The Clausius statement

"It is impossible to construct a device that operates in a cycle and produces no effect other than the transfer of heat from a lower-temperature body to a higher-temperature body." A refrigerator therefore needs work (or heat at a high temperature) as an input.

The reversed Carnot cycle

The ideal (most efficient possible) refrigerator between a cold reservoir at T_L and a hot reservoir at T_H runs a reversed Carnot cycle of four reversible processes:

  1. Isentropic compression (temperature rises from T_L to T_H).
  2. Isothermal heat rejection at T_H.
  3. Isentropic expansion (temperature falls from T_H to T_L).
  4. Isothermal heat absorption at T_L.

On a T-s diagram this is a rectangle: Q_L = T_L × Δs, Q_H = T_H × Δs, W = (T_H − T_L) × Δs.

Carnot COP

  • Refrigerator: COP_R,Carnot = T_L ÷ (T_H − T_L)
  • Heat pump: COP_HP,Carnot = T_H ÷ (T_H − T_L)

Temperatures must be in kelvin.
Worked example. A freezer compartment at −10°C in a kitchen at 40°C (the condenser side):

  • T_L = 263.15 K, T_H = 313.15 K, difference = 50 K.
  • COP_R = 263.15 ÷ 50 = 5.26.
  • COP_HP = 313.15 ÷ 50 = 6.26. Check: COP_HP = COP_R + 1. ✓

Effect of temperatures

  • Lowering T_L (colder freezing) reduces COP: at −20°C, COP = 253.15 ÷ 60 = 4.22, about 20% less than at −10°C.
  • Raising T_H (hot surroundings, dirty condenser, unit in direct sun) reduces COP.

Lesson for design: keep the evaporator as warm and the condenser as cool as the job allows.

Second-law efficiency

Real systems are compared with the Carnot COP:
Second-law efficiency = COP_actual ÷ COP_Carnot.
Worked example. A real unit working between the same −10°C and 40°C has COP 2.9. Efficiency = 2.9 ÷ 5.26 = 55%.

Why the Carnot refrigerator is not built

  • Isothermal heat transfer needs infinitely slow processes or infinite area.
  • Isentropic compression of a wet mixture (in the two-phase region) damages compressors ("wet compression").
  • Isentropic expansion of a mostly liquid mixture gives very little work, so a turbine is not worth its cost.

The practical vapour compression cycle changes these steps: it compresses dry vapour and replaces the expander with a throttling valve.

Reversible heat engine and refrigerator together

For an absorption system (see later), the ideal COP combines a Carnot engine running between the heat source and surroundings with a Carnot refrigerator. This is how the maximum COP of heat-driven refrigeration is found.

Exams usually ask: state the Clausius statement; derive the Carnot COP; compute Carnot COPs; explain why the reversed Carnot cycle is impractical and how the vapour compression cycle differs.

Common mistake: using degrees Celsius in the Carnot formula. With −10°C and 40°C in Celsius you would get a negative COP; always convert to kelvin.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.