MEG 508 · Power Plant Engineering

Feedwater heaters, pumps and auxiliaries

Regenerative feed heating with open and closed heaters, deaerators, feed pumps, and the other auxiliary systems of a steam plant.

Our notes

2 min read

Regenerative feed heating

Steam bled from the turbine heats the feedwater before the boiler. Benefits: higher average temperature of heat addition (higher efficiency), smaller condenser, less thermal stress in the boiler. Cost: less steam passes through later turbine stages (less work per kg of boiler steam).

Open (direct-contact) feedwater heater

Bled steam and feedwater mix; the outlet is saturated liquid at the heater pressure. Simple and good at removing gases (a deaerator is an open heater), but each open heater needs its own pump after it.
Mass balance for the fraction y of steam bled (per kg entering the turbine):
y h_bleed + (1 − y) h_in = h_out, so y = (h_out − h_in)/(h_bleed − h_in).

Worked example

Open heater at 0.5 MPa: outlet saturated liquid h = 640.2 kJ/kg; feedwater enters at h = 200 kJ/kg; bled steam h = 2,800 kJ/kg.
y = (640.2 − 200)/(2,800 − 200) = 440.2/2,600 = 0.169: about 17% of the steam is bled.

Closed feedwater heater

A shell-and-tube heat exchanger: feedwater in tubes, bled steam condenses outside without mixing. The drained condensate is either pumped forward into the feed line or cascaded backward to a lower-pressure heater (through a trap). No pump is needed for each heater, so several closed heaters at different pressures are combined with one open deaerator in big plants.

Deaerator

An open heater (often about 0.3-1 MPa) that removes dissolved oxygen and CO₂ by heating water to saturation, preventing corrosion in the boiler.

Pumps

  • Condensate extraction pump: from condenser hotwell through low-pressure heaters (must avoid cavitation: low NPSH available).
  • Boiler feed pump: raises water to above boiler pressure (multistage centrifugal, often driven by a small steam turbine in large plants).
  • Circulating water pumps: cooling water through the condenser.

Pump power = ρgQH/η.

Worked example

A feed pump delivers 100 kg/s of water (ρ ≈ 900 kg/m³ when hot) against a pressure rise of 18 MPa with 80% efficiency: power = (100/900) × 18 × 10⁶/0.8 = 2.5 MW.

Other auxiliaries

  • Fuel handling: gas reception and pressure reduction stations; coal yards, crushers, mills.
  • Ash and dust handling: electrostatic precipitators, bag filters, flue gas desulphurisation (coal plants).
  • Water treatment plant.
  • Fans (forced and induced draught), soot blowers.
  • Lubrication and seal oil systems; turning gear.
  • Generator cooling (air, hydrogen or water) and the excitation system.
  • Electrical auxiliaries: transformers, switchgear, station supply, black-start diesel generators.
  • Instrumentation and control (distributed control systems), fire protection.

Auxiliaries use a share of gross output (auxiliary consumption, often 5-10% in steam plants), so net output < gross output.

Exams usually ask

  • Compare open and closed feedwater heaters; calculate bled steam fractions.
  • Explain the purpose of a deaerator.
  • List and describe the auxiliaries of a steam power station.

Common mistake

Forgetting that bled steam does less turbine work. The turbine work per kg of boiler steam falls; efficiency rises because heat added falls more.