Fault clearance: circuit breakers, fuses and switchgear

Arc formation and interruption, types of circuit breaker (oil, air-blast, SF6, vacuum), ratings (breaking, making, short-time), restriking voltage, fuses, auto-reclosing and the clearing time chain.

Our notes

2 min read

The clearing chain

Fault occurs → CTs and VTs sense it → relay decides (milliseconds to seconds) → trip signal → circuit breaker opens its contacts → arc is extinguished at a current zero → fault cleared. Total clearing time = relay time + breaker time (modern HV breakers open in 2 to 3 cycles: 40 to 60 ms at 50 Hz).

The arc and its interruption

When contacts part under load, the current continues through an arc of ionised gas. AC arcs pass through current zero every half-cycle; the breaker must cool and de-ionise the gap fast enough that the recovery voltage cannot re-establish (restrike) the arc.

  • Restriking voltage: the transient voltage across the contacts just after current zero; its rate of rise (RRRV) decides whether the arc reignites.
  • Recovery voltage: the normal-frequency voltage after transients die out.

Interruption methods: high-resistance (lengthening and cooling the arc, low voltage) and current-zero (de-ionising the gap at current zero, used in HV).

Types of circuit breaker

TypeMediumUsedNotes
Bulk oil and minimum oilOilOlder 11 to 132 kVFire risk, maintenance
Air-blastCompressed airOlder EHVNoisy, needs compressors
SF6Sulphur hexafluoride gas33 kV to EHV (most modern HV)Excellent arc quenching and insulation; SF6 is a potent greenhouse gas, so leaks must be controlled
VacuumVacuum11 and 33 kV distributionCompact, long life, little maintenance
Air (moulded case, air circuit breakers)AirLow voltageBuildings and industry

Ratings

  • Rated voltage, current and frequency.
  • Breaking capacity: the largest fault current (rms, symmetrical) it can interrupt; also expressed as MVA = √3 × V × I.
  • Making capacity: the peak current it can close onto (a fault already present): 2.55 × the rms symmetrical breaking current (allowing for maximum DC offset: 1.8 × √2).
  • Short-time rating: current it can carry for a stated time (1 or 3 s) without damage.

Worked example. A 33 kV breaker must interrupt a fault of 20 kA rms symmetrical. Breaking capacity = √3 × 33 × 20 = 1,143 MVA; making capacity = 2.55 × 20 = 51 kA peak. Check: 1.732 × 660 = 1,143. ✓

Fuses

A fuse melts when current exceeds its rating, clearing faults on LV and distribution circuits (HRC fuses, drop-out fuses on 11 kV transformers). Cheap and fast but single-use and coarse in discrimination. Fuse-fuse and fuse-breaker coordination use their time-current curves.

Auto-reclosing

Most overhead line faults (lightning, flashover, brief contact with trees) are transient. Auto-reclosers open the line, wait a short dead time (a fraction of a second) for the arc path to de-ionise, then re-close; if the fault persists, they lock out after a set number of attempts. This keeps supply for most faults.

Switchgear and safety

Switchgear includes breakers, isolators (opened only off-load, for safe isolation), earthing switches, busbars and protection panels. Gas-insulated switchgear (GIS) is compact for cities. Safe work needs isolation, earthing, permit-to-work procedures and interlocks.

Exams usually ask: describe arc formation and interruption; compare types of circuit breakers; define breaking, making and short-time ratings and compute them; explain restriking voltage, fuses and auto-reclosing.

Common mistake: using an isolator to break load current. Isolators are for off-load switching; only circuit breakers interrupt load and fault currents.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.