MEG 407 · Principles of Air-conditioning and Refrigerating Engineering
Our notes
2 min readThe Clausius statement
"It is impossible to construct a device that operates in a cycle and produces no effect other than the transfer of heat from a lower-temperature body to a higher-temperature body." A refrigerator therefore needs work (or heat at a high temperature) as an input.
The reversed Carnot cycle
The ideal (most efficient possible) refrigerator between a cold reservoir at T_L and a hot reservoir at T_H runs a reversed Carnot cycle of four reversible processes:
- Isentropic compression (temperature rises from T_L to T_H).
- Isothermal heat rejection at T_H.
- Isentropic expansion (temperature falls from T_H to T_L).
- Isothermal heat absorption at T_L.
On a T-s diagram this is a rectangle: Q_L = T_L × Δs, Q_H = T_H × Δs, W = (T_H − T_L) × Δs.
Carnot COP
- Refrigerator: COP_R,Carnot = T_L ÷ (T_H − T_L)
- Heat pump: COP_HP,Carnot = T_H ÷ (T_H − T_L)
Temperatures must be in kelvin.
Worked example. A freezer compartment at −10°C in a kitchen at 40°C (the condenser side):
- T_L = 263.15 K, T_H = 313.15 K, difference = 50 K.
- COP_R = 263.15 ÷ 50 = 5.26.
- COP_HP = 313.15 ÷ 50 = 6.26. Check: COP_HP = COP_R + 1. ✓
Effect of temperatures
- Lowering T_L (colder freezing) reduces COP: at −20°C, COP = 253.15 ÷ 60 = 4.22, about 20% less than at −10°C.
- Raising T_H (hot surroundings, dirty condenser, unit in direct sun) reduces COP.
Lesson for design: keep the evaporator as warm and the condenser as cool as the job allows.
Second-law efficiency
Real systems are compared with the Carnot COP:
Second-law efficiency = COP_actual ÷ COP_Carnot.
Worked example. A real unit working between the same −10°C and 40°C has COP 2.9. Efficiency = 2.9 ÷ 5.26 = 55%.
Why the Carnot refrigerator is not built
- Isothermal heat transfer needs infinitely slow processes or infinite area.
- Isentropic compression of a wet mixture (in the two-phase region) damages compressors ("wet compression").
- Isentropic expansion of a mostly liquid mixture gives very little work, so a turbine is not worth its cost.
The practical vapour compression cycle changes these steps: it compresses dry vapour and replaces the expander with a throttling valve.
Reversible heat engine and refrigerator together
For an absorption system (see later), the ideal COP combines a Carnot engine running between the heat source and surroundings with a Carnot refrigerator. This is how the maximum COP of heat-driven refrigeration is found.
Exams usually ask: state the Clausius statement; derive the Carnot COP; compute Carnot COPs; explain why the reversed Carnot cycle is impractical and how the vapour compression cycle differs.
Common mistake: using degrees Celsius in the Carnot formula. With −10°C and 40°C in Celsius you would get a negative COP; always convert to kelvin.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Best pick University Physics Volume 2, 4.3 Refrigerators and Heat Pumps
(opens openstax.org in a new tab)
OpenStax, University Physics Volume 2, 4.3 Refrigerators and Heat Pumps, CC BY-NC-SA 4.0 · licence
-
University Physics Volume 2, 4.4 Statements of the Second Law of Thermodynamics
(opens openstax.org in a new tab)
OpenStax, University Physics Volume 2, 4.4 Statements of the Second Law of Thermodynamics, CC BY-NC-SA 4.0 · licence
-
University Physics Volume 2, 4.5 The Carnot Cycle
(opens openstax.org in a new tab)
OpenStax, University Physics Volume 2, 4.5 The Carnot Cycle, CC BY-NC-SA 4.0 · licence
-
Carnot cycle
(opens en.wikipedia.org in a new tab)
Wikipedia, Carnot cycle, CC BY-SA 4.0 · licence
-
OpenStax, University Physics Volume 2 (whole free textbook)
The whole book, free to read online or download as a PDF (the PDF is large: Wi-Fi).
(opens openstax.org in a new tab)
OpenStax, OpenStax, University Physics Volume 2 (whole free textbook), CC BY-NC-SA 4.0 · licence
Watch
We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.