MEG 502 · Control Engineering

Controller design: PID, lead and lag compensation

P, I and D actions, PID tuning by Ziegler-Nichols, and lead, lag and lead-lag compensators.

Our notes

2 min read

The PID controller

u(t) = K_p e + K_i ∫e dt + K_d de/dt, or C(s) = K_p + K_i/s + K_d s = K_p(1 + 1/(T_i s) + T_d s).

ActionEffect
Proportionalfaster response, smaller (but not zero) steady error; too much → oscillation
Integralremoves steady-state error for steps; adds lag, can cause overshoot and integrator windup
Derivativeadds damping and anticipation; amplifies noise (filtered in practice)

PID controllers run most industrial loops (temperature, pressure, flow, level, motor speed).

Ziegler-Nichols tuning (ultimate gain method)

With I and D off, raise K_p until the loop just oscillates steadily: the ultimate gain K_u and ultimate period P_u. Then:

ControllerK_pT_iT_d
P0.5K_u
PI0.45K_uP_u/1.2
PID0.6K_uP_u/2P_u/8

These give quick but oscillatory responses (about 25% decay ratio); fine-tune afterwards. The step-response (reaction curve) method uses the process's delay and time constant instead.

Worked example

For G(s) = 1 ÷ (s(s + 2)(s + 4)) with a proportional controller, the Routh array gave K_u = 48 and oscillation at 2.83 rad/s, so P_u = 2π ÷ 2.83 = 2.22 s.

  • PID: K_p = 0.6 × 48 = 28.8; T_i = 2.22 ÷ 2 = 1.11 s; T_d = 2.22 ÷ 8 = 0.278 s.
  • So K_i = K_p/T_i = 25.9 and K_d = K_p T_d = 8.0.

Lead compensator

C(s) = K(s + z) ÷ (s + p) with z < p (the zero nearer the origin). It adds phase lead near the crossover, increasing phase margin and speed (like a filtered PD). Maximum phase lead φ_m occurs at ω_m = √(zp), with sin φ_m = (p − z) ÷ (p + z).

Worked example: lead design check

Choose z = 2, p = 8: sin φ_m = 6/10 = 0.6, φ_m = 36.9° at ω_m = √16 = 4 rad/s. The compensator's gain rises by p/z = 4 (12 dB) from low to high frequency, so the gain crossover moves to a higher frequency; place ω_m at the new crossover.

Lag compensator

C(s) = K(s + z) ÷ (s + p) with p < z, both close to the origin (for example z = 0.1, p = 0.01). It raises low-frequency gain (here by 10 times), reducing steady-state error, with little effect on the transient response (like a filtered PI).

Lead-lag

Combines both: lead for transient response and margins, lag for steady-state accuracy.

Practical issues

Actuator saturation and integrator windup (use anti-windup: stop integrating when the actuator saturates), derivative kick on set-point changes (take the derivative of the measurement only), noise filtering, and sampling in digital controllers.

Exams usually ask

  • Explain the effects of P, I and D actions; tune a PID controller by Ziegler-Nichols.
  • Design or analyse lead and lag compensators.

Common mistake

Expecting proportional control alone to remove steady-state error in a type 0 system. Integral action is needed.