UNIHIVE

Study Hub UNIPORT EEE 510

EEE 510 · Power Systems Engineering

The bus admittance matrix and network equations

Nodal analysis, forming Y-bus by inspection, its properties, including line charging and transformers, and the power flow equations at each bus.

Our notes

2 min read

Nodal equations

For a network with n buses, the injected currents and bus voltages are related by I = Y_bus V. Nodal analysis suits power systems because buses are natural nodes and Y_bus is easy to build and sparse.

Forming Y-bus by inspection

  • Diagonal element Y_ii = sum of all admittances connected to bus i (including shunt admittances to ground).
  • Off-diagonal element Y_ij = minus the admittance of the branch between buses i and j (zero if not connected).

Worked example

A three-bus network has lines with series reactances: 1-2: j0.1 pu, 1-3: j0.2 pu, 2-3: j0.25 pu (shunt charging neglected).
Line admittances y = 1 ÷ (jX): y12 = −j10, y13 = −j5, y23 = −j4.

Bus 1Bus 2Bus 3
Bus 1−j15j10j5
Bus 2j10−j14j4
Bus 3j5j4−j9

Checks: Y11 = y12 + y13 = −j10 − j5 = −j15 ✓; each row sums to zero because there are no shunt elements. ✓

Line charging and transformers

  • With the π model, half the line charging susceptance (jB/2) is added to each end's diagonal element.
  • An off-nominal tap transformer is modelled by a π circuit whose elements depend on the tap ratio.

Properties of Y-bus

Square, symmetric (without phase-shifting transformers), sparse (most buses connect to only a few others: in a 1,000-bus grid over 99% of entries are zero), and diagonally dominant. Its inverse, Z-bus, is full and is used in fault studies.

Power flow equations

The complex power injected at bus i: S_i = P_i + jQ_i = V_i × conj(I_i), with I_i = Σ Y_ik V_k.
In polar form, with V_i = |V_i|∠δ_i and Y_ik = |Y_ik|∠θ_ik:

  • P_i = Σ |V_i||V_k||Y_ik| cos(θ_ik − δ_i + δ_k)
  • Q_i = −Σ |V_i||V_k||Y_ik| sin(θ_ik − δ_i + δ_k)

These are non-linear in V and δ, so load flow needs iterative methods.

Exams usually ask: form Y-bus for a given network; explain its properties; include line charging; derive the power flow equations.

Common mistake: forgetting the minus sign on off-diagonal elements, or adding reactances instead of admittances on the diagonal.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.

Read

Watch

We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.

All EEE 510 topics

Report

Sign in to report this. It is free.

Is this your work (a lecturer, author or publisher)? Ask us to take it down.