EEE 510 · Power Systems Engineering

Transmission line models and performance

Line parameters, short, medium (nominal π) and long line models, ABCD constants, voltage regulation and efficiency, with a worked short-line example.

Our notes

2 min read

Line parameters

Series resistance R and inductance L (reactance X = 2πfL), and shunt capacitance C (susceptance B = 2πfC) and conductance G (leakage, usually neglected). They are distributed along the line; per-kilometre values depend on conductor size, spacing and bundling.

Classifying lines (at 50 Hz, rough guide)

ModelLengthTreatment
ShortUp to about 80 kmSeries impedance only; capacitance neglected
MediumAbout 80 to 250 kmLumped capacitance: nominal π (half at each end) or nominal T
LongAbove about 250 kmDistributed parameters: hyperbolic functions, equivalent π

ABCD constants

Sending-end quantities from receiving-end: V_S = A V_R + B I_R; I_S = C V_R + D I_R, with AD − BC = 1.

  • Short line: A = D = 1, B = Z, C = 0.
  • Nominal π: A = D = 1 + YZ/2, B = Z, C = Y(1 + YZ/4).
  • Long line: A = D = cosh γl, B = Z_c sinh γl, C = sinh γl ÷ Z_c, where γ is the propagation constant and Z_c the characteristic impedance.

Voltage regulation and efficiency

  • Voltage regulation = (V_R at no load − V_R at full load) ÷ V_R at full load × 100. For a short line, V_R at no load = V_S.
  • Efficiency = power received ÷ power sent × 100.

Worked example: short line

An 11 kV three-phase line has Z = 2 + j4 Ω per phase and delivers 2 MW at 0.8 power factor lagging at 11 kV.

  1. Receiving phase voltage V_R = 11,000 ÷ √3 = 6,350.9 V (reference, angle 0).
  2. Current I = 2,000,000 ÷ (√3 × 11,000 × 0.8) = 2,000,000 ÷ 15,242 = 131.2 A at −36.87°: I = 104.97 − j78.73 A.
  3. Voltage drop I × Z = (104.97 − j78.73)(2 + j4) = 209.94 + j419.88 − j157.46 + 314.92 = 524.86 + j262.42 V.
  4. V_S = 6,350.9 + 524.86 + j262.42 = 6,875.8 + j262.42 V; magnitude 6,880.7 V per phase (11,918 V line).
  5. Regulation = (6,880.7 − 6,350.9) ÷ 6,350.9 = 8.34%.
  6. Loss = 3 × 131.2² × 2 = 103.3 kW; efficiency = 2,000 ÷ 2,103.3 = 95.1%.

Check with the approximate drop I(R cos φ + X sin φ) = 131.2 × (2 × 0.8 + 4 × 0.6) = 131.2 × 4.0 = 524.8 V, so about 8.26%: close to the exact 8.34%. ✓

Ferranti effect

On a long, lightly loaded line, the charging current through the series inductance makes the receiving-end voltage higher than the sending-end voltage. Shunt reactors are used to control it.

Improving performance

Raise voltage, bundle conductors, add series capacitors (reduce X), shunt capacitors or reactors, and improve load power factor.

Exams usually ask: classify lines and state the models; derive ABCD constants for short and nominal π lines; compute sending-end voltage, regulation and efficiency of a short line; explain the Ferranti effect.

Common mistake: mixing line and phase values. Work per phase (phase voltage, line current), then convert the answer back to line voltage.