MEG 307 · Engineering Thermodynamics

Reversed cycles: refrigeration and heat pumps

The reversed Carnot cycle, the vapour-compression cycle on T-s and P-h diagrams, COP and refrigerant mass flow, the gas (reversed Brayton) refrigeration cycle, and heat pumps.

Our notes

2 min read

Reversed Carnot cycle

The ideal limit: COP_R = T_L/(T_H − T_L), COP_HP = T_H/(T_H − T_L) = COP_R + 1. It is impractical (wet compression, isentropic expansion of liquid) but sets the target.
Example: T_L = 268 K (−5 °C), T_H = 308 K (35 °C): COP_R = 268/40 = 6.7, COP_HP = 308/40 = 7.7 (= 6.7 + 1 ✓).

Ideal vapour-compression cycle

1-2 isentropic compression of saturated vapour → superheated vapour; 2-3 condensation at constant pressure (heat out); 3-4 throttling (h₄ = h₃, isenthalpic, irreversible); 4-1 evaporation (heat in from the cold space).

  • Refrigerating effect q_L = h₁ − h₄; compressor work w = h₂ − h₁.
  • COP_R = (h₁ − h₄) ÷ (h₂ − h₁).
  • Refrigerant mass flow ṁ = cooling load ÷ q_L.

Worked example

Rounded enthalpies (illustrative, R-134a-like): h₁ = 395, h₂ = 425, h₃ = h₄ = 250 kJ/kg.
COP = (395 − 250) ÷ (425 − 395) = 145 ÷ 30 ≈ 4.83.
For 3.5 kW of cooling (about one "ton of refrigeration", 3.517 kW): ṁ = 3.5 ÷ 145 ≈ 0.0241 kg/s; compressor power = 0.0241 × 30 ≈ 0.72 kW.
Check: 3.5 ÷ 4.83 ≈ 0.72 kW ✓.

Real cycles

Superheat at the evaporator exit (protects the compressor), subcooling at the condenser exit (more refrigerating effect), pressure drops, non-isentropic compression. Higher condensing temperatures (hot Nigerian afternoons, dirty condenser coils) cut COP: why split units struggle in very hot weather.

Gas refrigeration (reversed Brayton)

Air is compressed, cooled, expanded in a turbine to very low temperature, then absorbs heat. Low COP but light and simple: aircraft cabin cooling; with a regenerator, used for gas liquefaction.

Heat pumps and refrigerants

A heat pump uses the same cycle to deliver heat (water heaters, dryers); COP_HP = q_H ÷ w. Refrigerants are being changed under the Montreal Protocol and Kigali Amendment (2016) to lower ozone and global-warming impact (R-22 phase-out, moves to R-32, R-290 propane, R-600a isobutane in fridges); flammable ones need trained technicians.

Exams usually ask: derive Carnot COPs; analyse the vapour-compression cycle on P-h and T-s diagrams; compute COP, mass flow and power; explain why throttling replaces an expansion engine; describe the gas refrigeration cycle.

Common mistake: writing the refrigerating effect as h₁ − h₃ and the compressor work as h₂ − h₃. Use h₁ − h₄ (with h₄ = h₃) and h₂ − h₁.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.