EEE 510 · Power Systems Engineering
Our notes
3 min readPurpose
Protection detects faults and abnormal conditions and isolates only the faulty part as fast as possible, to protect people and equipment and keep the rest of the system running.
Qualities of a protection system
- Selectivity (discrimination): trip only the breakers nearest the fault.
- Speed: limit damage and keep stability.
- Sensitivity: detect the smallest fault.
- Reliability: dependability (always trips for faults) and security (never trips wrongly).
- Simplicity and economy.
Instrument transformers
- Current transformers (CTs) scale primary current (for example 400/1 A) to relay levels.
- Voltage transformers (VTs) scale voltages (for example 132 kV/110 V).
CT saturation during large faults can upset relays, so CTs are chosen for the expected fault level.
Zones and backup
Each element (generator, transformer, bus, line) has its own protection zone, bounded by CTs and breakers; zones overlap at breakers so no part is left unprotected. Primary protection acts first; backup protection (on the same or the next upstream element) acts after a delay if the primary fails.
Overcurrent protection and IDMT relays
An inverse definite minimum time (IDMT) relay operates faster for larger currents. For the IEC standard inverse curve:
t = TMS × 0.14 ÷ (PSM^0.02 − 1)
where PSM (plug setting multiplier) = fault current ÷ relay pick-up current (in primary terms), and TMS is the time multiplier setting.
Worked example (grading two relays). A fault draws 4,000 A through both relays.
- Downstream relay R1: CT 400/1, plug setting 100% (pick-up 400 A), TMS 0.2. PSM = 4,000 ÷ 400 = 10. 10^0.02 = 1.04713, so t = 0.2 × 0.14 ÷ 0.04713 = 0.594 s.
- Upstream relay R2 must wait a grading margin (about 0.4 s): target 0.594 + 0.4 ≈ 1.0 s. R2: CT 600/1, plug 100% (600 A); PSM = 4,000 ÷ 600 = 6.667; 6.667^0.02 = 1.03867; time at TMS 1 = 0.14 ÷ 0.03867 = 3.620 s. TMS needed = 1.0 ÷ 3.620 = 0.276, so set TMS = 0.3, giving 1.086 s.
Check: 1.086 − 0.594 = 0.49 s ≥ 0.4 s margin. ✓ R1 clears the fault; R2 only trips if R1 or its breaker fails.
Earth-fault protection
Detects residual current (I_a + I_b + I_c = 3I0) with a lower setting than phase overcurrent, since ground faults may be small (especially through high-resistance paths).
Distance (impedance) protection
Used on transmission lines. The relay measures V ÷ I = apparent impedance; a fault inside the line shows an impedance smaller than the line's. Zones: Zone 1 about 80% of the line, instantaneous; Zone 2 the rest of the line plus part of the next, delayed (about 0.3 to 0.4 s); Zone 3 as backup for the next line, longer delay. Mho characteristics on the R-X diagram are common.
Differential protection
Compares current entering and leaving a zone (Merz-Price principle): in health they balance; an internal fault makes them differ. Fast and selective for generators, transformers and busbars. Biased (percentage) differential relays prevent false trips from CT mismatch; transformer differential relays also block on inrush (second-harmonic restraint).
Other protection
Under/over-voltage and frequency (load shedding during generation loss), negative-sequence protection of generators, Buchholz relays for oil-filled transformers, and numerical relays with communication (IEC 61850).
Exams usually ask: state the qualities of protection; explain zones and backup; calculate IDMT relay times and grade relays; explain distance and differential protection principles.
Common mistake: grading relays at different fault currents. Grade at the maximum fault current seen by both relays at the same fault location.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Best pick Protective relay
(opens en.wikipedia.org in a new tab)
Wikipedia, Protective relay, CC BY-SA 4.0 · licence
-
Protective relay
(opens en.wikipedia.org in a new tab)
Wikipedia, Protective relay, CC BY-SA 4.0 · licence
-
Power system protection
(opens en.wikipedia.org in a new tab)
Wikipedia, Power system protection, CC BY-SA 4.0 · licence
Watch
-
IDMT Relays Time Multiplier Setting (TMS) - IDMT Relay Calculation. Tutorial 3
11 min · ≈ 50 MB · about ₦28
(opens youtube.com in a new tab)
-
IDMT Relays Plug Setting & TMS - IDMT Relay Calculation. Tutorial 5 .Part 1
21 min · ≈ 95 MB · about ₦53
(opens youtube.com in a new tab)
-
Overcurrent Protection in Electrical Substations: the simple genius of the Relay
6 min · ≈ 27 MB · about ₦15
(opens youtube.com in a new tab)
-
Protective Zone in Power System - Introduction to Protective Relaying
15 min · ≈ 68 MB · about ₦38
(opens youtube.com in a new tab)
-
Transformer Differential Protection Explained
6 min · ≈ 27 MB · about ₦15
(opens youtube.com in a new tab)
-
Lecture 1 Fundamentals of Protective Relaying-I
34 min · ≈ 153 MB · about ₦86
(opens youtube.com in a new tab)
-
Lec-21: Coordination of Overcurrent Relays for Distribution Network-I
30 min · ≈ 135 MB · about ₦76
(opens youtube.com in a new tab)
We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.