CHE 513 · Process Dynamics and Control

Higher-order systems, dead time and inverse response

Poles and zeros, interacting and non-interacting tanks, dead time and its effect, Padé approximation, first-order-plus-dead-time models, and inverse response.

Our notes

2 min read

Poles and zeros

G(s) = N(s) ÷ D(s). Poles (roots of D) decide the form and stability of the response; zeros (roots of N) change the size of each term. A zero in the right half plane gives an inverse response.

Interacting and non-interacting systems

  • Non-interacting: the second tank does not affect the first (the first drains freely into the second): G = K ÷ [(τ₁s + 1)(τ₂s + 1)].
  • Interacting: the flow between tanks depends on both levels: the overall response is slower; the effective time constants spread apart.

Dead time (transport lag)

A delay θ between a change in input and any change in output: fluid travelling down a pipe, a conveyor belt, an analyser sampling time. G(s) = e^(−θs).
Worked example. Liquid flows at 0.5 m/s in a 20 m pipe from a mixing point to a sensor: θ = 20 ÷ 0.5 = 40 s. During those 40 s the controller sees nothing, which limits how fast it can act.
Dead time is the main enemy of tight control: it adds phase lag without reducing gain.

Padé approximation

For analysis, e^(−θs) ≈ (1 − θs/2) ÷ (1 + θs/2) (first order). It replaces the delay by a rational function, with a right-half-plane zero (hence the initial dip it shows).

First-order-plus-dead-time (FOPDT) models

Most real process step responses (S-shaped) can be approximated by G(s) = K e^(−θs) ÷ (τs + 1), fitted from a step test:

  • K = final change in output ÷ change in input.
  • From the response curve, the times to reach 28.3% and 63.2% of the final change (t₂₈ and t₆₃): τ = 1.5(t₆₃ − t₂₈), θ = t₆₃ − τ.

Worked example. A valve step of 5% raises temperature by 10°C finally (K = 2°C per %); t₂₈ = 6 min and t₆₃ = 10 min. τ = 1.5 × 4 = 6 min; θ = 10 − 6 = 4 min. Check: at t = θ + τ/3 = 4 + 2 = 6 min the FOPDT model gives 1 − e^(−1/3) = 28.3%, and at t = θ + τ = 10 min it gives 63.2%, matching both data points. ✓

Inverse response

The output first moves the wrong way before going to its final value: two opposing effects with different speeds, e.g. boiler drum level after a step increase in feedwater (cold water collapses steam bubbles, level first drops, then rises), or a reboiler duty increase in a distillation column. The transfer function has a right-half-plane zero; aggressive control makes it worse.

Higher-order lags

n equal lags in series: G = K ÷ (τs + 1)ⁿ: the response becomes more S-shaped and looks like dead time plus a lag, which is why FOPDT models fit so many processes.

Exams usually ask: compare interacting and non-interacting tanks; explain dead time and its effect on control; use the Padé approximation; fit an FOPDT model from step data; explain inverse response with an example.

Common mistake: treating dead time as a slow time constant. A lag responds at once but slowly; dead time shows no response at all for θ seconds.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.