CHE 513 · Process Dynamics and Control
Our notes
3 min readBasic loops
| Loop | Typical scheme | Notes |
|---|---|---|
| Flow | PI on a valve in the line | Fast, noisy: no derivative |
| Level | P or slow PI on outlet (or inlet) flow | Averaging level control lets the level float to smooth flows to the next unit |
| Gas pressure | PI on a vent or inlet valve | Fast |
| Liquid pressure | PI, fast like flow | |
| Temperature | PID, often cascaded to a flow or a jacket temperature | Slow, lag-dominated |
Heat exchangers
Outlet temperature of the process stream controlled by the heating or cooling medium flow (steam valve, often cascaded to steam flow or pressure), or by bypassing part of the process stream around the exchanger (faster response).
Furnaces and boilers
Outlet temperature cascaded to fuel flow; fuel-air ratio with cross-limiting (air leads on increase, fuel leads on decrease, so the mixture never becomes fuel-rich); excess oxygen trim from an analyser; drum level with three-element control (drum level, steam flow and feedwater flow) to handle inverse response.
Chemical reactors
- Temperature is the key variable (exothermic reactions can run away): reactor temperature cascaded to jacket or coolant temperature; feedforward from feed flow; high-temperature interlocks.
- Pressure for gas-phase reactors; level for liquid-phase CSTRs; feed ratio of reactants.
Distillation columns
- Pressure: condenser duty (cooling water or air-cooler fans) or vent.
- Levels: reflux drum level by distillate (or reflux) flow; column base level by bottoms flow.
- Compositions (often inferred from tray temperatures): top composition by reflux flow, bottom composition by reboiler steam.
- Feed disturbances handled by feedforward on reflux and boil-up.
The common LV configuration (reflux L and boil-up V for compositions) suffers from interaction (RGA checks); other configurations swap the level and composition pairings.
Plant-wide control
- Decide the throughput manipulator (usually the feed flow) and control inventories (levels and pressures) in the direction of flow away from it.
- Control product quality and safety variables tightly; let some levels float.
- Handle recycles: fixing a flow somewhere in each recycle loop avoids the "snowball effect" (large recycle swings from small feed changes).
- Use heat integration carefully: exchangers coupling units also couple their disturbances.
- Add optimisation layers (MPC, real-time optimisation) above basic control.
Worked example: averaging level control
A surge tank (A = 10 m²) smooths inflow swings of ±2 m³/min. Allowed level band ±0.5 m about the set point. With P-only control, the outflow changes by Kc × (level change): to let the full ±2 m³/min swing pass through gradually as the level moves 0.5 m, Kc = 2 ÷ 0.5 = 4 m³/min per m. The closed-loop time constant τ = A ÷ Kc = 10 ÷ 4 = 2.5 min, so outflow changes are spread over minutes instead of passing through at once. Check: at the edge of the band, outflow change = 4 × 0.5 = 2 m³/min, matching the inflow change, so the level stops moving there. ✓
Exams usually ask: sketch control schemes for heat exchangers, furnaces, reactors and distillation columns; explain cascade and ratio use in them; discuss plant-wide control decisions such as throughput manipulator and recycle control.
Common mistake: controlling every level tightly. Tight level control passes every flow disturbance straight to the next unit; surge tanks need averaging control.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Best pick Woolf, Chemical Process Dynamics and Controls, 11.5 Control loops for liquid pressure and level
(opens eng.libretexts.org in a new tab)
LibreTexts, Woolf, Chemical Process Dynamics and Controls, 11.5 Control loops for liquid pressure and level, CC BY 3.0 · licence
-
Piping and instrumentation diagram
(opens en.wikipedia.org in a new tab)
Wikipedia, Piping and instrumentation diagram, CC BY-SA 4.0 · licence
-
Woolf, Chemical Process Dynamics and Controls, 11.6 Control loops for temperature
(opens eng.libretexts.org in a new tab)
LibreTexts, Woolf, Chemical Process Dynamics and Controls, 11.6 Control loops for temperature, CC BY 3.0 · licence
-
Woolf, Chemical Process Dynamics and Controls, 11.7 Control architectures for reactors
(opens eng.libretexts.org in a new tab)
LibreTexts, Woolf, Chemical Process Dynamics and Controls, 11.7 Control architectures for reactors, CC BY 3.0 · licence
-
Distributed control system
(opens en.wikipedia.org in a new tab)
Wikipedia, Distributed control system, CC BY-SA 4.0 · licence
-
Woolf et al., Chemical Process Dynamics and Controls (whole free textbook)
University of Michigan's open process-control textbook on LibreTexts (CC BY 3.0): sensors and valves, modelling, Laplace transforms, PID, stability, control architectures. A full PDF is offered on the page.
(opens eng.libretexts.org in a new tab)
LibreTexts, Woolf et al., Chemical Process Dynamics and Controls (whole free textbook), CC BY 3.0 · licence
Watch
We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.