CHE 513 · Process Dynamics and Control

Feedback controllers and their modes

On-off control, proportional, integral and derivative action, PI, PD and PID controllers, proportional band, offset, reset and derivative times, controller action (direct or reverse), and practical forms.

Our notes

2 min read

On-off control

The output is fully on or fully off as the error changes sign (domestic thermostats, fridges, water tank float switches). A dead band stops rapid switching. Simple and cheap, but the variable cycles around the set point.

Proportional (P) control

p(t) = p̄ + Kc e(t), transfer function Gc = Kc.

  • Proportional band PB (%) = 100 ÷ Kc (for dimensionless gain): the % change in input needed to move the output across its full range. Kc = 2 → PB = 50%.
  • P control leaves an offset (steady-state error) after a load or set-point change, because a non-zero error is needed to hold a new output.

Integral (I) action

p(t) = p̄ + Kc [e + (1/τI) ∫e dt], Gc = Kc [1 + 1/(τI s)].

  • Integral action keeps changing the output while any error remains, so it removes offset.
  • τI = integral (reset) time; some controllers use repeats per minute = 1/τI. Too little τI (too much integral) makes loops oscillate.
  • Reset windup: when the valve is saturated (fully open), the integral keeps growing; anti-windup logic stops this.

Derivative (D) action

Adds Kc τD de/dt: responds to the rate of change of error, anticipating where it is heading; adds damping and allows higher gain. It amplifies noise, so it is filtered and often applied to the measurement rather than the error (no "derivative kick" on set-point steps). Used mainly on slow loops such as temperature; rarely on noisy flow loops.

Summary

ModeRemoves offsetSpeed and dampingTypical use
PNoFast; offsetAveraging level control
PIYesMost commonFlow, pressure, level, many temperatures
PDNoFaster, dampedSome batch and servo systems
PIDYesBest for slow, lag-dominated loopsTemperature, composition

Worked example: offset with P control

A first-order process with gain K = 2 under P control with Kc = 2 (valve and sensor gains 1). For a set-point step of 10 units, the closed-loop gain = KcK ÷ (1 + KcK) = 4 ÷ 5 = 0.8: the output settles at 8, leaving an offset of 2 (20%). Raising Kc to 9 gives KcK = 18, closed-loop gain 18/19 = 0.947, offset 0.53: smaller but not zero, and real loops (with lags and dead time) become oscillatory at high gain. Check: offset ÷ step = 1 ÷ (1 + KcK) = 1/5 = 0.2. ✓

Controller action

  • Reverse acting: output decreases when the measurement increases (heating loop: temperature up → reduce steam).
  • Direct acting: output increases when the measurement increases (cooling loop: temperature up → more cooling water).

Choose with the valve's fail-safe action so the overall loop gives negative feedback.

Exams usually ask: describe on-off, P, PI, PD and PID control; explain offset and how integral action removes it; define proportional band, reset time and derivative time; choose direct or reverse action.

Common mistake: expecting a higher proportional gain to remove offset completely. It only reduces it; integral action is needed for zero offset.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.