CHE 513 · Process Dynamics and Control
Our notes
2 min readThe standard form
G(s) = K ÷ (τ²s² + 2ζτs + 1), with τ the natural period (1/τ is the natural frequency) and ζ the damping ratio.
Kinds of response to a step
| Damping | Poles | Response |
|---|---|---|
| ζ > 1, overdamped | Two real, distinct | Sluggish, S-shaped, no overshoot |
| ζ = 1, critically damped | Two real, equal | Fastest without overshoot |
| 0 < ζ < 1, underdamped | Complex pair | Overshoots and oscillates, decaying |
| ζ = 0 | Imaginary | Sustained oscillation |
| ζ < 0 | Right half plane | Growing (unstable) |
Where second-order systems come from
- Two first-order systems in series: always overdamped or critically damped (e.g. two tanks in series).
- Inherently second-order systems with inertia (a U-tube manometer, a valve with a spring and mass).
- Processes under feedback control: a first-order process with PI control or a second-order process with P control can become underdamped.
Underdamped step response features
For ζ < 1:
- Overshoot OS = exp(−πζ ÷ √(1 − ζ²)).
- Decay ratio = (OS)² = exp(−2πζ ÷ √(1 − ζ²)) (ratio of successive peaks above the final value).
- Period of oscillation T = 2πτ ÷ √(1 − ζ²).
- Rise time: time to first reach the final value; settling time: time to stay within ±5% (or ±2%).
Worked example
A loop behaves as a second-order system with K = 1, τ = 1 min, ζ = 0.5, for a set-point step of 10°C.
- √(1 − 0.25) = 0.866.
- OS = exp(−π × 0.5 ÷ 0.866) = exp(−1.814) = 0.163: the peak is 10 × 1.163 = 11.63°C above the old value.
- Decay ratio = 0.163² = 0.0266 (the second peak overshoots by 0.163 × 0.163 × 10 = 0.27°C).
- Period = 2π × 1 ÷ 0.866 = 7.26 min.
Check: exp(−2π × 0.5 ÷ 0.866) = exp(−3.628) = 0.0266, the same decay ratio by the direct formula. ✓
(A rule often used in tuning is a quarter decay ratio (0.25), which corresponds to ζ ≈ 0.22 and an overshoot of 50%.)
Two non-interacting tanks in series
G = K ÷ [(τ₁s + 1)(τ₂s + 1)] = K ÷ [τ₁τ₂ s² + (τ₁ + τ₂)s + 1], so τ = √(τ₁τ₂) and ζ = (τ₁ + τ₂) ÷ (2√(τ₁τ₂)) ≥ 1. With τ₁ = τ₂ = 4 min: τ = 4 min, ζ = 8 ÷ 8 = 1 (critically damped). With τ₁ = 2, τ₂ = 8: τ = 4, ζ = 10 ÷ 8 = 1.25 (overdamped). ✓
Exams usually ask: derive the second-order transfer function for a given system; classify responses by ζ; calculate overshoot, decay ratio and period; show that tanks in series are overdamped.
Common mistake: claiming that two first-order lags in series can oscillate. Without feedback or inertia, ζ ≥ 1 always; oscillation needs feedback, inertia or an underdamped element.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Best pick Woolf, Chemical Process Dynamics and Controls, 7.3 Second-order differential equations
(opens eng.libretexts.org in a new tab)
LibreTexts, Woolf, Chemical Process Dynamics and Controls, 7.3 Second-order differential equations, CC BY 3.0 · licence
-
Damping
(opens en.wikipedia.org in a new tab)
Wikipedia, Damping, CC BY-SA 4.0 · licence
-
Settling time
(opens en.wikipedia.org in a new tab)
Wikipedia, Settling time, CC BY-SA 4.0 · licence
-
MIT 10.450 Process Dynamics, Operations, and Control (whole course)
MIT's chemical engineering course: lecture notes, problem sets and exams (PDFs, small).