Power in AC circuits and power factor

Real, reactive and apparent power, the power triangle, why power factor matters and how to correct it.

Our notes

2 min read

Three kinds of power

For a load with RMS voltage V, current I and phase angle φ between them:

  • Real (active) power P = VI cos φ, in watts (W): does useful work, becomes heat or motion. Only resistance consumes it: P = I²R.
  • Reactive power Q = VI sin φ, in volt-amperes reactive (var): energy that surges back and forth into the magnetic fields of inductors and the electric fields of capacitors each cycle. Q = I²X.
  • Apparent power S = VI, in volt-amperes (VA): what the supply must deliver in current. S² = P² + Q² (the power triangle).
  • Power factor pf = P/S = cos φ: lagging for inductive loads (motors, fluorescent ballasts), leading for capacitive loads.

Example (the RLC circuit of the last topic)

V = 230 V, I = 5.33 A, φ = 45.9° lagging.

  • S = 230 × 5.33 ≈ 1,226 VA.
  • P = 1,226 × cos 45.9° ≈ 853 W. Check: I²R = 5.33² × 30 ≈ 853 W ✓.
  • Q = I²X ≈ 5.33² × 31.0 ≈ 881 var. Check: √(853² + 881²) ≈ 1,226 ✓.
  • pf ≈ 0.70 lagging.

Why a low power factor is bad

For the same real power, a low pf needs more current: I = P/(V cos φ).

  • Bigger cables, transformers and switchgear (rated in kVA, not kW).
  • More I²R loss and voltage drop in lines.
  • Utilities charge large industrial users for poor power factor or kVA demand.

Power factor correction

Add capacitors in parallel with an inductive load: they supply the reactive power locally, so the supply carries less.
Method: Q_C = P(tan φ₁ − tan φ₂), then C = Q_C/(V²ω).

Example

A 10 kW motor load at 0.7 pf lagging on 230 V, 50 Hz; correct to 0.95 lagging.

  • tan φ₁ = tan(cos⁻¹ 0.7) ≈ 1.020, so Q₁ ≈ 10.2 kvar.
  • tan φ₂ = tan(cos⁻¹ 0.95) ≈ 0.329, so Q₂ ≈ 3.29 kvar.
  • Q_C ≈ 6.92 kvar.
  • C = 6,915/(230² × 314.2) ≈ 4.16 × 10⁻⁴ F ≈ 416 μF.
  • Supply current falls from 10,000/(230 × 0.7) ≈ 62.1 A to 10,000/(230 × 0.95) ≈ 45.8 A, with the same 10 kW of real power.

Correcting to exactly 1.0 costs much more capacitance for little gain, and over-correction makes the pf leading.

Other methods

Synchronous motors run over-excited (synchronous condensers), and automatic capacitor banks switched in steps in factories. Power electronics (active filters) also correct pf and harmonics.

Measuring power

A wattmeter measures P directly (it has a current coil and a voltage coil). Energy meters record kWh; many industrial meters also record kvarh or kVA demand.

Exams usually ask

  • Compute P, Q, S and pf, and draw the power triangle.
  • Explain the disadvantages of low power factor.
  • Find the capacitance needed to raise the power factor, and the current saved.

Common mistake

Saying capacitors reduce the real power used. They reduce the current and reactive power from the supply; the load's real power stays the same.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.

Read

Watch

We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.

All ENG 210.1 topics

Report

Sign in to report this. It is free.

Is this your work (a lecturer, author or publisher)? Ask us to take it down.