ENG 210.2 · Basic Electrical Engineering
Our notes
2 min readWhy three-phase
A three-phase supply has three voltages of equal size, 120° apart. Compared with single-phase it:
- Transmits more power per kg of conductor.
- Gives a constant total power (smooth running of motors).
- Produces a rotating magnetic field, so three-phase induction motors start themselves.
Nigeria's low-voltage supply is 415 V between lines and about 240 V (nominally 230 V) between line and neutral, 50 Hz. Phases are often coloured red, yellow and blue (R, Y, B).
Phase sequence
v_R = V_m sin ωt, v_Y = V_m sin(ωt − 120°), v_B = V_m sin(ωt − 240°). The order matters: swapping two lines reverses a motor.
Star (Y) connection
One end of each phase joins at the neutral point.
- V_L = √3 V_ph (line voltage between two lines).
- I_L = I_ph.
- Gives two voltages (415 V and 240 V) with a 4-wire system: used for distribution to homes.
- In a balanced load the neutral current is zero.
Delta (Δ) connection
The three phases form a closed triangle; no neutral.
- V_L = V_ph.
- I_L = √3 I_ph.
Used for motor windings and transmission.
Three-phase power
For a balanced load (either connection):
P = √3 V_L I_L cos φ = 3 V_ph I_ph cos φ,
Q = √3 V_L I_L sin φ, S = √3 V_L I_L.
Example
A balanced load of Z = 8 + j6 Ω per phase (|Z| = 10 Ω, pf 0.8 lagging) on a 415 V supply.
Star:
- V_ph = 415/√3 ≈ 239.6 V, I_ph = I_L = 239.6/10 ≈ 23.96 A.
- P = √3 × 415 × 23.96 × 0.8 ≈ 13.78 kW. Check: 3I²R = 3 × 23.96² × 8 ≈ 13.78 kW ✓.
Delta:
- V_ph = 415 V, I_ph = 41.5 A, I_L = √3 × 41.5 ≈ 71.9 A.
- P = 3 × 41.5² × 8 ≈ 41.3 kW: three times the star value.
That is why large motors use star-delta starters: start in star (one-third of the starting current and torque), then switch to delta to run.
Unbalanced loads
Homes on different phases draw different currents, so the neutral carries the difference. A broken neutral on an unbalanced system can give some sockets far more than 240 V and damage appliances: a common cause of burnt equipment.
Measuring three-phase power
The two-wattmeter method (on a 3-wire system): P = W₁ + W₂, and for a balanced load tan φ = √3(W₁ − W₂)/(W₁ + W₂).
Exams usually ask
- State the line and phase relations for star and delta and prove V_L = √3 V_ph.
- Compute currents and power for balanced star and delta loads.
- Explain the two-wattmeter method.
Common mistake
Using P = 3 V_L I_L cos φ. Use √3 with line values, or 3 with phase values, never 3 with line values.
Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.
Read
-
Three-phase electric power
(opens en.wikipedia.org in a new tab)
Wikipedia, Three-phase electric power, CC BY-SA 4.0 · licence
-
Delta–wye transformer
(opens en.wikipedia.org in a new tab)
Wikipedia, Delta–wye transformer, CC BY-SA 4.0 · licence
-
OpenStax, University Physics Volume 2 (whole free textbook)
The whole book, free to read online or download as a PDF (the PDF is large: Wi-Fi).
(opens openstax.org in a new tab)
OpenStax, OpenStax, University Physics Volume 2 (whole free textbook), CC BY-NC-SA 4.0 · licence
Watch
-
Best pick 49 - Voltage, Current and Power in a Balanced 3 - Phase Delta & Star Circuit
27 min · ≈ 122 MB · about ₦69
(opens youtube.com in a new tab)
-
How Three Phase Electricity works - The basics explained
8 min · ≈ 36 MB · about ₦20
(opens youtube.com in a new tab)
-
01 - What is 3-Phase Power? Three Phase Electricity Tutorial
23 min · ≈ 104 MB · about ₦58
(opens youtube.com in a new tab)
-
(E)ENA Ex & Pr 12.1 || Understanding Phase Sequence (Must Watch) || Three-Phase Circuits ||
18 min · ≈ 81 MB · about ₦45
(opens youtube.com in a new tab)
-
Lecture 47: Three phase circuits
35 min · ≈ 158 MB · about ₦89
(opens youtube.com in a new tab)
We link to free material and never copy it. Every link was opened by our team before it went up; video data is a rough guide at 360p.