MEG 407 · Principles of Air-conditioning and Refrigerating Engineering

Air-conditioning systems and supply air

Summer and winter air-conditioning, design conditions, the simple summer air-conditioning cycle, finding the supply air state and mass flow, and the main types of systems in use.

Our notes

3 min read

Purpose

Air-conditioning controls temperature, humidity, air movement, cleanliness and fresh air for comfort (homes, offices, lecture theatres) or for industrial processes (textiles, printing, hospitals, data centres).

Summer air-conditioning (hot, humid climate)

  1. Return air from the room mixes with fresh outdoor air.
  2. The mixture passes over a cooling coil: it is cooled and dehumidified.
  3. If the coil leaves the air too cold, a reheater warms it (only where humidity control is strict, because reheat wastes energy).
  4. A fan supplies the air to the room, where it picks up the room's sensible and latent heat.

Winter air-conditioning (cold climate)

Air is heated and humidified (and filtered). In Nigeria, true winter heating is rarely needed, but the harmattan brings very dry air in the north; humidification is used in some hospitals and industries.

Design conditions

  • Outdoor: chosen from local weather data so the system copes with all but the hottest few hours of the year (for Port Harcourt, design values around 32 to 33°C dry-bulb with high humidity are typical; use the current ASHRAE climate data for the station).
  • Indoor: usually 24 to 26°C and 50 to 60% RH for comfort.

The supply air state and mass flow

The supply air must be cool and dry enough to absorb the room's sensible load (temperature) and latent load (moisture).

  • Sensible: Q_s = m_a c_p (T_room − T_supply), with c_p of moist air about 1.02 kJ/kg K (1.005 for dry air is often used).
  • Latent: Q_l = m_a (ω_room − ω_supply) h_fg, with h_fg about 2,450 kJ/kg.

Worked example. A room has a sensible load of 10 kW and a latent load of 3 kW, kept at 25°C. Supply air enters at 13°C.

  • Mass flow of dry air = 10 ÷ (1.005 × 12) = 10 ÷ 12.06 = 0.829 kg/s.
  • Moisture difference needed: ω_room − ω_supply = 3 ÷ (0.829 × 2,450) = 3 ÷ 2,031 = 0.00148 kg/kg. If the room is at ω = 0.0099, supply ω = 0.0099 − 0.0015 = 0.0084.
  • Volume flow (v ≈ 0.82 m³/kg at 13°C) = 0.829 × 0.82 = 0.68 m³/s (about 1,440 cfm, at 2,119 cfm per m³/s).
  • SHF = 10 ÷ 13 = 0.77.

Check: 0.829 × 1.005 × 12 = 10.0 kW. ✓

Types of systems

SystemDescriptionTypical use
Window and through-wall unitsAll parts in one boxSingle rooms (being replaced by splits)
Split units (wall, ceiling, floor)Indoor fan coil and outdoor condensing unit joined by pipesHomes, offices, hostels in Nigeria
Packaged units and rooftop unitsLarger self-contained units with ductsShops, halls
Central chilled waterChillers make chilled water piped to air handling units and fan coilsHotels, hospitals, large buildings
VRF (variable refrigerant flow)One outdoor unit with variable-speed compressors serving many indoor unitsOffices, banks
Evaporative coolersWater evaporationDry northern climates

Nigerian market labels

Units in Nigeria are often sold by horsepower (hp), a loose label: commonly 1 hp ≈ 9,000 Btu/h (2.6 kW), 1.5 hp ≈ 12,000 Btu/h (3.5 kW), 2 hp ≈ 18,000 Btu/h (5.3 kW) of cooling. Always check the rated cooling capacity in Btu/h or kW and the power input on the nameplate.

Exams usually ask: describe summer and winter air-conditioning with a chart sketch; calculate supply air mass flow and state; compare types of air-conditioning systems.

Common mistake: sizing supply air from the total load with the dry-bulb difference. The temperature difference fixes the sensible load only; the latent load sets the supply humidity.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.