UNIHIVE

Study Hub UNIPORT PHY 200

PHY 200 · Energy & Environment

The grid, transmission and storage

Why power is sent at high voltage, line losses, capacity factor, and ways of storing electrical energy.

Our notes

2 min read

The grid

Power stations feed a national grid of transmission lines, substations and transformers. In Nigeria the Transmission Company of Nigeria (TCN) runs the 330 kV and 132 kV lines; distribution companies (DisCos) bring power at 33 kV, 11 kV and finally 415/230 V to users.

Why high voltage?

For a given power P = VI, a higher voltage means a smaller current. Heat lost in the wires is P_loss = I²R, so a smaller current gives much smaller losses.

Worked example: line losses

A line with total resistance 10 Ω must carry 100 MW (treat it as a simple single circuit).

  • At 132 kV: I = 100 × 10⁶ / 132 × 10³ = 757.6 A; loss = 757.6² × 10 = 5.74 MW (5.7%).
  • At 330 kV: I = 303.0 A; loss = 303.0² × 10 = 0.92 MW (0.9%).

Raising the voltage 2.5 times cuts the loss 2.5² = 6.25 times.

Capacity factor

Capacity factor = energy actually produced / (rated power × hours in the period).

Worked example: a solar farm

A 10 MW solar farm produces 15,000 MWh in a year.

  • Maximum possible = 10 × 8,760 = 87,600 MWh.
  • Capacity factor = 15,000 / 87,600 = 0.17 (17%).

Typical values: nuclear 85-90%, gas 40-80%, hydro 30-60%, wind 25-45%, solar 15-25%.

Why storage matters

Demand changes through the day, and solar and wind change with the weather. Storage moves energy from times of plenty to times of need.

StorageHow it worksNotes
Pumped hydropump water uphill, release laterlarge, cheap per kWh, needs hills
Batteries (lithium-ion, lead-acid)chemical energyfast, falling in price; used in homes and solar systems
Flywheelsspinning massvery fast, short duration
Compressed airair stored in cavernsfew sites
Hydrogenelectricity splits water; hydrogen burned or used in fuel cellslow round-trip efficiency
Thermalhot water, molten saltused with solar thermal plants

Worked example: a home battery

An inverter battery bank of 4 × 200 Ah at 12 V stores 4 × 200 × 12 = 9,600 Wh = 9.6 kWh. If only 50% may be used (to protect lead-acid batteries), it can run a 400 W load for 4.8 / 0.4 = 12 hours.

Grid stability

Supply must match demand every second; if not, the frequency (50 Hz in Nigeria) drifts and protective systems trip, which can cause a grid collapse (Nigeria has had many, including several in 2024).

Exams usually ask

  • Explain why electricity is transmitted at high voltage, with I²R.
  • Define capacity factor; compare energy storage methods.

Common mistake

Using V²/R with the line voltage to find the loss. The voltage that drives the loss is the voltage drop along the line, not the line voltage; use I²R.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.