Heat exchanger design: LMTD and effectiveness-NTU

Overall U with fouling, the LMTD method with correction factors, the effectiveness-NTU method, and design and rating steps.

Our notes

2 min read

Overall heat transfer coefficient (tube)

Based on the outer area: 1/(U_oA_o) = 1/(h_iA_i) + R″_f,i/A_i + ln(r_o/r_i)/(2πkL) + R″_f,o/A_o + 1/(h_oA_o).
Fouling factors R″_f (scale, rust, biological growth) are added for long-term design: typical 0.0001-0.0009 m²·K/W for water services.

LMTD method

q = UA F ΔT_lm,cf, with ΔT_lm,cf the log mean temperature difference for counterflow and F a correction factor (≤ 1) for shell-and-tube and cross-flow arrangements (from charts using P and R).
Best when all four terminal temperatures are known (sizing a new exchanger).

Effectiveness-NTU method

Best when only the inlet temperatures are known (rating an existing exchanger).

  • Heat capacity rates: C_h = ṁ_hc_p,h, C_c = ṁ_cc_p,c; C_min, C_max; C_r = C_min/C_max.
  • q_max = C_min(T_h,in − T_c,in).
  • Effectiveness ε = q/q_max.
  • NTU = UA/C_min.
  • ε = f(NTU, C_r, arrangement). Counterflow: ε = [1 − exp(−NTU(1 − C_r))]/[1 − C_r exp(−NTU(1 − C_r))].
  • For C_r = 0 (one fluid boiling or condensing): ε = 1 − exp(−NTU) for any arrangement.

Worked example (counterflow)

Hot oil: C_h = 2000 W/K, inlet 150 °C. Water: C_c = 4000 W/K, inlet 30 °C. UA = 3000 W/K.

  • C_min = 2000, C_r = 0.5, NTU = 3000/2000 = 1.5
  • exp(−1.5 × 0.5) = e^(−0.75) = 0.4724
  • ε = (1 − 0.4724)/(1 − 0.5 × 0.4724) = 0.5276/0.7638 = 0.691
  • q_max = 2000 × 120 = 240 kW → q = 165.8 kW
  • T_h,out = 150 − 165 800/2000 = 67.1 °C; T_c,out = 30 + 165 800/4000 = 71.4 °C

Check with LMTD: ΔT₁ = 150 − 71.4 = 78.6 K, ΔT₂ = 67.1 − 30 = 37.1 K; ΔT_lm = 41.5/ln(2.119) = 55.3 K; q = 3000 × 55.3 = 165.9 kW ✓.

Design and selection

  1. Define duty (q), temperatures and flow rates; choose the type (double-pipe, shell-and-tube, plate, compact).
  2. Estimate U (from tables or correlations), find area by LMTD or ε-NTU.
  3. Choose tube size, number, length, passes, baffles.
  4. Check pressure drop (pumping cost) and velocities (fouling, erosion).
  5. Iterate; cost the design.

Standards: TEMA for shell-and-tube exchangers.

Heat and mass exchangers

Cooling towers and evaporative condensers transfer heat and water vapour together; their design uses enthalpy-based driving forces (Merkel's method).

Exams usually ask: when to use LMTD versus ε-NTU; outlet temperatures by ε-NTU; overall U with fouling; correction factor F.

Common mistake: using C_max in q_max. The maximum possible heat transfer is limited by the fluid with the smaller heat capacity rate.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.