The Nyquist criterion and gain and phase margins

The Nyquist stability criterion, reading margins from Bode and Nyquist plots, and what the margins mean for robustness.

Our notes

2 min read

The Nyquist criterion

For the closed loop with open-loop G(s)H(s), plot G(jω)H(jω) for ω from −∞ to +∞ (the Nyquist plot). Then:

Z = N + P

  • P = number of open-loop poles in the right half plane (known from G H).
  • N = number of clockwise encirclements of the point −1 + j0 by the plot.
  • Z = number of closed-loop poles in the right half plane. Stable if Z = 0.

For the common case of a stable open loop (P = 0), the closed loop is stable if the plot does not encircle −1. Open-loop poles on the imaginary axis (integrators) are bypassed by small semicircles.

The criterion works with measured frequency-response data and handles time delays (e^(−sT)), which the Routh test cannot.

Gain margin and phase margin

  • Phase crossover frequency ω_pc: where the phase is −180°.
  • Gain margin GM = 1 ÷ |GH(jω_pc)|, or in dB −20 log|GH(jω_pc)|: how much the gain can rise before instability.
  • Gain crossover frequency ω_gc: where |GH| = 1 (0 dB).
  • Phase margin PM = 180° + ∠GH(jω_gc): how much extra phase lag can be tolerated.

A stable minimum-phase system has positive GM (dB) and PM. Typical design targets: GM ≥ 6 dB, PM 30° to 60°.

Worked example

G(s) = K ÷ (s(s + 2)(s + 4)) with K = 12.

  • Phase −180° when 90° + arctan(ω/2) + arctan(ω/4) = 180°, giving ω² = 8, ω_pc = 2.83 rad/s.
  • |G| there = 12 ÷ (2.83 × √12 × √24) = 12 ÷ 48 = 0.25, so GM = 4 (12.0 dB). The gain can be raised four times (to K = 48, matching the Routh result).
  • Gain crossover: solve ω√(ω² + 4)√(ω² + 16) = 12, giving ω_gc ≈ 1.22 rad/s; phase = −90° − arctan(0.612) − arctan(0.306) = −90° − 31.5° − 17.0° = −138.5°, so PM ≈ 41.5°.

Phase margin and damping

For a second-order loop, PM ≈ 100ζ (degrees) for PM below about 70°. PM ≈ 41.5° suggests ζ ≈ 0.42 and about 23% overshoot.

Time delay

A delay e^(−sT) leaves the magnitude unchanged but adds phase lag ωT radians. With PM = 41.5° (0.725 rad) at ω_gc = 1.22 rad/s, the largest delay the loop tolerates is 0.725 ÷ 1.22 ≈ 0.59 s. Delays are common in process control (transport in pipes, sensors) and in networked control.

Robustness

Margins measure how far the loop is from instability: they cover errors in the model, ageing of components and changes in load. Too large a margin usually means a sluggish system.

Exams usually ask

  • State and apply the Nyquist criterion to simple plots.
  • Calculate gain and phase margins from a transfer function or read them from Bode plots.

Common mistake

Counting encirclements of the origin instead of the critical point −1 + j0.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.