ENG 213.2 · Basic Electrical Engineering
Our notes
2 min readThree kinds of power
For a load with RMS voltage V, current I and phase angle φ between them:
- Real (active) power P = VI cos φ, in watts (W): does useful work, becomes heat or motion. Only resistance consumes it: P = I²R.
- Reactive power Q = VI sin φ, in volt-amperes reactive (var): energy that surges back and forth into the magnetic fields of inductors and the electric fields of capacitors each cycle. Q = I²X.
- Apparent power S = VI, in volt-amperes (VA): what the supply must deliver in current. S² = P² + Q² (the power triangle).
- Power factor pf = P/S = cos φ: lagging for inductive loads (motors, fluorescent ballasts), leading for capacitive loads.
Example (the RLC circuit of the last topic)
V = 230 V, I = 5.33 A, φ = 45.9° lagging.
- S = 230 × 5.33 ≈ 1,226 VA.
- P = 1,226 × cos 45.9° ≈ 853 W. Check: I²R = 5.33² × 30 ≈ 853 W ✓.
- Q = I²X ≈ 5.33² × 31.0 ≈ 881 var. Check: √(853² + 881²) ≈ 1,226 ✓.
- pf ≈ 0.70 lagging.
Why a low power factor is bad
For the same real power, a low pf needs more current: I = P/(V cos φ).
- Bigger cables, transformers and switchgear (rated in kVA, not kW).
- More I²R loss and voltage drop in lines.
- Utilities charge large industrial users for poor power factor or kVA demand.
Power factor correction
Add capacitors in parallel with an inductive load: they supply the reactive power locally, so the supply carries less.
Method: Q_C = P(tan φ₁ − tan φ₂), then C = Q_C/(V²ω).
Example
A 10 kW motor load at 0.7 pf lagging on 230 V, 50 Hz; correct to 0.95 lagging.
- tan φ₁ = tan(cos⁻¹ 0.7) ≈ 1.020, so Q₁ ≈ 10.2 kvar.
- tan φ₂ = tan(cos⁻¹ 0.95) ≈ 0.329, so Q₂ ≈ 3.29 kvar.
- Q_C ≈ 6.92 kvar.
- C = 6,915/(230² × 314.2) ≈ 4.16 × 10⁻⁴ F ≈ 416 μF.
- Supply current falls from 10,000/(230 × 0.7) ≈ 62.1 A to 10,000/(230 × 0.95) ≈ 45.8 A, with the same 10 kW of real power.
Correcting to exactly 1.0 costs much more capacitance for little gain, and over-correction makes the pf leading.
Other methods
Synchronous motors run over-excited (synchronous condensers), and automatic capacitor banks switched in steps in factories. Power electronics (active filters) also correct pf and harmonics.
Measuring power
A wattmeter measures P directly (it has a current coil and a voltage coil). Energy meters record kWh; many industrial meters also record kvarh or kVA demand.
Exams usually ask
- Compute P, Q, S and pf, and draw the power triangle.
- Explain the disadvantages of low power factor.
- Find the capacitance needed to raise the power factor, and the current saved.
Common mistake
Saying capacitors reduce the real power used. They reduce the current and reactive power from the supply; the load's real power stays the same.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Best pick University Physics Volume 2, 15.4 Power in an AC Circuit
(opens openstax.org in a new tab)
OpenStax, University Physics Volume 2, 15.4 Power in an AC Circuit, CC BY-NC-SA 4.0 · licence
-
Power factor
(opens en.wikipedia.org in a new tab)
Wikipedia, Power factor, CC BY-SA 4.0 · licence
-
AC power
(opens en.wikipedia.org in a new tab)
Wikipedia, AC power, CC BY-SA 4.0 · licence
-
OpenStax, University Physics Volume 2 (whole free textbook)
The whole book, free to read online or download as a PDF (the PDF is large: Wi-Fi).
(opens openstax.org in a new tab)
OpenStax, OpenStax, University Physics Volume 2 (whole free textbook), CC BY-NC-SA 4.0 · licence
Watch
-
What is power factor? (Power in AC circuits) | Alternating current | Physics | Khan Academy
11 min · ≈ 50 MB · about ₦28
(opens youtube.com in a new tab)
-
Power Factor and Reactive Factor in AC Circuit Analysis
13 min · ≈ 59 MB · about ₦33
(opens youtube.com in a new tab)
-
Inductive Reactance, Impedance, & Power Factor - AC Circuits - Physics
13 min · ≈ 59 MB · about ₦33
(opens youtube.com in a new tab)
-
Power in AC Circuit: Instantaneous Power, Average Power, Apparent Power and Power Factor
15 min · ≈ 68 MB · about ₦38
(opens youtube.com in a new tab)
-
Lecture 4: Power Factor
52 min · ≈ 234 MB · about ₦131
(opens youtube.com in a new tab)
We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.