EEE 510 · Power Systems Engineering
Our notes
2 min readThe clearing chain
Fault occurs → CTs and VTs sense it → relay decides (milliseconds to seconds) → trip signal → circuit breaker opens its contacts → arc is extinguished at a current zero → fault cleared. Total clearing time = relay time + breaker time (modern HV breakers open in 2 to 3 cycles: 40 to 60 ms at 50 Hz).
The arc and its interruption
When contacts part under load, the current continues through an arc of ionised gas. AC arcs pass through current zero every half-cycle; the breaker must cool and de-ionise the gap fast enough that the recovery voltage cannot re-establish (restrike) the arc.
- Restriking voltage: the transient voltage across the contacts just after current zero; its rate of rise (RRRV) decides whether the arc reignites.
- Recovery voltage: the normal-frequency voltage after transients die out.
Interruption methods: high-resistance (lengthening and cooling the arc, low voltage) and current-zero (de-ionising the gap at current zero, used in HV).
Types of circuit breaker
| Type | Medium | Used | Notes |
|---|---|---|---|
| Bulk oil and minimum oil | Oil | Older 11 to 132 kV | Fire risk, maintenance |
| Air-blast | Compressed air | Older EHV | Noisy, needs compressors |
| SF6 | Sulphur hexafluoride gas | 33 kV to EHV (most modern HV) | Excellent arc quenching and insulation; SF6 is a potent greenhouse gas, so leaks must be controlled |
| Vacuum | Vacuum | 11 and 33 kV distribution | Compact, long life, little maintenance |
| Air (moulded case, air circuit breakers) | Air | Low voltage | Buildings and industry |
Ratings
- Rated voltage, current and frequency.
- Breaking capacity: the largest fault current (rms, symmetrical) it can interrupt; also expressed as MVA = √3 × V × I.
- Making capacity: the peak current it can close onto (a fault already present): 2.55 × the rms symmetrical breaking current (allowing for maximum DC offset: 1.8 × √2).
- Short-time rating: current it can carry for a stated time (1 or 3 s) without damage.
Worked example. A 33 kV breaker must interrupt a fault of 20 kA rms symmetrical. Breaking capacity = √3 × 33 × 20 = 1,143 MVA; making capacity = 2.55 × 20 = 51 kA peak. Check: 1.732 × 660 = 1,143. ✓
Fuses
A fuse melts when current exceeds its rating, clearing faults on LV and distribution circuits (HRC fuses, drop-out fuses on 11 kV transformers). Cheap and fast but single-use and coarse in discrimination. Fuse-fuse and fuse-breaker coordination use their time-current curves.
Auto-reclosing
Most overhead line faults (lightning, flashover, brief contact with trees) are transient. Auto-reclosers open the line, wait a short dead time (a fraction of a second) for the arc path to de-ionise, then re-close; if the fault persists, they lock out after a set number of attempts. This keeps supply for most faults.
Switchgear and safety
Switchgear includes breakers, isolators (opened only off-load, for safe isolation), earthing switches, busbars and protection panels. Gas-insulated switchgear (GIS) is compact for cities. Safe work needs isolation, earthing, permit-to-work procedures and interlocks.
Exams usually ask: describe arc formation and interruption; compare types of circuit breakers; define breaking, making and short-time ratings and compute them; explain restriking voltage, fuses and auto-reclosing.
Common mistake: using an isolator to break load current. Isolators are for off-load switching; only circuit breakers interrupt load and fault currents.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Best pick Circuit breaker
(opens en.wikipedia.org in a new tab)
Wikipedia, Circuit breaker, CC BY-SA 4.0 · licence
-
Fuse (electrical)
(opens en.wikipedia.org in a new tab)
Wikipedia, Fuse (electrical), CC BY-SA 4.0 · licence
-
Recloser
(opens en.wikipedia.org in a new tab)
Wikipedia, Recloser, CC BY-SA 4.0 · licence
Watch
-
TRV vs Recovery Voltage vs Restriking Voltage | Circuit Breaker Concepts Made Easy
8 min · ≈ 36 MB · about ₦20
(opens youtube.com in a new tab)
-
Arc Voltage | Recovery Voltage | Restriking Voltage | RRRV
8 min · ≈ 36 MB · about ₦20
(opens youtube.com in a new tab)
-
Restriking Voltage, RRRV, Recovery Voltage - Circuit Breakers and Fuses
5 min · ≈ 23 MB · about ₦13
(opens youtube.com in a new tab)
-
Lecture 34 Arc Interruption Theory in Circuit Breaker-I
32 min · ≈ 144 MB · about ₦81
(opens youtube.com in a new tab)
We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.