EEE 510 · Power Systems Engineering

Symmetrical components

Fortescue's theorem, the operator a, positive, negative and zero sequence components, transforming between phase and sequence quantities, sequence impedances and sequence networks.

Our notes

2 min read

Fortescue's theorem (1918)

Any set of three unbalanced phasors can be written as the sum of three balanced sets:

  • Positive sequence (1): three equal phasors 120° apart, in the normal phase order a-b-c.
  • Negative sequence (2): three equal phasors 120° apart, in the reverse order a-c-b.
  • Zero sequence (0): three equal phasors in phase.

The operator a

a = 1∠120° = −0.5 + j0.866. Properties: a² = 1∠240° = −0.5 − j0.866, a³ = 1, and 1 + a + a² = 0.

Transformations

Phase from sequence:

  • I_a = I0 + I1 + I2
  • I_b = I0 + a²I1 + aI2
  • I_c = I0 + aI1 + a²I2

Sequence from phase:

  • I0 = (1/3)(I_a + I_b + I_c)
  • I1 = (1/3)(I_a + aI_b + a²I_c)
  • I2 = (1/3)(I_a + a²I_b + aI_c)

Worked example

I_a = 10∠0°, I_b = 10∠180° (= −10), I_c = 0 (a line-to-line current pattern).

  • I0 = (1/3)(10 − 10 + 0) = 0.
  • I1 = (1/3)(10 + a(−10)) = (1/3)(10 + 5 − j8.66) = 5 − j2.887 = 5.774∠−30°.
  • I2 = (1/3)(10 + a²(−10)) = (1/3)(10 + 5 + j8.66) = 5 + j2.887 = 5.774∠30°.

Check: I_a = 0 + (5 − j2.887) + (5 + j2.887) = 10 ✓. I_b = a²I1 + aI2 = 5.774∠−150° + 5.774∠150° = (−5 − j2.887) + (−5 + j2.887) = −10 ✓.

Useful facts

  • Zero-sequence current flows only if there is a return path: I_n = 3I0 in the neutral. A delta winding or ungrounded star blocks it from the lines.
  • A balanced system has only positive sequence; negative sequence indicates unbalance (it heats rotors of machines, so generators have negative-sequence protection).

Sequence impedances

  • Lines: Z1 = Z2; Z0 is larger (typically 2 to 3.5 times) because of ground return.
  • Transformers: Z1 = Z2 = Z0 (leakage) but the zero-sequence path depends on connections: grounded star to delta passes zero sequence on the star side only.
  • Generators: Z1, Z2 and Z0 all different; Z0 is small; a neutral impedance Z_n appears as 3Z_n in the zero-sequence network.

Sequence networks

Each sequence has its own network; only the positive-sequence network contains sources (generators produce balanced positive-sequence voltages). Unbalanced faults are solved by connecting the three networks at the fault point in ways set by the fault type (next topics).

Exams usually ask: state Fortescue's theorem; prove 1 + a + a² = 0; resolve unbalanced phasors into sequence components; explain zero-sequence paths through transformer connections.

Common mistake: forgetting the factor 1/3 when finding sequence components, or using a where a² belongs. Check by rebuilding the phase values.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.