2 min readOverall heat transfer coefficient (tube)
Based on the outer area: 1/(U_oA_o) = 1/(h_iA_i) + R″_f,i/A_i + ln(r_o/r_i)/(2πkL) + R″_f,o/A_o + 1/(h_oA_o).
Fouling factors R″_f (scale, rust, biological growth) are added for long-term design: typical 0.0001-0.0009 m²·K/W for water services.
LMTD method
q = UA F ΔT_lm,cf, with ΔT_lm,cf the log mean temperature difference for counterflow and F a correction factor (≤ 1) for shell-and-tube and cross-flow arrangements (from charts using P and R).
Best when all four terminal temperatures are known (sizing a new exchanger).
Effectiveness-NTU method
Best when only the inlet temperatures are known (rating an existing exchanger).
- Heat capacity rates: C_h = ṁ_hc_p,h, C_c = ṁ_cc_p,c; C_min, C_max; C_r = C_min/C_max.
- q_max = C_min(T_h,in − T_c,in).
- Effectiveness ε = q/q_max.
- NTU = UA/C_min.
- ε = f(NTU, C_r, arrangement). Counterflow: ε = [1 − exp(−NTU(1 − C_r))]/[1 − C_r exp(−NTU(1 − C_r))].
- For C_r = 0 (one fluid boiling or condensing): ε = 1 − exp(−NTU) for any arrangement.
Worked example (counterflow)
Hot oil: C_h = 2000 W/K, inlet 150 °C. Water: C_c = 4000 W/K, inlet 30 °C. UA = 3000 W/K.
- C_min = 2000, C_r = 0.5, NTU = 3000/2000 = 1.5
- exp(−1.5 × 0.5) = e^(−0.75) = 0.4724
- ε = (1 − 0.4724)/(1 − 0.5 × 0.4724) = 0.5276/0.7638 = 0.691
- q_max = 2000 × 120 = 240 kW → q = 165.8 kW
- T_h,out = 150 − 165 800/2000 = 67.1 °C; T_c,out = 30 + 165 800/4000 = 71.4 °C
Check with LMTD: ΔT₁ = 150 − 71.4 = 78.6 K, ΔT₂ = 67.1 − 30 = 37.1 K; ΔT_lm = 41.5/ln(2.119) = 55.3 K; q = 3000 × 55.3 = 165.9 kW ✓.
Design and selection
- Define duty (q), temperatures and flow rates; choose the type (double-pipe, shell-and-tube, plate, compact).
- Estimate U (from tables or correlations), find area by LMTD or ε-NTU.
- Choose tube size, number, length, passes, baffles.
- Check pressure drop (pumping cost) and velocities (fouling, erosion).
- Iterate; cost the design.
Standards: TEMA for shell-and-tube exchangers.
Heat and mass exchangers
Cooling towers and evaporative condensers transfer heat and water vapour together; their design uses enthalpy-based driving forces (Merkel's method).
Exams usually ask: when to use LMTD versus ε-NTU; outlet temperatures by ε-NTU; overall U with fouling; correction factor F.
Common mistake: using C_max in q_max. The maximum possible heat transfer is limited by the fluid with the smaller heat capacity rate.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Heat exchanger
(opens en.wikipedia.org in a new tab)
Wikipedia, Heat exchanger, CC BY-SA 4.0 · licence
-
Logarithmic mean temperature difference
(opens en.wikipedia.org in a new tab)
Wikipedia, Logarithmic mean temperature difference, CC BY-SA 4.0 · licence
-
NTU method
(opens en.wikipedia.org in a new tab)
Wikipedia, NTU method, CC BY-SA 4.0 · licence
-
A Heat Transfer Textbook, 6th edition (Lienhard and Lienhard)
The whole book, free from the authors as a PDF (large: Wi-Fi). Fuller than our notes.
(opens ahtt.mit.edu in a new tab)
Watch
-
Best pick Heat Transfer L33 p1 - Effectiveness-NTU Method
9 min · ≈ 41 MB · about ₦23
(opens youtube.com in a new tab)
-
Heat Transfer Chapter 11.4 Heat Exchangers: Effectiveness NTU method
2 min · ≈ 9 MB · about ₦5
(opens youtube.com in a new tab)
-
LMTD Correction Factor F - Shell and Tube Heat Exchanger
12 min · ≈ 54 MB · about ₦30
(opens youtube.com in a new tab)
-
Heat Exchanger 2 ME4313
41 min · ≈ 185 MB · about ₦104
(opens youtube.com in a new tab)
We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.