CHE 513 · Process Dynamics and Control
Our notes
3 min readSensors
| Variable | Common sensors |
|---|---|
| Temperature | Thermocouples (type K, J: wide range, cheap), resistance temperature detectors (RTDs, Pt100: accurate), thermistors; always in a thermowell |
| Pressure | Bourdon tubes, diaphragm and strain-gauge or capacitance transmitters |
| Flow | Orifice plate with differential pressure (DP) cell (flow ∝ √ΔP), magnetic, vortex, turbine, Coriolis (mass flow), ultrasonic |
| Level | DP cell (level from hydrostatic head), displacer, float, radar, ultrasonic, nuclear (difficult services) |
| Composition | Gas chromatographs, pH probes, conductivity, infrared analysers, oxygen analysers (often with dead time) |
Transmitters and signals
A transmitter converts the sensor reading to a standard signal: 4-20 mA current (most common; 4 mA "live zero" detects broken wires), 3-15 psig pneumatic (older plants), or digital (HART, Foundation Fieldbus, Profibus). A transducer converts between signal types (current-to-pressure, I/P, for valve actuators).
Worked example. A temperature transmitter spans 0 to 200°C as 4 to 20 mA. At 120°C: 4 + 16 × (120/200) = 4 + 9.6 = 13.6 mA. Reverse: 10 mA means (10 − 4)/16 × 200 = 75°C. Check: 4 + 16 × 75/200 = 10 mA. ✓
Control valves
- Types: globe (most common for throttling), ball, butterfly (large flows, low ΔP), diaphragm (slurries).
- Actuators: pneumatic diaphragm with spring (most common), electric, hydraulic.
- Fail-safe action: air-to-open (fail-closed) for fuel and steam to heaters (shut on air failure); air-to-close (fail-open) for cooling water to an exothermic reactor. The choice is a safety decision.
- Positioners: a local controller on the valve that makes the stem position match the signal, overcoming friction and high pressure drop.
Valve characteristics (flow against stem travel at constant ΔP)
| Characteristic | Relation | Use |
|---|---|---|
| Linear | f = l | Level control, where ΔP across the valve is fairly constant |
| Equal percentage | f = R^(l − 1) | Most common: compensates for falling ΔP as flow rises; temperature and flow loops |
| Quick opening | Large flow at small opening | On-off and safety service |
(f = fraction of maximum flow, l = fraction of stem travel, R = rangeability, often 50.)
Worked example. Equal percentage, R = 50, half open (l = 0.5): f = 50^(−0.5) = 1 ÷ 7.07 = 0.141 (14% of maximum flow). Check: each 10% of travel multiplies flow by 50^0.1 = 1.48, the constant percentage that gives the name. ✓
Valve sizing
Liquid flow (US units): q = Cv √(ΔP ÷ SG) (q in gal/min, ΔP in psi). A valve with Cv = 20 passing water (SG = 1) with ΔP = 16 psi gives q = 20 × 4 = 80 gal/min (about 303 L/min). Size so the valve works between about 20% and 80% open at normal flow.
Analog computation
Before digital computers, analog computers built from operational amplifiers (summers, integrators, multipliers) solved process differential equations in real time and simulated control loops; an op-amp integrator's output is −(1/RC)∫v dt. The same ideas live on in analog electronic controllers.
Digital control
Distributed control systems (DCS) and PLCs run PID algorithms digitally, sampling every fraction of a second, with operator screens, alarms, trends and historians; safety instrumented systems (SIS) are kept separate for emergency shutdown. Sample fast compared with the loop's time constant (typically 10 or more samples per time constant). Cyber security of control systems is now a design requirement.
Exams usually ask: describe sensors for temperature, pressure, flow and level; explain 4-20 mA signals; describe control valve types, characteristics and fail-safe choice; size a valve with the Cv equation; describe DCS and digital control.
Common mistake: choosing valve fail action for convenience. Ask what is safest on air or power failure: fuel and steam usually fail closed; cooling usually fails open.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Best pick Woolf, Chemical Process Dynamics and Controls, 3.9 Valves: types, kinds and selection
(opens eng.libretexts.org in a new tab)
LibreTexts, Woolf, Chemical Process Dynamics and Controls, 3.9 Valves: types, kinds and selection, CC BY 3.0 · licence
-
Woolf, Chemical Process Dynamics and Controls, 3.1 Measurement devices
(opens eng.libretexts.org in a new tab)
LibreTexts, Woolf, Chemical Process Dynamics and Controls, 3.1 Measurement devices, CC BY 3.0 · licence
-
Control valve
(opens en.wikipedia.org in a new tab)
Wikipedia, Control valve, CC BY-SA 4.0 · licence
-
Piping and instrumentation diagram
(opens en.wikipedia.org in a new tab)
Wikipedia, Piping and instrumentation diagram, CC BY-SA 4.0 · licence
-
Woolf et al., Chemical Process Dynamics and Controls (whole free textbook)
University of Michigan's open process-control textbook on LibreTexts (CC BY 3.0): sensors and valves, modelling, Laplace transforms, PID, stability, control architectures. A full PDF is offered on the page.
(opens eng.libretexts.org in a new tab)
LibreTexts, Woolf et al., Chemical Process Dynamics and Controls (whole free textbook), CC BY 3.0 · licence
Watch
We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.