MEG 407 · Principles of Air-conditioning and Refrigerating Engineering

Moist air and psychrometric properties

Composition of moist air, Dalton's law, humidity ratio, relative humidity, dew point, dry-bulb, wet-bulb and adiabatic saturation temperatures, enthalpy of moist air, specific volume and the psychrometric chart.

Our notes

2 min read

Moist air

Atmospheric air is a mixture of dry air and water vapour. At the low pressures and temperatures of air-conditioning both behave as ideal gases, and by Dalton's law the total pressure is the sum of the partial pressures: p = p_a + p_v. Standard sea-level pressure p = 101.325 kPa.

Properties

  1. Dry-bulb temperature (T): the ordinary air temperature.
  2. Humidity ratio (specific humidity) ω: kg of water vapour per kg of dry air:

ω = 0.622 p_v ÷ (p − p_v)

  1. Relative humidity φ = p_v ÷ p_g, where p_g is the saturation pressure of water at the dry-bulb temperature.
  2. Dew point: the temperature at which the vapour starts to condense when air is cooled at constant pressure and ω: the saturation temperature at p_v.
  3. Wet-bulb temperature: read by a thermometer with a wet wick in moving air; close to the adiabatic saturation temperature. The gap between dry-bulb and wet-bulb shows how dry the air is.
  4. Enthalpy per kg of dry air: h = 1.005 T + ω (2501 + 1.88 T) kJ/kg dry air (T in °C).
  5. Specific volume per kg of dry air: v = R_a T ÷ p_a = 0.287 × (T + 273.15) ÷ (p − p_v) m³/kg dry air.

Worked example: Port Harcourt afternoon air

Air at 30°C and 70% relative humidity, p = 101.325 kPa. Saturation pressure of water at 30°C: p_g = 4.247 kPa (steam tables).

  1. p_v = 0.70 × 4.247 = 2.973 kPa.
  2. ω = 0.622 × 2.973 ÷ (101.325 − 2.973) = 1.849 ÷ 98.352 = 0.01880 kg/kg (18.8 g of water per kg of dry air).
  3. h = 1.005 × 30 + 0.01880 × (2501 + 1.88 × 30) = 30.15 + 0.01880 × 2557.4 = 30.15 + 48.08 = 78.2 kJ/kg dry air.
  4. Dew point: the saturation temperature at 2.973 kPa is about 23.9°C (between 2.985 kPa at 24°C and 2.810 kPa at 23°C, interpolated).
  5. v = 0.287 × 303.15 ÷ 98.352 = 0.885 m³/kg dry air.

Check: the saturated humidity ratio at 30°C = 0.622 × 4.247 ÷ 97.078 = 0.02721, and 0.01880 ÷ 0.02721 = 0.691. This ratio (the degree of saturation, 69.1%) is a little below the relative humidity (70%) because ω is not proportional to p_v, as expected. ✓

The psychrometric chart

A chart of these properties at one pressure: dry-bulb temperature along the bottom, humidity ratio up the right side, the saturation curve (100% RH) on the left boundary, curved lines of constant relative humidity, sloping lines of constant wet-bulb (and roughly constant enthalpy), and lines of constant specific volume. Two independent properties fix a state; the rest are read off.

Human comfort

Comfort depends on temperature, humidity, air movement, radiation, clothing and activity. Typical indoor design conditions for cooling in hot climates: 24 to 26°C dry-bulb and 50 to 60% RH. High humidity makes 30°C feel much worse because sweat cannot evaporate easily.

Exams usually ask: define the psychrometric properties; derive ω = 0.622 p_v ÷ (p − p_v); compute ω, h, dew point and specific volume from given conditions; read properties from the chart.

Common mistake: expressing enthalpy per kg of moist air. Air-conditioning calculations use kg of dry air, because the dry air flow stays constant through processes while the water content changes.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.