EEE 510 · Power Systems Engineering
Our notes
2 min readFaults and their causes
A fault is any abnormal condition, usually a short circuit: lightning, insulation failure, trees and animals on lines, vandalism, equipment failure, human error. Frequency (rough guide): single line-to-ground about 70 to 80%; line-to-line 8 to 15%; double line-to-ground 10%; three-phase about 5% (rarest but often most severe). Faults also include open circuits (broken conductors, blown fuses).
Short-circuit transient
When a three-phase fault occurs at a generator's terminals, the AC current is largest in the first few cycles (subtransient period, X″d), then decays (transient, X′d) to steady state (Xd). There may also be a decaying DC offset depending on the point on the voltage wave. Breaker ratings use the subtransient current, with allowances for the DC offset.
Calculating a three-phase fault
A balanced fault needs only the positive-sequence network: I_f = V_f ÷ Z_th, where V_f is the pre-fault voltage (often 1.0 pu) and Z_th the Thevenin impedance seen from the fault point.
Fault MVA (short-circuit level) = √3 × V_L × I_f, or in per unit: S_f = S_base ÷ Z_th (pu, with V_f = 1).
Worked example (from the reactance diagram topic)
Generator 0.4 pu, T1 0.1 pu, line 0.3 pu, T2 0.08 pu on 100 MVA. Fault at the 132 kV end of the line (before T2).
- Z_th = 0.4 + 0.1 + 0.3 = 0.8 pu; I_f = 1.0 ÷ 0.8 = 1.25 pu.
- Base current at 132 kV = 437.4 A, so I_f = 1.25 × 437.4 = 546.7 A.
- Fault level = 1.25 × 100 = 125 MVA.
Check: √3 × 132 kV × 546.7 A = 228.63 × 546.7 = 124,990 kVA ≈ 125 MVA. ✓
Fault at the generator terminals: Z_th = 0.4 pu, I_f = 2.5 pu. Base current at 11 kV = 100,000 ÷ (√3 × 11) = 5,248.6 A, so I_f = 13,121 A (250 MVA).
Fault studies with Z-bus
For large networks, I_f at bus k = V_f ÷ Z_kk (the diagonal element of Z-bus), and post-fault voltages are V_i = V_i(pre) − Z_ik I_f. Fault currents in lines follow from the voltages.
Limiting fault levels
Series reactors, splitting buses, higher-impedance transformers, and fault current limiters keep fault levels within breaker ratings as grids grow.
Uses
Choosing circuit-breaker ratings, setting protective relays, designing earthing and checking equipment strength.
Exams usually ask: describe causes and types of faults; explain the subtransient, transient and steady-state periods; compute three-phase fault currents and fault MVA in per unit; use Z-bus for fault analysis.
Common mistake: using the base current of the wrong voltage zone. Convert the per-unit fault current with the base current where the fault is.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Best pick Electrical fault
(opens en.wikipedia.org in a new tab)
Wikipedia, Electrical fault, CC BY-SA 4.0 · licence
-
MIT 6.061 Introduction to Electric Power Systems (whole course)
Lecture notes, problem sets and exams as PDFs: per unit, transmission lines, load flow, faults (harder than our notes).
(opens ocw.mit.edu in a new tab)
MIT OpenCourseWare, MIT 6.061 Introduction to Electric Power Systems (whole course), CC BY-NC-SA 4.0 · licence
Watch
-
Short Circuit MVA - Symmetrical Fault Analysis - Power System 2
19 min · ≈ 86 MB · about ₦48
(opens youtube.com in a new tab)
-
SHORT CIRCUIT MVA / FAULT MVA WITH CURRENT LIMITING REACTANCE / KTU/ POWER SYSTEM ANALYSIS
14 min · ≈ 63 MB · about ₦35
(opens youtube.com in a new tab)
-
Fault Calculation in Power System | Per Unit Method & Fault MVA Explained
10 min · ≈ 45 MB · about ₦25
(opens youtube.com in a new tab)
-
PS101 Short Circuit Transients in Alternator
22 min · ≈ 99 MB · about ₦56
(opens youtube.com in a new tab)
-
Lecture -25 Short Circuit Analysis
1 h · ≈ 270 MB · about ₦152
(opens youtube.com in a new tab)
We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.