Cooling loads and ventilation

Sources of heat gain (conduction, solar, people, lights, equipment, infiltration and ventilation), a worked lecture-room load estimate, ventilation rates and indoor air quality.

Our notes

2 min read

Heat gains to a room

SourceSensible or latentNotes
Conduction through walls, roof, windowsSensibleQ = U A ΔT (with sol-air temperature for sunlit surfaces)
Solar radiation through glassSensibleLarge on east and west windows; reduce with shading and tinted glass
PeopleBothDepends on activity: seated students give about 70 W sensible and 45 W latent each (typical table values)
LightsSensibleLED lighting gives far less heat than old fluorescent or filament lamps
EquipmentMostly sensibleComputers, projectors, fridges
Infiltration (leaks)BothDoors opening, gaps
Ventilation (fresh air)BothOutdoor air brought in deliberately: a big latent load in humid climates

Conduction example

A 20 m² west wall with U = 2.0 W/m² K, outdoor sol-air temperature 45°C, room at 25°C: Q = 2.0 × 20 × (45 − 25) = 800 W.

Worked example: a 60-seat lecture room in Port Harcourt

Room kept at 25°C, ω = 0.0099. Outdoor design air 32°C, ω = 0.0210.

  1. People: 60 × 70 W = 4.20 kW sensible; 60 × 45 W = 2.70 kW latent.
  2. Lights: 20 LED fittings × 36 W = 0.72 kW sensible.
  3. Walls, roof, windows and sun (from a separate calculation): 6.00 kW sensible.
  4. Ventilation: 5 L/s per person × 60 = 0.30 m³/s of outdoor air ≈ 0.30 × 1.2 = 0.36 kg/s.
  • Sensible = 0.36 × 1.005 × (32 − 25) = 2.53 kW.
  • Latent = 0.36 × (0.0210 − 0.0099) × 2,501 = 0.36 × 0.0111 × 2,501 = 9.99 kW.
  1. Totals: sensible = 4.20 + 0.72 + 6.00 + 2.53 = 13.45 kW; latent = 2.70 + 9.99 = 12.69 kW; total = 26.14 kW.
  2. With a 10% safety margin: 26.14 × 1.1 = 28.75 kW = 28.75 ÷ 3.517 = 8.2 TR.

Lesson: in humid climates, fresh air can be the largest single load. Energy recovery ventilators and good dehumidification design pay off. (The ventilation rate and people loads here are typical textbook values; ASHRAE Standard 62.1 and local codes give the exact rates.)

Ventilation

Ventilation brings in outdoor air to dilute carbon dioxide, odours, moisture and pollutants and to supply oxygen.

  • Rates are set per person and per floor area (for classrooms, roughly 5 L/s per person plus an area allowance in ASHRAE 62.1).
  • Measured by air changes per hour (ACH): ACH = volume flow per hour ÷ room volume. Worked example. A 10 m × 8 m × 3.5 m room (280 m³) with 0.30 m³/s outdoor air: 0.30 × 3,600 ÷ 280 = 3.9 ACH.
  • CO₂ level is a quick check of ventilation: outdoor air is about 420 ppm (dated, 2020s); indoor levels much above 1,000 ppm suggest poor ventilation.
  • Natural ventilation (windows, cross ventilation) suits many Nigerian buildings when air-conditioning is not used.

Reducing loads

Shade windows (especially east and west), insulate roofs (hot zinc roofs add heavily), use light-coloured roofs, LED lighting, tight doors, and efficient (inverter) units.

Exams usually ask: list and explain the components of a cooling load; estimate a room cooling load; calculate ventilation air flow and ACH; explain the importance of ventilation.

Common mistake: forgetting the latent load of fresh air. In a humid climate the moisture in outdoor air can need more cooling than its temperature.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.