UNIHIVE

Study Hub UNIPORT CHE 513

CHE 513 · Process Dynamics and Control

Controller tuning

Performance criteria, the Ziegler-Nichols continuous cycling and reaction curve methods, Cohen-Coon and integral error criteria, direct synthesis and IMC tuning, and field tuning practice.

Our notes

2 min read

What good tuning means

A balance between speed (fast response to set-point changes and disturbances), stability (adequate margins), little overshoot, robustness to model errors, and gentle valve movement. Criteria:

  • Quarter decay ratio (classic).
  • Integral error criteria: IAE = ∫|e| dt, ISE = ∫e² dt, ITAE = ∫t|e| dt (smaller is better; ITAE punishes errors that last).

Ziegler-Nichols continuous cycling method

  1. Put the controller on P only; raise Kc until the loop oscillates steadily: that gain is Ku, and the period is Pu.
  2. Set:
ControllerKcτIτD
P0.5 Ku
PI0.45 KuPu ÷ 1.2
PID0.6 KuPu ÷ 2Pu ÷ 8

Worked example. From the stability topic, Ku = 8 and Pu = 3.63 (time units).

  • PI: Kc = 0.45 × 8 = 3.6, τI = 3.63 ÷ 1.2 = 3.02.
  • PID: Kc = 0.6 × 8 = 4.8, τI = 3.63 ÷ 2 = 1.81, τD = 3.63 ÷ 8 = 0.45.

Check: the P setting 0.5 Ku = 4 gives a gain margin of 2, matching the Bode result. ✓ Z-N settings are aggressive (near quarter decay); many engineers start with them and then reduce Kc.
Drawback: driving a real plant to the edge of instability can be unsafe.

Process reaction curve methods

Open the loop, step the controller output, record the response, fit an FOPDT model (K, τ, θ), and use a table. Ziegler-Nichols reaction curve rules for PI: Kc = 0.9τ ÷ (Kθ), τI = 3.33θ. Cohen-Coon rules adjust these for larger θ/τ.
Worked example. K = 2, τ = 6 min, θ = 4 min (the FOPDT model fitted earlier). Z-N PI: Kc = 0.9 × 6 ÷ (2 × 4) = 0.675, τI = 3.33 × 4 = 13.3 min.

Direct synthesis and IMC tuning

Choose the desired closed-loop response (for example first-order with time constant τc) and solve for the controller. For an FOPDT process, IMC-based PI tuning: Kc = τ ÷ [K(τc + θ)], τI = τ. With τc = θ = 4 min: Kc = 6 ÷ (2 × 8) = 0.375, τI = 6 min. One parameter (τc) trades speed against robustness: smaller τc means faster but less robust control. Check: IMC gives a gentler gain (0.375) than Z-N (0.675), as expected from a method designed for robustness. ✓

Field tuning practice

  • Tune flow loops first (fast), then the loops above them (cascade masters, level, temperature).
  • Change one parameter at a time; test with small set-point steps.
  • Watch valve movement; avoid saturating it.
  • Typical starting points: flow PI with Kc 0.4 to 0.6 and τI of a few seconds; level often P or slow PI (averaging).

Exams usually ask: state performance criteria; apply Ziegler-Nichols continuous cycling or reaction curve rules; use Cohen-Coon or IMC formulas; discuss practical tuning.

Common mistake: using Z-N settings as final values. They are a starting point, usually too oscillatory for modern plants.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.

Read

Watch

We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.

All CHE 513 topics

Report

Sign in to report this. It is free.

Is this your work (a lecturer, author or publisher)? Ask us to take it down.