CHE 513 · Process Dynamics and Control

Feedforward, cascade and multivariable control

Feedforward control and its design, combined feedforward-feedback, cascade control, ratio, split-range, override and selective control, and an introduction to multivariable control and the relative gain array.

Our notes

2 min read

Feedforward control

Measure the disturbance and adjust the MV before the CV moves.
Ideal feedforward controller: Gf = −Gd ÷ (Gv Gp Gt), where Gt is the disturbance transmitter.
Worked example. Gp = 2 ÷ (5s + 1), Gd = 1 ÷ (5s + 1), Gv = Gt = 1. Gf = −(1/(5s + 1)) ÷ (2/(5s + 1)) = −0.5: a simple gain. If instead Gd = 1 ÷ (10s + 1), Gf = −0.5 (5s + 1) ÷ (10s + 1): a lead-lag unit. Check (static case): a disturbance of +1 changes the output by +1 × 1 directly and by −0.5 × 2 = −1 through the process: net zero. ✓
Feedforward cannot correct unmeasured disturbances or model errors, so it is combined with feedback trim.

Cascade control

Two loops, one inside the other: the primary (master) controller sets the set point of the secondary (slave) controller.

  • Example: reactor temperature (primary) → jacket temperature or coolant flow (secondary) → coolant valve.
  • The fast inner loop corrects disturbances in the secondary variable (coolant pressure, temperature) before they reach the main process.
  • Requirements: the secondary loop must be faster than the primary (about 3 to 5 times); tune the inner loop first.

Ratio control

Keep the ratio of two flows constant: fuel-to-air in a furnace, reactant feeds, blending of petrol components. The wild flow is measured; the controlled flow's set point = ratio × wild flow.

Split-range control

One controller drives two valves over different parts of its output range (0 to 50% opens cooling, 50 to 100% opens heating), common in batch reactors.

Override and selective control

A low or high selector picks between controllers, for example to protect equipment: a compressor normally on flow control switches to pressure control if discharge pressure approaches its limit. Auctioneering: use the highest of several temperatures in a reactor bed.

Multivariable control and interaction

Many units have several inputs affecting several outputs (a distillation column: reflux and boil-up both affect top and bottom compositions). Loops interact: moving one MV disturbs the other loop.
The relative gain array (RGA) guides pairing. For a 2×2 process with steady-state gains K₁₁, K₁₂, K₂₁, K₂₂: λ₁₁ = 1 ÷ [1 − (K₁₂K₂₁) ÷ (K₁₁K₂₂)]; the other elements follow because each row and column sums to 1.
Worked example. K₁₁ = 2, K₁₂ = 1.5, K₂₁ = 1.5, K₂₂ = 2. λ₁₁ = 1 ÷ (1 − 2.25/4) = 1 ÷ 0.4375 = 2.29; λ₁₂ = 1 − 2.29 = −1.29. Pair 1-1 and 2-2 (positive λ, the pairing nearest 1); never pair on a negative relative gain (the loop would reverse its action when the other loop closes). λ = 2.29 warns of strong interaction: consider decoupling or model predictive control. Check: row sum 2.29 − 1.29 = 1. ✓
Model predictive control (MPC) uses a dynamic model to compute moves of all MVs together while respecting constraints; it is standard in refineries and petrochemical plants.

Exams usually ask: design a feedforward controller; explain and draw cascade, ratio, split-range and override schemes; compute the RGA and recommend pairings.

Common mistake: making the secondary loop of a cascade slower than the primary. The inner loop must respond much faster, or the cascade gives no benefit.