MEG 407 · Principles of Air-conditioning and Refrigerating Engineering
Our notes
3 min readPrinciple
In absorption refrigeration, the compressor is replaced by a thermal compressor: the low-pressure refrigerant vapour is absorbed into a liquid (the absorbent), the solution is pumped to high pressure (pumping a liquid takes very little work), and heat drives the refrigerant out of the solution again. Most of the energy input is heat, not electricity.
Components
| Component | Job |
|---|---|
| Evaporator | Refrigerant evaporates at low pressure, absorbing heat from the load |
| Absorber | Absorbent soaks up the vapour; this releases heat, which must be removed by cooling water |
| Pump | Lifts the strong solution to high pressure |
| Generator | Heat (steam, hot water, gas flame, solar or waste heat) boils refrigerant out of the solution |
| Rectifier (ammonia systems) | Removes water vapour carried with the ammonia |
| Condenser | Refrigerant condenses, rejecting heat |
| Expansion valves | For refrigerant and for the weak solution returning to the absorber |
| Heat exchanger | Weak hot solution preheats strong cold solution (improves COP) |
The two main pairs
| Ammonia-water | Lithium bromide-water | |
|---|---|---|
| Refrigerant | Ammonia (NH₃) | Water |
| Absorbent | Water | LiBr solution |
| Lowest temperature | Below 0°C (freezing and ice making) | Above 0°C only (water freezes): chilled water at about 5 to 7°C |
| Pressures | High | Very low (deep vacuum) |
| Special needs | Rectifier; ammonia is toxic | Crystallisation of LiBr if concentration gets too high; air leaks must be removed |
| Typical use | Industrial refrigeration, gas-fired caravan fridges | Large building air-conditioning chillers |
Maximum COP
An ideal absorption system is a reversible heat engine (between the source at T_s and surroundings at T₀) driving a reversible refrigerator (between T_L and T₀):
COP_max = (1 − T₀ ÷ T_s) × [T_L ÷ (T₀ − T_L)]
Worked example. Heat source at 120°C, surroundings at 30°C, cold space at 5°C:
- T_s = 393.15 K, T₀ = 303.15 K, T_L = 278.15 K.
- 1 − 303.15 ÷ 393.15 = 1 − 0.7711 = 0.2289.
- 278.15 ÷ 25 = 11.126.
- COP_max = 0.2289 × 11.126 = 2.55.
Real single-effect LiBr chillers reach about 0.6 to 0.8, double-effect about 1.0 to 1.3 (COP here is cooling ÷ heat input).
Advantages and limits
- Advantages: few moving parts (only a pump), quiet, little electricity, can use waste heat, steam, gas or solar heat; refrigerants with no ozone or climate harm.
- Limits: low COP, bulky and expensive, needs a heat supply and cooling water or cooling towers.
Where absorption fits in Nigeria
- Gas-fired plants and refineries with waste heat; buildings with combined heat and power from gas engines.
- Off-grid cold storage with solar thermal collectors or kerosene and gas fridges (the old kerosene vaccine fridges were absorption units, now replaced mostly by solar photovoltaic fridges).
- Where electricity is unreliable but gas or heat is cheap.
The Electrolux (diffusion) refrigerator
A three-fluid system (ammonia, water and hydrogen) with no pump: hydrogen keeps the total pressure equal throughout while allowing ammonia to evaporate at low partial pressure. Silent; used in hotel minibars and camping fridges.
Exams usually ask: describe the vapour absorption cycle with a diagram; compare ammonia-water and LiBr-water systems; derive and compute the maximum COP; compare absorption with vapour compression.
Common mistake: comparing absorption COP (cooling ÷ heat) directly with compression COP (cooling ÷ electrical work) and calling absorption "bad". Heat is usually cheaper than electricity and can be waste heat; the right comparison is in cost or primary energy.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Absorption refrigerator
(opens en.wikipedia.org in a new tab)
Wikipedia, Absorption refrigerator, CC BY-SA 4.0 · licence
-
NPTEL: Refrigeration and Air Conditioning (IIT Kharagpur, whole course)
Forty lessons as free PDFs: refrigerants, vapour compression and multistage systems, absorption, air cycle, psychrometry, cooling loads and air-conditioning systems.
(opens nptel.ac.in in a new tab)
NPTEL, NPTEL: Refrigeration and Air Conditioning (IIT Kharagpur, whole course), CC BY-NC-SA 4.0 · licence
Watch
-
Best pick Absorption Chiller, How it works - working principle hvac
11 min · ≈ 50 MB · about ₦28
(opens youtube.com in a new tab)
-
Intro Absorption Refrigeration
4 min · ≈ 18 MB · about ₦10
(opens youtube.com in a new tab)
-
Absorption Cycle Example
8 min · ≈ 36 MB · about ₦20
(opens youtube.com in a new tab)
We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.