.335 ÷ 0.14 = 2.39 instead of 0.8 ÷ 0.14 = 5.71 for one stage.
Multiple evaporators
One plant often serves loads at different temperatures (a freezer at −25°C and a chiller at 2°C):
- Individual expansion valves with back-pressure regulators: each warmer evaporator keeps its own higher pressure, then its vapour is throttled to the common suction pressure (simple but wasteful).
- Multiple compressors with each evaporator at its own suction pressure, combined with flash intercooling (more efficient).
Cascade systems
Two separate circuits with different refrigerants: the low-temperature circuit's condenser is the high-temperature circuit's evaporator (a cascade heat exchanger). Used for very low temperatures (−60°C to −100°C), for example CO₂ in the low stage and ammonia in the high stage.
Exams usually ask: explain why multistage systems are used; describe flash gas removal and intercooling; analyse a two-stage system with a flash chamber; describe multiple-evaporator and cascade systems.
Common mistake: sending the flash gas through the evaporator. Its purpose is to bypass the evaporator and low-stage compressor, saving work.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Cascade refrigeration
(opens en.wikipedia.org in a new tab)
Wikipedia, Cascade refrigeration, CC BY-SA 4.0 · licence
-
NPTEL: Refrigeration and Air Conditioning (IIT Kharagpur, whole course)
Forty lessons as free PDFs: refrigerants, vapour compression and multistage systems, absorption, air cycle, psychrometry, cooling loads and air-conditioning systems.
(opens nptel.ac.in in a new tab)
NPTEL, NPTEL: Refrigeration and Air Conditioning (IIT Kharagpur, whole course), CC BY-NC-SA 4.0 · licence
Watch
-
Best pick Intro Multistage Refrigeration with Intercooling
6 min · ≈ 27 MB · about ₦15
(opens youtube.com in a new tab)
-
Intro cascade refrigeration
3 min · ≈ 14 MB · about ₦8
(opens youtube.com in a new tab)
-
Industrial Refrigeration system Basics - Ammonia refrigeration working principle
9 min · ≈ 41 MB · about ₦23
(opens youtube.com in a new tab)
-
Lecture -12 Vapour Compression Refrigeration Systems(contd.)
1 h · ≈ 270 MB · about ₦152
(opens youtube.com in a new tab)
We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.