MEG 407 · Principles of Air-conditioning and Refrigerating Engineering
Our notes
2 min readThe basic processes on the chart
| Process | Path on the chart | Example |
|---|---|---|
| Sensible heating | Horizontal to the right (ω constant) | Winter heating, reheat after cooling |
| Sensible cooling | Horizontal to the left, above the dew point | Cooling coil warmer than dew point |
| Cooling and dehumidification | Down and left, towards the coil surface temperature | Air-conditioner evaporator in humid climates |
| Heating and humidification | Up and right | Winter air-conditioning with steam |
| Evaporative cooling | Up and left along a constant wet-bulb line | Evaporative coolers |
| Adiabatic mixing | A straight line between the two states | Fresh air mixed with return air |
Worked example 1: cooling and dehumidifying
Air at 30°C, 70% RH (state 1 from the previous topic: ω₁ = 0.01880, h₁ = 78.2 kJ/kg) is cooled to 14°C saturated (state 2). Dry air flow 0.5 kg/s.
- At 14°C, p_g = 1.599 kPa: ω₂ = 0.622 × 1.599 ÷ (101.325 − 1.599) = 0.9946 ÷ 99.726 = 0.00997 kg/kg.
- h₂ = 1.005 × 14 + 0.00997 × (2501 + 1.88 × 14) = 14.07 + 0.00997 × 2527.3 = 14.07 + 25.20 = 39.27 kJ/kg.
- Water removed = ω₁ − ω₂ = 0.01880 − 0.00997 = 0.00883 kg/kg → 0.5 × 0.00883 = 0.00442 kg/s = 15.9 kg of condensate an hour.
- Heat removed per kg dry air = (h₁ − h₂) − (ω₁ − ω₂) h_w, with the condensate leaving at 14°C (h_w = 58.8 kJ/kg): 38.93 − 0.00883 × 58.8 = 38.93 − 0.52 = 38.4 kJ/kg.
- Cooling capacity = 0.5 × 38.4 = 19.2 kW = 19.2 ÷ 3.517 = 5.5 TR.
Notice that more than half the load is latent (removing moisture): sensible part ≈ 1.02 × 16 = 16.3 kJ/kg of the 38.4, latent about 22 kJ/kg. This is typical of humid Port Harcourt.
Worked example 2: adiabatic mixing
2 kg/s of outdoor air (30°C, ω = 0.0188, h = 78.2) mixes with 3 kg/s of return air (25°C, ω = 0.0099, h = 50.4).
- ω_mix = (2 × 0.0188 + 3 × 0.0099) ÷ 5 = (0.0376 + 0.0297) ÷ 5 = 0.01346.
- h_mix = (2 × 78.2 + 3 × 50.4) ÷ 5 = (156.4 + 151.2) ÷ 5 = 61.5 kJ/kg.
- Temperature from h: T = (h − 2501 ω) ÷ (1.005 + 1.88 ω) = (61.52 − 33.66) ÷ 1.0303 = 27.0°C, close to the mass-weighted average (2 × 30 + 3 × 25) ÷ 5 = 27°C. ✓
The mixed state lies on the straight line joining the two states, nearer the larger stream.
Bypass factor and apparatus dew point
A real cooling coil does not bring all the air to the coil surface temperature. The apparatus dew point (ADP) is the effective coil surface temperature, and the bypass factor BF is the fraction of air that behaves as if it missed the coil:
BF = (T_out − ADP) ÷ (T_in − ADP); contact factor = 1 − BF.
Worked example. Air enters at 27°C, the ADP is 10°C, BF = 0.15: T_out = 10 + 0.15 × (27 − 10) = 10 + 2.55 = 12.6°C.
More coil rows or slower air give a lower BF.
Heating with humidification (winter air-conditioning)
In cold, dry places (or the harmattan in the north: very dry, cool mornings) air may be heated and humidified with steam or water sprays. The steam added = m_a (ω₂ − ω₁).
Sensible heat factor
SHF = sensible heat ÷ total heat. The room SHF line on the chart, drawn from the room state, shows all supply air states that can meet the room's sensible and latent loads together.
Exams usually ask: sketch processes on a psychrometric chart; compute the cooling load and condensate in cooling and dehumidification; compute the mixed state; use bypass factor and ADP.
Common mistake: averaging relative humidities when mixing two air streams. Mix ω and h by mass of dry air; relative humidity is not additive.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Psychrometrics
(opens en.wikipedia.org in a new tab)
Wikipedia, Psychrometrics, CC BY-SA 4.0 · licence
-
NPTEL: Refrigeration and Air Conditioning (IIT Kharagpur, whole course)
Forty lessons as free PDFs: refrigerants, vapour compression and multistage systems, absorption, air cycle, psychrometry, cooling loads and air-conditioning systems.
(opens nptel.ac.in in a new tab)
NPTEL, NPTEL: Refrigeration and Air Conditioning (IIT Kharagpur, whole course), CC BY-NC-SA 4.0 · licence
Watch
-
Best pick Humidity Chart: Adiabatic Humidification
6 min · ≈ 27 MB · about ₦15
(opens youtube.com in a new tab)
-
Psychrometric Chart Examples
4 min · ≈ 18 MB · about ₦10
(opens youtube.com in a new tab)
-
Sensible and Latent Heat Transfer Formula for Air
4 min · ≈ 18 MB · about ₦10
(opens youtube.com in a new tab)
-
Sensible Heat Transfer Equation for Air
4 min · ≈ 18 MB · about ₦10
(opens youtube.com in a new tab)
-
BASIC CONCEPTS Psychrometry and Air-Conditioning
47 min · ≈ 212 MB · about ₦119
(opens youtube.com in a new tab)
We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.