Characteristics of open- and closed-loop control systems

Comparing open and closed loops, steady-state error and system type, disturbance rejection, and on-off, P, PI and PID control.

Our notes

3 min read

Open-loop control

The control action does not depend on the output: input → controller → process → output.

  • Advantages: simple, cheap, no stability problems, good when the process is well known and disturbances are small.
  • Disadvantages: cannot correct for disturbances or changes in the process; accuracy depends on calibration.
  • Examples: a traffic light on a fixed timer, a microwave oven timer, a fan regulator, a stepper-motor positioner without feedback.

Closed-loop control

The output is measured and compared with the set point; the error drives the controller.

  • Advantages: corrects disturbances, less sensitive to changes in the process, more accurate, faster (with good design).
  • Disadvantages: needs sensors, more complex and costly, can become unstable, sensor noise enters the loop.
  • Examples: an electric iron with a thermostat, an automatic voltage regulator (AVR) on a generator, a car's cruise control, level control in a water tank, the temperature control of an incubator.

Comparison

Open loopClosed loop
Uses output measurementnoyes
Disturbance rejectionnonegood
Accuracydepends on calibrationdepends on the sensor
Stabilityno problemmust be designed
Costlowhigher

Steady-state error

For a unity-feedback loop with open-loop transfer function G(s), the error E(s) = R(s)/(1 + G(s)). By the final value theorem e_ss = lim (s→0) sR(s)/(1 + G(s)).
System type = number of integrators (poles at s = 0) in G(s).

InputType 0Type 1Type 2
Step1/(1 + K_p)00
Ramp∞1/K_v0

K_p = lim G(s) as s → 0 (position constant); K_v = lim sG(s) (velocity constant).

Example

G(s) = 9/(2s + 1) (type 0), unit step set-point change: K_p = 9, e_ss = 1/(1 + 9) = 0.1 (10% offset).
Check: the closed loop is 9/(2s + 10), whose steady value is 9/10 = 0.9, so the error is 0.1 ✓.
Raising the gain to 99 cuts the error to 1%, but very high gain may cause instability with more lags; adding an integrator removes the error.

Controller actions

  • On-off (two-position): fully on or off (a thermostat in an iron or fridge). Simple; the variable cycles around the set point within a differential (hysteresis band) that stops rapid switching.
  • Proportional (P): output ∝ error (gain K_p). Smooth, but leaves an offset (steady-state error) for type 0 processes.
  • Integral (I): output ∝ integral of error: removes offset, but slows the response and can cause overshoot and "windup".
  • Derivative (D): output ∝ rate of change of error: anticipates, adds damping, but amplifies noise.
  • PID: u = K_p[e + (1/T_i)∫e dt + T_d de/dt], the most common industrial controller; tuned by methods such as Ziegler-Nichols (starting from the gain at which the loop just oscillates: the K found by Routh or Nyquist).

Disturbance rejection

A disturbance D entering at the process output is reduced in the closed loop by the factor 1/(1 + GH): with a loop gain of 99, a disturbance is cut to 1% of its open-loop effect.

Exams usually ask

  • Compare open- and closed-loop control with examples and block diagrams.
  • Find the steady-state error for step and ramp inputs and relate it to system type.
  • Describe on-off, P, PI and PID control actions.

Common mistake

Saying proportional control alone gives zero steady-state error. For a type 0 process it always leaves an offset; integral action is needed to remove it.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.