MEG 407 · Principles of Air-conditioning and Refrigerating Engineering
Our notes
3 min readExpansion devices
| Device | How it works | Use |
|---|---|---|
| Capillary tube | A long, narrow tube gives a fixed pressure drop | Small fridges and window or split ACs; cheap, no moving parts, but cannot adjust to load |
| Thermostatic expansion valve (TXV) | A bulb at the evaporator outlet senses superheat and opens or closes the valve to keep about 5 K superheat | Medium systems, cold rooms |
| Electronic expansion valve (EEV) | A stepper motor valve set by a controller from temperature and pressure sensors | Inverter units, VRF, chillers: precise, efficient |
| Float valves | Keep a liquid level | Flooded evaporators, large ammonia plants |
Other controls
- Thermostat: switches the compressor (on-off) or sets its speed to keep the room or cabinet temperature.
- Low-pressure cut-out: stops the compressor if suction pressure falls too low (loss of refrigerant, frozen coil).
- High-pressure cut-out: stops it if discharge pressure rises too high (dirty condenser, fan failure): a safety device.
- Overload and thermal protectors on the motor; time delays to stop rapid restarts after power cuts (important where supply is unstable).
- Defrost control for evaporators below 0°C: electric heaters, hot gas or off-cycle defrost on a timer or on demand.
Microprocessor control
Modern units use microcontrollers that read sensors (temperatures, pressures, current) and run control logic:
- PID control (proportional, integral, derivative) of temperature and valve opening.
- Inverter (variable-speed) compressors: instead of switching fully on and off, the compressor speed matches the load, which cuts energy use (often 20 to 40% compared with fixed speed in part-load conditions, depending on use), keeps temperature steadier and reduces starting current.
- Fault codes for diagnosis, remote monitoring, and building management systems (BMS).
- Protection against voltage swings: many units now accept a wide voltage range, which matters on Nigerian grids and generators.
Computer-aided design and analysis
Engineers use software to: compute cooling loads hour by hour, select coils, fans and compressors, size ducts and pipes, model cycles with refrigerant property libraries (for example EES, CoolProp in Python, manufacturers' selection tools), and simulate building energy use. Spreadsheets with property tables are enough for student projects.
System design steps
- Define the requirement (space, product, temperatures, hours).
- Estimate the load (cooling load topic).
- Choose the system type and refrigerant.
- Select the equipment at the design conditions (capacity tables).
- Design distribution (ducts or pipes) and controls.
- Check energy use, cost, noise and maintenance access.
Installation, maintenance and safety
- Correct pipe sizing and insulation; vacuum the system before charging to remove air and moisture; charge by weight.
- Clean filters monthly and coils regularly; check drains (blocked drains cause leaks and mould).
- Check refrigerant charge and leaks; recover refrigerant (never vent it).
- Safety: electrical isolation before work; high pressures; burns from hot and frostbite from cold lines; ammonia toxicity (ventilation, detectors, breathing apparatus in plant rooms); flammable refrigerants (R-290, R-600a, R-32) need no flames and proper ventilation.
- Standards and training: technicians should be certified in safe refrigerant handling (training is run in Nigeria under ozone and HFC phase-down programmes).
Worked example: energy and cost
A 1.5 hp (3.5 kW cooling) fixed-speed split AC draws 1.2 kW and runs 8 hours a day for 30 days: 1.2 × 8 × 30 = 288 kWh. An inverter unit averaging 0.8 kW for the same comfort uses 0.8 × 240 = 192 kWh, saving 96 kWh a month. At ₦200 per kWh (a practice figure; tariffs change by band and date), that is ₦19,200 a month.
Exams usually ask: compare expansion devices; describe safety controls; explain microprocessor and inverter control; outline the steps in designing an air-conditioning or refrigeration system.
Common mistake: describing a capillary tube as adjusting to the load. It is a fixed restriction; that is why it suits small systems with steady loads and why larger systems use TXVs or electronic valves.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Thermal expansion valve
(opens en.wikipedia.org in a new tab)
Wikipedia, Thermal expansion valve, CC BY-SA 4.0 · licence
-
Inverter compressor
(opens en.wikipedia.org in a new tab)
Wikipedia, Inverter compressor, CC BY-SA 4.0 · licence
-
Auto-defrost
(opens en.wikipedia.org in a new tab)
Wikipedia, Auto-defrost, CC BY-SA 4.0 · licence
-
NPTEL: Refrigeration and Air Conditioning (IIT Kharagpur, whole course)
Forty lessons as free PDFs: refrigerants, vapour compression and multistage systems, absorption, air cycle, psychrometry, cooling loads and air-conditioning systems.
(opens nptel.ac.in in a new tab)
NPTEL, NPTEL: Refrigeration and Air Conditioning (IIT Kharagpur, whole course), CC BY-NC-SA 4.0 · licence
Watch
We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.