CHE 513 · Process Dynamics and Control
Our notes
2 min readWhy dynamic models
Control is about how a process moves from one state to another in time. Models come from conservation laws written for an unsteady state:
Rate of accumulation = rate in − rate out + rate of generation
A liquid tank
Tank of cross-section A, inflow qᵢ, outflow q, level h: A dh/dt = qᵢ − q.
- If outflow is pumped at a fixed rate, the tank is an integrator: a step in qᵢ makes h rise as a ramp with no new steady state.
- If outflow is through a valve, q depends on h (q = C√h for turbulent flow), and the level settles.
The stirred-tank heater
For a well-mixed tank of volume V with feed w (kg/s) at Tᵢ and heat input Q: ρ V c dT/dt = w c (Tᵢ − T) + Q.
Dividing by w c gives τ dT/dt + T = Tᵢ + Q ÷ (w c), with time constant τ = ρV ÷ w (the residence time).
Deviation variables
Define each variable as its departure from the initial steady state (T′ = T − T_s). The steady-state terms cancel, initial conditions become zero, and Laplace transforms become simple.
Linearisation
Nonlinear terms (√h, Arrhenius rates, radiation) are replaced near the steady state by the first terms of a Taylor series: f(x) ≈ f(x_s) + (df/dx)_s (x − x_s).
Worked example: a tank with square-root outflow. A = 2 m², q = C√h with C = 0.5 m^2.5/min, steady inflow 1.0 m³/min.
- Steady level: h_s = (q_s ÷ C)² = (1.0 ÷ 0.5)² = 4 m.
- Linearised: q ≈ q_s + (C ÷ (2√h_s)) h′ = q_s + (0.5 ÷ 4) h′, so the resistance R = dh/dq = 2√h_s ÷ C = 8 min/m².
- Linear model: A dh′/dt = qᵢ′ − h′/R → τ dh′/dt + h′ = R qᵢ′ with τ = AR = 2 × 8 = 16 min and gain K = R = 8 m per (m³/min).
Check: R = 2h_s ÷ q_s = 2 × 4 ÷ 1.0 = 8. ✓ A 0.1 m³/min rise in inflow eventually raises the level by about 0.8 m (exact nonlinear answer: (1.1 ÷ 0.5)² − 4 = 4.84 − 4 = 0.84 m; the linear model is close for small changes).
Degrees of freedom
Number of variables − number of independent equations = variables that must be specified (by inputs or controllers). Each controller uses up one degree of freedom.
Exams usually ask: write dynamic mass and energy balances for tanks and heaters; introduce deviation variables; linearise a nonlinear model; identify time constants and gains.
Common mistake: forgetting to linearise about the actual steady state. The resistance and time constant change with operating level; a model fitted at 4 m is wrong at 1 m.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Best pick Woolf, Chemical Process Dynamics and Controls, 2.1 Verbal modelling
(opens eng.libretexts.org in a new tab)
LibreTexts, Woolf, Chemical Process Dynamics and Controls, 2.1 Verbal modelling, CC BY 3.0 · licence
-
Woolf, Chemical Process Dynamics and Controls, 2.2 Degrees of freedom
(opens eng.libretexts.org in a new tab)
LibreTexts, Woolf, Chemical Process Dynamics and Controls, 2.2 Degrees of freedom, CC BY 3.0 · licence
-
Mathematical model
(opens en.wikipedia.org in a new tab)
Wikipedia, Mathematical model, CC BY-SA 4.0 · licence
-
Continuous stirred-tank reactor
(opens en.wikipedia.org in a new tab)
Wikipedia, Continuous stirred-tank reactor, CC BY-SA 4.0 · licence
-
Woolf et al., Chemical Process Dynamics and Controls (whole free textbook)
University of Michigan's open process-control textbook on LibreTexts (CC BY 3.0): sensors and valves, modelling, Laplace transforms, PID, stability, control architectures. A full PDF is offered on the page.
(opens eng.libretexts.org in a new tab)
LibreTexts, Woolf et al., Chemical Process Dynamics and Controls (whole free textbook), CC BY 3.0 · licence
-
MIT 10.450 Process Dynamics, Operations, and Control (whole course)
MIT's chemical engineering course: lecture notes, problem sets and exams (PDFs, small).
(opens ocw.mit.edu in a new tab)
MIT OpenCourseWare, MIT 10.450 Process Dynamics, Operations, and Control (whole course), CC BY-NC-SA 4.0 · licence
We link to free material and never copy it. Every link was opened by our team before it went up.