EEE 510 · Power Systems Engineering
Our notes
2 min readPurpose
A load flow (power flow) study finds the steady-state voltage magnitude and angle at every bus for given loads and generation, and from them the line flows and losses. Used for planning, operation, contingency studies and as the starting point for stability and fault studies.
Bus types
| Bus type | Specified | Unknown |
|---|---|---|
| Slack (swing, reference) | V (magnitude), δ (usually 1.0∠0°) | P, Q (it supplies the losses and balance) |
| PV (generator, voltage-controlled) | P, V (magnitude) | Q, δ |
| PQ (load) | P, Q | V (magnitude), δ |
Usually one slack bus, a few PV buses, and many PQ buses. PV buses also have Q limits; if violated, they are treated as PQ at the limit.
Gauss-Seidel algorithm
For a PQ bus i:
V_i(new) = (1 ÷ Y_ii) × [ (P_i − jQ_i) ÷ conj(V_i(old)) − Σ (k ≠ i) Y_ik V_k ]
using the newest available voltages for other buses. Repeat until changes are below a tolerance (say 0.0001 pu). An acceleration factor (about 1.4 to 1.6) speeds convergence: V(acc) = V(old) + α(V(new) − V(old)).
Worked example: two buses
Bus 1 is the slack, V1 = 1.0∠0°. Bus 2 is a PQ bus with a load of 0.5 + j0.2 pu, so P2 = −0.5, Q2 = −0.2. Line reactance j0.1: Y22 = −j10, Y21 = j10. Start V2 = 1.0∠0°. (1 ÷ Y22 = j0.1.)
Iteration 1.
- (P2 − jQ2) ÷ conj(V2) = (−0.5 + j0.2) ÷ 1 = −0.5 + j0.2.
- Subtract Y21V1 = j10: −0.5 + j0.2 − j10 = −0.5 − j9.8.
- Multiply by j0.1: V2 = 0.98 − j0.05 (|V2| = 0.9813).
Iteration 2.
- (−0.5 + j0.2) ÷ (0.98 + j0.05) = (−0.5 + j0.2)(0.98 − j0.05) ÷ 0.9629 = (−0.48 + j0.221) ÷ 0.9629 = −0.4985 + j0.2295.
- Subtract j10: −0.4985 − j9.7705.
- Multiply by j0.1: V2 = 0.97705 − j0.04985, |V2| = 0.9783, angle −2.92°.
Check by power balance. I2 = Y21V1 + Y22V2 = j10 + (−j10)(0.97705 − j0.04985) = −0.4985 + j0.2295. S2 = V2 × conj(I2) = (0.97705 − j0.04985)(−0.4985 − j0.2295) = −0.4985 − j0.1994, almost exactly the specified −0.5 − j0.2. ✓ One or two more iterations settle it.
Pros and cons
Gauss-Seidel is simple, needs little memory, and each iteration is fast, but convergence is slow (number of iterations grows with system size) and can fail for heavily loaded systems.
Exams usually ask: state the bus types and their specified quantities; write the Gauss-Seidel update; carry out one or two iterations by hand; explain acceleration factors and treatment of PV buses.
Common mistake: using V instead of conj(V) in the (P − jQ) term. It must be the complex conjugate.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Best pick Power-flow study
(opens en.wikipedia.org in a new tab)
Wikipedia, Power-flow study, CC BY-SA 4.0 · licence
-
Gauss–Seidel method
(opens en.wikipedia.org in a new tab)
Wikipedia, Gauss–Seidel method, CC BY-SA 4.0 · licence
-
MIT 6.061 Introduction to Electric Power Systems (whole course)
Lecture notes, problem sets and exams as PDFs: per unit, transmission lines, load flow, faults (harder than our notes).
(opens ocw.mit.edu in a new tab)
MIT OpenCourseWare, MIT 6.061 Introduction to Electric Power Systems (whole course), CC BY-NC-SA 4.0 · licence
Watch
-
Gauss Seidel Method with Example
14 min · ≈ 63 MB · about ₦35
(opens youtube.com in a new tab)
-
Problem Based on Gauss Seidel Method
18 min · ≈ 81 MB · about ₦45
(opens youtube.com in a new tab)
-
Lecture - 26 Load Flow Studies
51 min · ≈ 230 MB · about ₦129
(opens youtube.com in a new tab)
-
Gauss Seidel Method and Algorithm - Load Flow Studies - Power System 3
1 h 4 min · ≈ 288 MB · about ₦162
(opens youtube.com in a new tab)
-
GAUSS SEIDEL LOAD FLOW PROBLEM- 1 / KTU/ POWER SYSTEM ANALYSIS
31 min · ≈ 140 MB · about ₦79
(opens youtube.com in a new tab)
-
Lecture 37: Power flow analysis- Gauss-Seidel method.
40 min · ≈ 180 MB · about ₦101
(opens youtube.com in a new tab)
We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.