Three-phase circuits

Why three phases, star and delta connections, line and phase values, and three-phase power.

Our notes

2 min read

Why three-phase

A three-phase supply has three voltages of equal size, 120° apart. Compared with single-phase it:

  • Transmits more power per kg of conductor.
  • Gives a constant total power (smooth running of motors).
  • Produces a rotating magnetic field, so three-phase induction motors start themselves.

Nigeria's low-voltage supply is 415 V between lines and about 240 V (nominally 230 V) between line and neutral, 50 Hz. Phases are often coloured red, yellow and blue (R, Y, B).

Phase sequence

v_R = V_m sin ωt, v_Y = V_m sin(ωt − 120°), v_B = V_m sin(ωt − 240°). The order matters: swapping two lines reverses a motor.

Star (Y) connection

One end of each phase joins at the neutral point.

  • V_L = √3 V_ph (line voltage between two lines).
  • I_L = I_ph.
  • Gives two voltages (415 V and 240 V) with a 4-wire system: used for distribution to homes.
  • In a balanced load the neutral current is zero.

Delta (Δ) connection

The three phases form a closed triangle; no neutral.

  • V_L = V_ph.
  • I_L = √3 I_ph.

Used for motor windings and transmission.

Three-phase power

For a balanced load (either connection):

P = √3 V_L I_L cos φ = 3 V_ph I_ph cos φ,
Q = √3 V_L I_L sin φ, S = √3 V_L I_L.

Example

A balanced load of Z = 8 + j6 Ω per phase (|Z| = 10 Ω, pf 0.8 lagging) on a 415 V supply.
Star:

  • V_ph = 415/√3 ≈ 239.6 V, I_ph = I_L = 239.6/10 ≈ 23.96 A.
  • P = √3 × 415 × 23.96 × 0.8 ≈ 13.78 kW. Check: 3I²R = 3 × 23.96² × 8 ≈ 13.78 kW ✓.

Delta:

  • V_ph = 415 V, I_ph = 41.5 A, I_L = √3 × 41.5 ≈ 71.9 A.
  • P = 3 × 41.5² × 8 ≈ 41.3 kW: three times the star value.

That is why large motors use star-delta starters: start in star (one-third of the starting current and torque), then switch to delta to run.

Unbalanced loads

Homes on different phases draw different currents, so the neutral carries the difference. A broken neutral on an unbalanced system can give some sockets far more than 240 V and damage appliances: a common cause of burnt equipment.

Measuring three-phase power

The two-wattmeter method (on a 3-wire system): P = W₁ + W₂, and for a balanced load tan φ = √3(W₁ − W₂)/(W₁ + W₂).

Exams usually ask

  • State the line and phase relations for star and delta and prove V_L = √3 V_ph.
  • Compute currents and power for balanced star and delta loads.
  • Explain the two-wattmeter method.

Common mistake

Using P = 3 V_L I_L cos φ. Use √3 with line values, or 3 with phase values, never 3 with line values.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.