Representation of power systems

Single-line diagrams, models of generators, transformers, lines and loads, impedance and reactance diagrams, and building a per-unit reactance diagram.

Our notes

2 min read

Single-line (one-line) diagram

A balanced three-phase system can be analysed per phase, so it is drawn with one line standing for three phases, with standard symbols for generators, transformers (with connections: star, delta, grounded star), circuit breakers, buses, lines and loads. It also shows ratings (MVA, kV, impedance).

Component models

ComponentModel for load flow and faults
Synchronous generatorInternal voltage E behind a reactance (subtransient X″d for the first cycles of a fault, transient X′d, synchronous Xd for steady state)
TransformerSeries leakage impedance (magnetising branch usually neglected); off-nominal taps as a modified admittance
Transmission lineSeries R + jX and shunt capacitance (short, medium or long line model)
LoadConstant power (P + jQ), constant current or constant impedance
MotorLike a generator: internal voltage behind reactance (contributes to fault current)

Impedance and reactance diagrams

The impedance diagram replaces each component by its per-phase equivalent circuit in per unit. For fault studies a reactance diagram is often used: resistances, shunt capacitances and magnetising currents are neglected (they are small compared with reactances in HV networks), and loads are often omitted.

Worked example: building a reactance diagram

System: a generator (50 MVA, 11 kV, X″ = 0.2 pu) feeds transformer T1 (100 MVA, 11/132 kV, X = 0.1 pu), a 132 kV line of X = 52.27 Ω, and transformer T2 (100 MVA, 132/33 kV, X = 0.08 pu) to a 33 kV load bus. Base: 100 MVA, 11 kV in the generator zone.

  1. Base voltages: 11 kV (generator), 132 kV (line), 33 kV (load) from the transformer ratios.
  2. Generator: 0.2 × (100 ÷ 50) = 0.4 pu.
  3. T1: already on 100 MVA and matching voltages: 0.1 pu.
  4. Line: Z_b = 174.24 Ω, so 52.27 ÷ 174.24 = 0.3 pu.
  5. T2: 0.08 pu.

Series reactance from the generator's internal voltage to the 33 kV bus: 0.4 + 0.1 + 0.3 + 0.08 = 0.88 pu. This diagram is used for the fault examples later.

Why representation matters

Every later study (load flow, faults, stability, protection settings) starts from a correct model. Wrong data or wrong base conversions give wrong results everywhere.

Exams usually ask: draw a single-line diagram from a description; state component models; convert a single-line diagram into a per-unit reactance diagram on a common base.

Common mistake: using the generator's own MVA rating as the base after choosing a system base. Convert every component to the one common base.