ENG 209 · Basic Thermodynamics and Heat Transfer

Combined modes, insulation and heat exchangers

The overall heat transfer coefficient, combined convection and radiation, critical insulation radius, and heat exchanger types and LMTD.

Our notes

2 min read

Overall heat transfer coefficient

For heat flowing from a fluid, through a wall, into another fluid, the resistances add:
1/U = 1/h_i + L/k + 1/h_o (plane wall, per m²), and Q̇ = UAΔT_overall.

Example. Room air (h_i = 10), a 0.2 m brick wall (k = 0.7), outside air (h_o = 25):
1/U = 0.1 + 0.2857 + 0.04 = 0.4257 → U = 2.35 W/m²·K. For 10 m² and a 20 K difference: Q̇ = 2.35 × 10 × 20 = 470 W (less than the 700 W for the bare wall faces, because the air films add resistance).

Combined convection and radiation

A hot surface loses heat both ways in parallel: Q̇ = (h_conv + h_rad) A ΔT, with h_rad = εσ(T_s² + T_∞²)(T_s + T_∞). For a pipe at 80 °C in a room, radiation can be as large as free convection.

Insulation

  • Adds resistance; chosen by k, temperature limit, cost, moisture behaviour (glass wool, rock wool, polyurethane foam, calcium silicate).
  • Critical radius of insulation for a pipe: r_c = k/h. Adding insulation to a pipe smaller than r_c actually increases heat loss (the outer surface area grows faster than the resistance). For k = 0.05 and h = 10: r_c = 5 mm. Electrical cables use this to shed heat.
  • Increasing heat transfer: fins (extended surfaces) on motorbike engines and radiators.

Heat exchangers

TypeDescription
Double-pipeOne pipe inside another; simple
Shell-and-tubeMany tubes inside a shell, with baffles; oil and power plants
PlateThin corrugated plates; compact, easy to clean (food, dairy)
Compact / finnedCar radiators, air conditioners

Flow arrangements: parallel flow (both fluids the same direction) and counterflow (opposite: more effective).

Log mean temperature difference

Q̇ = UA ΔT_lm, with ΔT_lm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), where ΔT₁ and ΔT₂ are the temperature differences at the two ends.

Example (counterflow). Hot oil 150 → 90 °C; cold water 30 → 70 °C. ΔT₁ = 150 − 70 = 80 K; ΔT₂ = 90 − 30 = 60 K.
ΔT_lm = 20/ln(80/60) = 20/0.2877 = 69.5 K. For Q̇ = 100 kW and U = 500 W/m²·K: A = 100 000/(500 × 69.5) = 2.88 m².
Check: the LMTD always lies between the two end differences (60 < 69.5 < 80) ✓.

Fouling

Deposits (scale, rust, oil) add a fouling resistance and lower U over time: exchangers are cleaned on a schedule.

Exams usually ask: overall U of a wall or pipe; critical insulation radius; LMTD and exchanger area; parallel versus counterflow.

Common mistake: using the arithmetic mean temperature difference. It overestimates the heat transfer; use the log mean.

Written by the UniHive team in our own words. Spotted a mistake? Tell us on WhatsApp.