MEG 407 · Principles of Air-conditioning and Refrigerating Engineering
Our notes
2 min readHeat gains to a room
| Source | Sensible or latent | Notes |
|---|---|---|
| Conduction through walls, roof, windows | Sensible | Q = U A ΔT (with sol-air temperature for sunlit surfaces) |
| Solar radiation through glass | Sensible | Large on east and west windows; reduce with shading and tinted glass |
| People | Both | Depends on activity: seated students give about 70 W sensible and 45 W latent each (typical table values) |
| Lights | Sensible | LED lighting gives far less heat than old fluorescent or filament lamps |
| Equipment | Mostly sensible | Computers, projectors, fridges |
| Infiltration (leaks) | Both | Doors opening, gaps |
| Ventilation (fresh air) | Both | Outdoor air brought in deliberately: a big latent load in humid climates |
Conduction example
A 20 m² west wall with U = 2.0 W/m² K, outdoor sol-air temperature 45°C, room at 25°C: Q = 2.0 × 20 × (45 − 25) = 800 W.
Worked example: a 60-seat lecture room in Port Harcourt
Room kept at 25°C, ω = 0.0099. Outdoor design air 32°C, ω = 0.0210.
- People: 60 × 70 W = 4.20 kW sensible; 60 × 45 W = 2.70 kW latent.
- Lights: 20 LED fittings × 36 W = 0.72 kW sensible.
- Walls, roof, windows and sun (from a separate calculation): 6.00 kW sensible.
- Ventilation: 5 L/s per person × 60 = 0.30 m³/s of outdoor air ≈ 0.30 × 1.2 = 0.36 kg/s.
- Sensible = 0.36 × 1.005 × (32 − 25) = 2.53 kW.
- Latent = 0.36 × (0.0210 − 0.0099) × 2,501 = 0.36 × 0.0111 × 2,501 = 9.99 kW.
- Totals: sensible = 4.20 + 0.72 + 6.00 + 2.53 = 13.45 kW; latent = 2.70 + 9.99 = 12.69 kW; total = 26.14 kW.
- With a 10% safety margin: 26.14 × 1.1 = 28.75 kW = 28.75 ÷ 3.517 = 8.2 TR.
Lesson: in humid climates, fresh air can be the largest single load. Energy recovery ventilators and good dehumidification design pay off. (The ventilation rate and people loads here are typical textbook values; ASHRAE Standard 62.1 and local codes give the exact rates.)
Ventilation
Ventilation brings in outdoor air to dilute carbon dioxide, odours, moisture and pollutants and to supply oxygen.
- Rates are set per person and per floor area (for classrooms, roughly 5 L/s per person plus an area allowance in ASHRAE 62.1).
- Measured by air changes per hour (ACH): ACH = volume flow per hour ÷ room volume. Worked example. A 10 m × 8 m × 3.5 m room (280 m³) with 0.30 m³/s outdoor air: 0.30 × 3,600 ÷ 280 = 3.9 ACH.
- CO₂ level is a quick check of ventilation: outdoor air is about 420 ppm (dated, 2020s); indoor levels much above 1,000 ppm suggest poor ventilation.
- Natural ventilation (windows, cross ventilation) suits many Nigerian buildings when air-conditioning is not used.
Reducing loads
Shade windows (especially east and west), insulate roofs (hot zinc roofs add heavily), use light-coloured roofs, LED lighting, tight doors, and efficient (inverter) units.
Exams usually ask: list and explain the components of a cooling load; estimate a room cooling load; calculate ventilation air flow and ACH; explain the importance of ventilation.
Common mistake: forgetting the latent load of fresh air. In a humid climate the moisture in outdoor air can need more cooling than its temperature.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Cooling load
(opens en.wikipedia.org in a new tab)
Wikipedia, Cooling load, CC BY-SA 4.0 · licence
-
Ventilation (architecture)
(opens en.wikipedia.org in a new tab)
Wikipedia, Ventilation (architecture), CC BY-SA 4.0 · licence
-
NPTEL: Refrigeration and Air Conditioning (IIT Kharagpur, whole course)
Forty lessons as free PDFs: refrigerants, vapour compression and multistage systems, absorption, air cycle, psychrometry, cooling loads and air-conditioning systems.
(opens nptel.ac.in in a new tab)
NPTEL, NPTEL: Refrigeration and Air Conditioning (IIT Kharagpur, whole course), CC BY-NC-SA 4.0 · licence
Watch
We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.