EEE 510 · Power Systems Engineering

Unsymmetrical faults

Single line-to-ground, line-to-line and double line-to-ground faults, connecting sequence networks for each, fault impedance, and a worked comparison on one generator.

Our notes

2 min read

Approach

  1. Draw the positive, negative and zero sequence networks and find their Thevenin impedances Z1, Z2, Z0 at the fault point.
  2. Write the fault's boundary conditions in phase quantities.
  3. Convert them to sequence quantities; this tells how to connect the networks.
  4. Solve for sequence currents; convert back to phase currents and voltages.

Single line-to-ground (SLG) fault on phase a

Conditions: I_b = I_c = 0, V_a = Z_f I_a. Result: I0 = I1 = I2, and the three networks are in series:
I_a1 = V_f ÷ (Z1 + Z2 + Z0 + 3Z_f); fault current I_f = I_a = 3I_a1.

Line-to-line (LL) fault between b and c

Conditions: I_a = 0, I_b = −I_c, V_b − V_c = Z_f I_b. Result: positive and negative networks in parallel opposition (connected at the fault), zero sequence absent:
I_a1 = −I_a2 = V_f ÷ (Z1 + Z2 + Z_f); fault current |I_b| = √3 |I_a1|.

Double line-to-ground (DLG) fault on b and c

Positive network in series with the parallel combination of the negative network and (zero network + 3Z_f):
I_a1 = V_f ÷ [Z1 + Z2(Z0 + 3Z_f) ÷ (Z2 + Z0 + 3Z_f)]; then I_a2 = −I_a1 (Z0 + 3Z_f) ÷ (Z2 + Z0 + 3Z_f) and I_a0 = −I_a1 Z2 ÷ (Z2 + Z0 + 3Z_f). Ground current = 3I_a0.

Worked comparison

A solidly grounded generator (base 50 MVA, 11 kV): X1 = 0.2, X2 = 0.15, X0 = 0.05 pu, V_f = 1.0 pu, Z_f = 0. Base current = 50,000 ÷ (√3 × 11) = 2,624.3 A.

FaultCalculationFault current (pu)Amperes
Three-phase1 ÷ 0.25.013,122
SLGI_a1 = 1 ÷ (0.2 + 0.15 + 0.05) = 2.5; I_f = 3 × 2.57.519,682
LLI_a1 = 1 ÷ 0.35 = 2.857; I_f = √3 × 2.8574.9512,990
DLG (ground current)X2 parallel X0 = 0.0375; I_a1 = 1 ÷ 0.2375 = 4.211; I_a0 = −4.211 × 0.15 ÷ 0.20 = −3.158; 3I_a09.4724,860

Checks: in the DLG case I_a1 + I_a2 + I_a0 = 4.211 − 1.053 − 3.158 = 0 (phase a carries no current). ✓ The SLG current exceeds the three-phase current here because X0 is small: this is why generator neutrals are often grounded through a resistor or reactor.

Effect of neutral grounding

Adding a neutral impedance Z_n adds 3Z_n to the zero-sequence network, reducing ground-fault currents. Ungrounded systems have almost no SLG fault current but suffer overvoltages on the healthy phases.

Exams usually ask: derive the sequence network connections for SLG, LL and DLG faults; compute fault currents for each; explain why SLG current can exceed three-phase current; explain neutral grounding.

Common mistake: forgetting the factor 3 in the SLG fault current (I_f = 3I_a1), or including the zero-sequence network in an LL fault.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.