UNIHIVE

Study Hub UNIPORT ENG 209

ENG 209 · Basic Thermodynamics and Heat Transfer

Convection, boiling and condensation

Newton's law of cooling, the heat transfer coefficient, forced and free convection, dimensionless numbers and correlations, boiling and condensation.

Our notes

2 min read

Newton's law of cooling

Q̇ = hA(T_s − T_∞), with h the convective heat transfer coefficient (W/m²·K).

Situationh (rough range)
Free convection, air2-25
Forced convection, air25-250
Forced convection, water100-20 000
Boiling water2500-100 000
Condensing steam5000-100 000

Example. A 2 m² surface at 60 °C in air at 30 °C with h = 25: Q̇ = 25 × 2 × 30 = 1500 W.

Forced and free convection

  • Forced: a pump, fan or wind moves the fluid.
  • Free (natural): buoyancy moves it (hot air rises from a hot plate).

Dimensionless groups

NumberFormulaMeaning
Reynolds ReρVD/μInertia/viscous forces: laminar or turbulent
Prandtl Prμcp/kMomentum/heat diffusion (air ≈ 0.7, water ≈ 7)
Nusselt NuhL/kConvection/conduction: gives h
Grashof GrgβΔTL³/ν²Buoyancy/viscous (free convection)

Correlations come from experiments: Nu = f(Re, Pr) for forced convection; Nu = f(Gr, Pr) for free.

Worked example: turbulent pipe flow (Dittus-Boelter)

Nu = 0.023 Re^0.8 Pr^0.4 (heating the fluid; Re > 10 000).
Air in a 0.05 m pipe with Re = 50 000, Pr = 0.7, k = 0.026 W/m·K:

  • Re^0.8 = 5744; Pr^0.4 = 0.867
  • Nu = 0.023 × 5744 × 0.867 = 114.5
  • h = Nu k/D = 114.5 × 0.026/0.05 = 59.5 W/m²·K

For laminar fully developed flow with constant wall temperature, Nu = 3.66 (a constant).

Boiling

Pool boiling stages as the surface gets hotter than the saturation temperature: natural convection → nucleate boiling (bubbles form at the surface; very high h) → transition → film boiling (a vapour film insulates the surface). The critical heat flux at the peak of nucleate boiling is a safety limit in boilers: pass it and the tube can burn out.

Condensation

  • Film condensation: a liquid film covers the surface (usual, lower h).
  • Dropwise condensation: drops form and roll off (much higher h, hard to keep).

Condensers in power stations turn exhaust steam back to water.

Exams usually ask: Newton's law of cooling calculations; meaning of Re, Pr, Nu; use a given correlation; the boiling curve.

Common mistake: using the Dittus-Boelter equation for laminar flow. Check Re first.