UNIHIVE

Study Hub UNIPORT CHE 513

CHE 513 · Process Dynamics and Control

Frequency response and Bode plots

Response to sinusoidal inputs, amplitude ratio and phase angle from G(jω), first-order, integrator and dead-time elements, Bode plots, and Nyquist diagrams.

Our notes

2 min read

The idea

If a stable linear process is fed a sine wave u = A sin ωt, the output (after transients die away) is a sine wave of the same frequency but a different amplitude and shifted phase:
y = A × AR × sin(ωt + φ).

  • Amplitude ratio AR = |G(jω)|.
  • Phase angle φ = ∠G(jω).

Substitute s = jω in G(s) and find the magnitude and angle.

Basic elements

ElementARPhase
Gain KK0°
First-order lag 1/(τs + 1)1 ÷ √(1 + ω²τ²)−tan⁻¹(ωτ), from 0° to −90°
Integrator 1/s1/ω−90°
Dead time e^(−θs)1−ωθ (radians), without limit
Lead (τs + 1)√(1 + ω²τ²)+tan⁻¹(ωτ)

For elements in series, multiply ARs and add phase angles.

Worked example: a first-order process

K = 2, τ = 5 min, input oscillating at ω = 0.2 rad/min (period 2π ÷ 0.2 = 31.4 min) with amplitude 4 units.

  • ωτ = 1 → AR = 2 ÷ √2 = 1.414; φ = −tan⁻¹(1) = −45°.
  • Output amplitude = 4 × 1.414 = 5.66 units, lagging the input by 45° (31.4 × 45/360 = 3.9 min).

Check: at very low frequency AR → K = 2 (steady state) and φ → 0; at ωτ = 1 the magnitude is K/√2, the "corner". ✓

Bode plots

Two graphs against log ω: log AR (or 20 log AR in decibels) and phase.

  • First-order lag: flat at K below the corner frequency 1/τ, then falling with slope −1 (−20 dB per decade) above it; phase −45° at the corner, tending to −90°.
  • Dead time: AR flat at 1, phase falling ever faster at high frequency.

Asymptotes make Bode plots quick to sketch by hand.

Worked example: the phase crossover of three lags

G = 1 ÷ (s + 1)³: phase = −3 tan⁻¹ω. Phase = −180° when tan⁻¹ω = 60°, so ω = tan 60° = √3 = 1.732 rad/time. There, AR = 1 ÷ (1 + 3)^(3/2) = 1 ÷ 8 = 0.125. (This gives the ultimate gain 8 in the stability topic.) Check: (√(1 + ω²))³ = 2³ = 8. ✓

Nyquist diagram

A polar plot of G(jω) in the complex plane as ω goes from 0 to ∞ (AR as distance from the origin, φ as angle). Used with the Nyquist stability criterion, which works even for dead time and open-loop unstable systems.

Why frequency response matters

It gives stability margins, shows how disturbances of different frequencies are filtered (a tank smooths fast fluctuations), and allows controller design without solving differential equations.

Exams usually ask: derive AR and phase for first-order, second-order and dead-time systems; sketch Bode plots; calculate the output amplitude and lag for a sinusoidal input; find the phase crossover frequency.

Common mistake: adding amplitude ratios of elements in series. Amplitude ratios multiply (or their logarithms add); phase angles add.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.