MEG 310 · Heat and Transfer

Boiling and condensation

The boiling curve, nucleate and film boiling, critical heat flux, film and dropwise condensation and Nusselt's analysis, evaporation.

Our notes

2 min read

Boiling

Heat transfer to a liquid at a surface hotter than the saturation temperature; excess temperature ΔT_e = T_s − T_sat.

The pool boiling curve (water at 1 atm)

  1. Natural convection (ΔT_e below about 5 K): no bubbles.
  2. Nucleate boiling (about 5-30 K): bubbles form at surface cavities and stir the liquid; very high h. Rohsenow's correlation predicts the heat flux.
  3. Critical heat flux (CHF), about 1 MW/m² for water at 1 atm: the peak.
  4. Transition boiling: unstable vapour patches; the flux falls as ΔT rises.
  5. Film boiling (Leidenfrost point onwards): a vapour blanket insulates the surface (water droplets dancing on a very hot pan).

Danger: if a heat-flux-controlled surface (electric element, nuclear fuel, boiler tube) passes the CHF, it jumps to film boiling at a much higher temperature and can burn out. Boilers are designed with a margin below CHF.

Flow boiling

Boiling in tubes (boilers, evaporators): flow regimes change from bubbly to slug to annular to mist as the vapour fraction rises.

Condensation

Vapour touching a surface below T_sat condenses.

  • Film condensation: a continuous liquid film; the film is the main resistance. Nusselt's analysis (1916) for a vertical plate gives h̄ ∝ [g ρ_l(ρ_l − ρ_v) k_l³ h′_fg/(μ_l (T_sat − T_s) L)]^(1/4), with constant 0.943. Thicker film lower down → lower local h.
  • Dropwise condensation: droplets roll off and expose bare surface: h can be 10 times higher, but is hard to keep (needs special coatings).
  • Non-condensable gases (air leaking into a condenser) collect at the surface and sharply reduce condensation: why power-plant condensers have air ejectors.
  • Horizontal tubes condense better than vertical ones of the same area (thinner films): condensers use horizontal tube banks.

Evaporation

Liquid becoming vapour at a free surface below boiling point, controlled by mass transfer of vapour into the air (later topics): cooling towers, evaporative coolers ("desert coolers"), drying crops, sweating.

Latent heat

Phase change moves large amounts of energy at nearly constant temperature (h_fg of water about 2257 kJ/kg at 100 °C), which is why boiling and condensation give such high heat transfer rates.

Exams usually ask: sketch and explain the boiling curve; the significance of critical heat flux; film versus dropwise condensation; effect of non-condensable gases.

Common mistake: assuming more superheat always means more heat flux. Past the critical heat flux, the flux falls as the surface gets hotter.