CHE 513 · Process Dynamics and Control
Our notes
2 min readFeedforward control
Measure the disturbance and adjust the MV before the CV moves.
Ideal feedforward controller: Gf = −Gd ÷ (Gv Gp Gt), where Gt is the disturbance transmitter.
Worked example. Gp = 2 ÷ (5s + 1), Gd = 1 ÷ (5s + 1), Gv = Gt = 1. Gf = −(1/(5s + 1)) ÷ (2/(5s + 1)) = −0.5: a simple gain. If instead Gd = 1 ÷ (10s + 1), Gf = −0.5 (5s + 1) ÷ (10s + 1): a lead-lag unit. Check (static case): a disturbance of +1 changes the output by +1 × 1 directly and by −0.5 × 2 = −1 through the process: net zero. ✓
Feedforward cannot correct unmeasured disturbances or model errors, so it is combined with feedback trim.
Cascade control
Two loops, one inside the other: the primary (master) controller sets the set point of the secondary (slave) controller.
- Example: reactor temperature (primary) → jacket temperature or coolant flow (secondary) → coolant valve.
- The fast inner loop corrects disturbances in the secondary variable (coolant pressure, temperature) before they reach the main process.
- Requirements: the secondary loop must be faster than the primary (about 3 to 5 times); tune the inner loop first.
Ratio control
Keep the ratio of two flows constant: fuel-to-air in a furnace, reactant feeds, blending of petrol components. The wild flow is measured; the controlled flow's set point = ratio × wild flow.
Split-range control
One controller drives two valves over different parts of its output range (0 to 50% opens cooling, 50 to 100% opens heating), common in batch reactors.
Override and selective control
A low or high selector picks between controllers, for example to protect equipment: a compressor normally on flow control switches to pressure control if discharge pressure approaches its limit. Auctioneering: use the highest of several temperatures in a reactor bed.
Multivariable control and interaction
Many units have several inputs affecting several outputs (a distillation column: reflux and boil-up both affect top and bottom compositions). Loops interact: moving one MV disturbs the other loop.
The relative gain array (RGA) guides pairing. For a 2×2 process with steady-state gains K₁₁, K₁₂, K₂₁, K₂₂: λ₁₁ = 1 ÷ [1 − (K₁₂K₂₁) ÷ (K₁₁K₂₂)]; the other elements follow because each row and column sums to 1.
Worked example. K₁₁ = 2, K₁₂ = 1.5, K₂₁ = 1.5, K₂₂ = 2. λ₁₁ = 1 ÷ (1 − 2.25/4) = 1 ÷ 0.4375 = 2.29; λ₁₂ = 1 − 2.29 = −1.29. Pair 1-1 and 2-2 (positive λ, the pairing nearest 1); never pair on a negative relative gain (the loop would reverse its action when the other loop closes). λ = 2.29 warns of strong interaction: consider decoupling or model predictive control. Check: row sum 2.29 − 1.29 = 1. ✓
Model predictive control (MPC) uses a dynamic model to compute moves of all MVs together while respecting constraints; it is standard in refineries and petrochemical plants.
Exams usually ask: design a feedforward controller; explain and draw cascade, ratio, split-range and override schemes; compute the RGA and recommend pairings.
Common mistake: making the secondary loop of a cascade slower than the primary. The inner loop must respond much faster, or the cascade gives no benefit.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Best pick Woolf, Chemical Process Dynamics and Controls, 11.3 Cascade control
(opens eng.libretexts.org in a new tab)
LibreTexts, Woolf, Chemical Process Dynamics and Controls, 11.3 Cascade control, CC BY 3.0 · licence
-
Woolf, Chemical Process Dynamics and Controls, 11.2 Feed-forward control
(opens eng.libretexts.org in a new tab)
LibreTexts, Woolf, Chemical Process Dynamics and Controls, 11.2 Feed-forward control, CC BY 3.0 · licence
-
Woolf, Chemical Process Dynamics and Controls, 11.4 Ratio control
(opens eng.libretexts.org in a new tab)
LibreTexts, Woolf, Chemical Process Dynamics and Controls, 11.4 Ratio control, CC BY 3.0 · licence
-
Model predictive control
(opens en.wikipedia.org in a new tab)
Wikipedia, Model predictive control, CC BY-SA 4.0 · licence
-
Woolf et al., Chemical Process Dynamics and Controls (whole free textbook)
University of Michigan's open process-control textbook on LibreTexts (CC BY 3.0): sensors and valves, modelling, Laplace transforms, PID, stability, control architectures. A full PDF is offered on the page.
(opens eng.libretexts.org in a new tab)
LibreTexts, Woolf et al., Chemical Process Dynamics and Controls (whole free textbook), CC BY 3.0 · licence
Watch
-
Introduction to Cascade Control
10 min · ≈ 45 MB · about ₦25
(opens youtube.com in a new tab)
-
Introduction to Feedforward Control
9 min · ≈ 41 MB · about ₦23
(opens youtube.com in a new tab)
-
Cascade, Ratio and Feed Forward Control
57 min · ≈ 257 MB · about ₦144
(opens youtube.com in a new tab)
-
Feedforward and Cascade Control Examples
27 min · ≈ 122 MB · about ₦69
(opens youtube.com in a new tab)
We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.