Refrigeration principles and units

What refrigeration is, methods of producing low temperatures, the refrigeration effect, the ton of refrigeration, coefficient of performance, and applications.

Our notes

2 min read

What refrigeration is

Refrigeration is the removal of heat from a space or substance to bring it below the temperature of its surroundings and keep it there. Heat flows naturally from hot to cold, so moving heat from cold to hot needs work or another input of energy (the second law).

Methods of producing low temperatures

  1. Ice and evaporative cooling: melting ice absorbs about 334 kJ/kg; evaporating water absorbs about 2,450 kJ/kg (clay pots and "zeer pot" coolers use this).
  2. Vapour compression: a liquid refrigerant evaporates at low pressure (absorbing heat) and is compressed and condensed (rejecting heat). The most common method: fridges, freezers, split ACs, cold rooms.
  3. Vapour absorption: heat (gas, steam, solar, waste heat) drives the cycle instead of a compressor.
  4. Gas (air) cycle: compressing and expanding air (aircraft cabins).
  5. Steam jet (ejector): high-pressure steam entrains low-pressure vapour.
  6. Thermoelectric (Peltier) cooling: an electric current across junctions of two materials pumps heat (small coolers).
  7. Throttling (Joule-Thomson) expansion of real gases (liquefaction of gases).
  8. Dry ice and liquid nitrogen.

Key terms

  • Refrigeration effect (Q_L): the heat removed from the cold space.
  • Heat rejected (Q_H): the heat given out to the surroundings (in a condenser).
  • Work input (W): Q_H = Q_L + W (energy balance).
  • Coefficient of performance (COP) of a refrigerator = Q_L ÷ W. Unlike efficiency it is usually greater than 1.
  • Heat pump COP = Q_H ÷ W = COP_R + 1 (same machine used for heating).

The ton of refrigeration

1 ton of refrigeration (TR) is the cooling rate needed to freeze 1 short ton (2,000 lb) of water at 0°C in 24 hours: 12,000 Btu/h = 211 kJ/min = 3.517 kW.
Worked example. A cold room needs 14 kW of cooling. In tons: 14 ÷ 3.517 = 3.98 TR (about 4 tons). If the machine's COP is 2.8, power input = 14 ÷ 2.8 = 5.0 kW, and heat rejected = 14 + 5 = 19.0 kW.

Energy efficiency ratio

Air-conditioners are often rated by EER = cooling output (Btu/h) ÷ power input (W). Since 1 W = 3.412 Btu/h, EER = 3.412 × COP. Worked example. A split unit gives 12,000 Btu/h for 1,100 W: EER = 12,000 ÷ 1,100 = 10.9, COP = 10.9 ÷ 3.412 = 3.20. Check: 3.517 kW ÷ 1.1 kW = 3.20. ✓

Applications

Domestic fridges and freezers; cold rooms for fish, meat, fruit and vaccines (the cold chain); ice making; air-conditioning of homes, offices, cars and hospitals; industrial process cooling (breweries, petrochemicals, LNG); data centres.

Exams usually ask: define refrigeration and COP; list methods of producing low temperatures; convert between kW and tons; compute COP, power and heat rejected.

Common mistake: using COP = W ÷ Q_L or treating COP as a percentage below 1. COP = Q_L ÷ W and is normally 2 to 5 for practical systems.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.