PHY 315 · Electronic Instrumentation I
Our notes
3 min readOpen-loop control
The control action does not depend on the output: input → controller → process → output.
- Advantages: simple, cheap, no stability problems, good when the process is well known and disturbances are small.
- Disadvantages: cannot correct for disturbances or changes in the process; accuracy depends on calibration.
- Examples: a traffic light on a fixed timer, a microwave oven timer, a fan regulator, a stepper-motor positioner without feedback.
Closed-loop control
The output is measured and compared with the set point; the error drives the controller.
- Advantages: corrects disturbances, less sensitive to changes in the process, more accurate, faster (with good design).
- Disadvantages: needs sensors, more complex and costly, can become unstable, sensor noise enters the loop.
- Examples: an electric iron with a thermostat, an automatic voltage regulator (AVR) on a generator, a car's cruise control, level control in a water tank, the temperature control of an incubator.
Comparison
| Open loop | Closed loop | |
|---|---|---|
| Uses output measurement | no | yes |
| Disturbance rejection | none | good |
| Accuracy | depends on calibration | depends on the sensor |
| Stability | no problem | must be designed |
| Cost | low | higher |
Steady-state error
For a unity-feedback loop with open-loop transfer function G(s), the error E(s) = R(s)/(1 + G(s)). By the final value theorem e_ss = lim (s→0) sR(s)/(1 + G(s)).
System type = number of integrators (poles at s = 0) in G(s).
| Input | Type 0 | Type 1 | Type 2 |
|---|---|---|---|
| Step | 1/(1 + K_p) | 0 | 0 |
| Ramp | ∞ | 1/K_v | 0 |
K_p = lim G(s) as s → 0 (position constant); K_v = lim sG(s) (velocity constant).
Example
G(s) = 9/(2s + 1) (type 0), unit step set-point change: K_p = 9, e_ss = 1/(1 + 9) = 0.1 (10% offset).
Check: the closed loop is 9/(2s + 10), whose steady value is 9/10 = 0.9, so the error is 0.1 ✓.
Raising the gain to 99 cuts the error to 1%, but very high gain may cause instability with more lags; adding an integrator removes the error.
Controller actions
- On-off (two-position): fully on or off (a thermostat in an iron or fridge). Simple; the variable cycles around the set point within a differential (hysteresis band) that stops rapid switching.
- Proportional (P): output ∝ error (gain K_p). Smooth, but leaves an offset (steady-state error) for type 0 processes.
- Integral (I): output ∝ integral of error: removes offset, but slows the response and can cause overshoot and "windup".
- Derivative (D): output ∝ rate of change of error: anticipates, adds damping, but amplifies noise.
- PID: u = K_p[e + (1/T_i)∫e dt + T_d de/dt], the most common industrial controller; tuned by methods such as Ziegler-Nichols (starting from the gain at which the loop just oscillates: the K found by Routh or Nyquist).
Disturbance rejection
A disturbance D entering at the process output is reduced in the closed loop by the factor 1/(1 + GH): with a loop gain of 99, a disturbance is cut to 1% of its open-loop effect.
Exams usually ask
- Compare open- and closed-loop control with examples and block diagrams.
- Find the steady-state error for step and ramp inputs and relate it to system type.
- Describe on-off, P, PI and PID control actions.
Common mistake
Saying proportional control alone gives zero steady-state error. For a type 0 process it always leaves an offset; integral action is needed to remove it.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Open-loop controller
(opens en.wikipedia.org in a new tab)
Wikipedia, Open-loop controller, CC BY-SA 4.0 · licence
-
Closed-loop controller
(opens en.wikipedia.org in a new tab)
Wikipedia, Closed-loop controller, CC BY-SA 4.0 · licence
-
Control system
(opens en.wikipedia.org in a new tab)
Wikipedia, Control system, CC BY-SA 4.0 · licence
Watch
-
Best pick Open Loop Systems
4 min · ≈ 18 MB · about ₦10
(opens youtube.com in a new tab)
-
Control Systems Lectures - Closed Loop Control
9 min · ≈ 41 MB · about ₦23
(opens youtube.com in a new tab)
-
Open and Closed Loop Control Systems - Introduction of Control Systems - Control System
20 min · ≈ 90 MB · about ₦51
(opens youtube.com in a new tab)
-
Open vs Closed Loop Systems in Control Systems: A Detailed Comparison
8 min · ≈ 36 MB · about ₦20
(opens youtube.com in a new tab)
-
Mod-01 Lec-02 Lecture-02-Introduction to Process Control (Contd.)
57 min · ≈ 257 MB · about ₦144
(opens youtube.com in a new tab)
We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.