MEG 407 · Principles of Air-conditioning and Refrigerating Engineering
Our notes
3 min readPurpose
Air-conditioning controls temperature, humidity, air movement, cleanliness and fresh air for comfort (homes, offices, lecture theatres) or for industrial processes (textiles, printing, hospitals, data centres).
Summer air-conditioning (hot, humid climate)
- Return air from the room mixes with fresh outdoor air.
- The mixture passes over a cooling coil: it is cooled and dehumidified.
- If the coil leaves the air too cold, a reheater warms it (only where humidity control is strict, because reheat wastes energy).
- A fan supplies the air to the room, where it picks up the room's sensible and latent heat.
Winter air-conditioning (cold climate)
Air is heated and humidified (and filtered). In Nigeria, true winter heating is rarely needed, but the harmattan brings very dry air in the north; humidification is used in some hospitals and industries.
Design conditions
- Outdoor: chosen from local weather data so the system copes with all but the hottest few hours of the year (for Port Harcourt, design values around 32 to 33°C dry-bulb with high humidity are typical; use the current ASHRAE climate data for the station).
- Indoor: usually 24 to 26°C and 50 to 60% RH for comfort.
The supply air state and mass flow
The supply air must be cool and dry enough to absorb the room's sensible load (temperature) and latent load (moisture).
- Sensible: Q_s = m_a c_p (T_room − T_supply), with c_p of moist air about 1.02 kJ/kg K (1.005 for dry air is often used).
- Latent: Q_l = m_a (ω_room − ω_supply) h_fg, with h_fg about 2,450 kJ/kg.
Worked example. A room has a sensible load of 10 kW and a latent load of 3 kW, kept at 25°C. Supply air enters at 13°C.
- Mass flow of dry air = 10 ÷ (1.005 × 12) = 10 ÷ 12.06 = 0.829 kg/s.
- Moisture difference needed: ω_room − ω_supply = 3 ÷ (0.829 × 2,450) = 3 ÷ 2,031 = 0.00148 kg/kg. If the room is at ω = 0.0099, supply ω = 0.0099 − 0.0015 = 0.0084.
- Volume flow (v ≈ 0.82 m³/kg at 13°C) = 0.829 × 0.82 = 0.68 m³/s (about 1,440 cfm, at 2,119 cfm per m³/s).
- SHF = 10 ÷ 13 = 0.77.
Check: 0.829 × 1.005 × 12 = 10.0 kW. ✓
Types of systems
| System | Description | Typical use |
|---|---|---|
| Window and through-wall units | All parts in one box | Single rooms (being replaced by splits) |
| Split units (wall, ceiling, floor) | Indoor fan coil and outdoor condensing unit joined by pipes | Homes, offices, hostels in Nigeria |
| Packaged units and rooftop units | Larger self-contained units with ducts | Shops, halls |
| Central chilled water | Chillers make chilled water piped to air handling units and fan coils | Hotels, hospitals, large buildings |
| VRF (variable refrigerant flow) | One outdoor unit with variable-speed compressors serving many indoor units | Offices, banks |
| Evaporative coolers | Water evaporation | Dry northern climates |
Nigerian market labels
Units in Nigeria are often sold by horsepower (hp), a loose label: commonly 1 hp ≈ 9,000 Btu/h (2.6 kW), 1.5 hp ≈ 12,000 Btu/h (3.5 kW), 2 hp ≈ 18,000 Btu/h (5.3 kW) of cooling. Always check the rated cooling capacity in Btu/h or kW and the power input on the nameplate.
Exams usually ask: describe summer and winter air-conditioning with a chart sketch; calculate supply air mass flow and state; compare types of air-conditioning systems.
Common mistake: sizing supply air from the total load with the dry-bulb difference. The temperature difference fixes the sensible load only; the latent load sets the supply humidity.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Air conditioning
(opens en.wikipedia.org in a new tab)
Wikipedia, Air conditioning, CC BY-SA 4.0 · licence
-
Chiller
(opens en.wikipedia.org in a new tab)
Wikipedia, Chiller, CC BY-SA 4.0 · licence
-
Heat pump
(opens en.wikipedia.org in a new tab)
Wikipedia, Heat pump, CC BY-SA 4.0 · licence
-
NPTEL: Refrigeration and Air Conditioning (IIT Kharagpur, whole course)
Forty lessons as free PDFs: refrigerants, vapour compression and multistage systems, absorption, air cycle, psychrometry, cooling loads and air-conditioning systems.
(opens nptel.ac.in in a new tab)
NPTEL, NPTEL: Refrigeration and Air Conditioning (IIT Kharagpur, whole course), CC BY-NC-SA 4.0 · licence
Watch
We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.